SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
Warnings on Refrigerant Leakage
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant
gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than
air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A
is almost non-existent. With the recent increase in the number of high concentration buildings, however, the
installation of multi air conditioner systems is on the increase because of the need for effective use of floor space,
individual control, energy conservation by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can
occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak detection device.The concentration is as given below.
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m
3
.
▼ NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as
charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg.
The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
▼ NOTE 2
The standards for minimum room volume are as follows.
1) No partition (shaded portion)
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
3
)
≤ Concentration limit (kg/m
3
)
e.g., charged amount (10 kg)
e.g., charged amount (15 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the
door).
3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with
a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next
smallest room becomes the object.
▼ NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows:
(When the ceiling is 2.7 m high)
Important
Refrigerant piping
Indoor unit
Outdoor unit
Outdoor unit
Very small room
Refrigerant piping
Indoor unit
Mechanical ventilation device - Gas leak detector
Small
room
Medium
room
Large room
0
5
10
10 20 30
15
20
25
30
35
40
m
2
kg
Min. indoor floor area
Range above the
density limit of 0.3 kg/m
3
(countermeasures
needed)
Range below the
density limit of
0.3 kg/m
3
(countermeasures
not needed)
Total amount of refrigerant
53-EN 54-EN
+00EH99879301_01EN.book Page 27 Tuesday, March 15, 2011 8:42 PM
Содержание
- Installation manual p.1
- Original instruction p.2
- Maintenance 19 p.2
- Installation 7 p.2
- Generic denomination air conditioner p.2
- Electrical connection 14 p.2
- Duct design 10 p.2
- Troubleshooting 21 p.2
- Drain piping 8 p.2
- This air conditioner uses r410a an environmentally friendly refrigerant p.2
- Definition of qualified installer or qualified service person the air conditioner must be installed maintained repaired and removed by a qualified installer or qualified service person when any of these jobs is to be done ask a qualified installer or qualified service person to do them for you a qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below p.2
- Thank you for purchasing this toshiba air conditioner please read carefully through these instructions that contain important information which complies with the machinery directive directive 2006 42 ec and ensure that you understand them after completing the installation work hand over this installation manual as well as the owner s manual attached to the outdoor unit provided with the outdoor unit to the user and ask the user to keep them in a safe place for future reference p.2
- Contents p.2
- Test run 18 p.2
- Applicable controls 16 p.2
- Specifications 26 p.2
- Adoption of new refrigerant p.2
- Smms slim duct type installation manual smms slim duct type installation manual p.2
- Accessory parts 4 p.2
- Selection of installation place 5 p.2
- Refrigerant piping 13 p.2
- Precautions for safety 3 p.2
- Please read this installation manual carefully before installing the air conditioner p.2
- Warning p.3
- Stop the unit before the servicing p.3
- Open the service valves before the operation otherwise there might be the burst p.3
- Moving parts do not operate unit with grille removed p.3
- Electrical shock hazard p.3
- Caution p.3
- Warning indications on the air conditioner unit p.3
- Warning p.4
- The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual p.4
- Smms slim duct type installation manual smms slim duct type installation manual p.4
- Selection of installation location p.4
- Refrigerant piping p.4
- Precautions for safety p.4
- Installation p.4
- General p.4
- Electrical wiring p.4
- Caution p.5
- Accessory parts p.5
- Selection of installation place p.6
- Installation under high humidity atmosphere p.6
- Installation space p.6
- Avoid installing in the following places p.6
- The lighting term setup of the filter sign notification of filter cleaning of the remote controller can be changed according to the condition of installation for setup method refer to filter sign setting in the applicable controls of this manual p.7
- Smms slim duct type installation manual p.7
- Service space p.7
- Filter cleaning sign term setting p.7
- Arranging the to back air intake type p.7
- Installation of hanging bolt p.8
- Installation p.8
- External dimensions p.8
- Caution p.8
- Wireless remote controller p.9
- Installation of remote p.9
- Installation of indoor unit p.9
- Flexible hose p.9
- Drain piping p.9
- Controller sold separately p.9
- After the electric work has finished pour water during cool mode operation if the electric work has not yet finished pull out the float switch connector cn34 red from the electrical control box and check draining by plugging the single phase 220 240 v power to the terminal blocks r l and s n if doing so the drain pump motor operates test water drain while checking the operation sound of the drain pump motor if the operation sound changes from continuous sound to intermittent sound water is normally drained after the check the drain pump motor runs connecting the float switch connector in case of check by pulling out the float switch connector be sure to return the connector to the original position p.10
- When a down gradient cannot be secured for the drainpipe drain up piping is possible the height of the drain pipe must be 850 mm or less from the bottom of the ceiling take the drain pipe out of the drain pipe joint with the indoor unit in 300 mm or less and bend up the pipe vertically immediately after the pipe is bent up vertically lay the pipe making a down gradient set downward grading immediately after raising up vertically p.10
- Smms slim duct type installation manual smms slim duct type installation manual p.10
- Requirement p.10
- Pour water gently so that it does not spread around inside the indoor unit which may cause a malfunction p.10
- In the test run check that water drain is properly performed and water does not leak from the connecting part of the pipes check draining also when installed in heating period by using a pitcher or hose pour water 1500 2000 cc into the discharge port before installation of the ceiling panel pour water gradually so that water does not spread on the motor of the drain pump p.10
- Drain up p.10
- Connecting drain pipe p.10
- Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage it takes some time until the adhesive is dried and hardened refer to the manual of the adhesive do not apply stress to the joint with the drain pipe during this time period p.10
- Connect a hard socket locally procured to the hard socket of the attached supplied flexible hose connect a drain pipe locally procured to the connected hard socket p.10
- Check the draining p.10
- Caution p.10
- Perform heat insulating p.11
- Duct design p.11
- Arrangement p.11
- Connecting method of the duct p.12
- Caution p.12
- Smms slim duct type installation manual smms slim duct type installation manual p.12
- Mount an air filter to the air intake side otherwise decrease of capacity may be caused p.12
- Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop p.12
- No filter p.13
- Filter attached p.13
- Fan characteristics p.13
- 00eh99879301_01en book page 12 tuesday march 15 2011 8 42 pm p.13
- Permissible piping length and p.14
- Open the valve fully p.14
- Height difference p.14
- Heat insulation process p.14
- Flaring diameter size a unit mm p.14
- Flaring p.14
- Connecting refrigerant piping p.14
- Caution p.14
- Airtight test air purge etc p.14
- Refrigerant piping p.14
- Projection margin in flaring b unit mm p.14
- Pipe size p.14
- Power supply wire and communication wires specifications p.15
- Electrical connection p.15
- Wiring example p.16
- Wiring between indoor and outdoor units p.16
- Wire connection p.16
- Smms slim duct type installation manual smms slim duct type installation manual p.16
- Requirement p.16
- Before remove the electrical control box cover remove the cover plate and air filter remove the cover of the electrical control box by taking off the mounting screws 2 positions and pushing the hooking section the cover of the electrical control box remains hanged to the hinge tighten the screws of the terminal block and fix the wires with cord clamp attached to the electrical control box do not apply tension to the connecting section of the terminal block set a loop for the connecting wire of the storing part of the indoor unit electric parts otherwise the electrical control box cannot be drawn out in service time mount the cover of the electrical control box without pinching wires p.16
- An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit p.16
- Change the settings while the air conditioner is not working stop the air conditioner before making settings p.17
- Basic procedure for changing p.17
- Applicable controls p.17
- Address setup p.17
- Wiring diagram p.17
- Strip off approx 9 mm the wire to be connected p.17
- Smms slim duct type installation manual p.17
- Settings p.17
- Set up the addresses as per the installation manual supplied with the outdoor unit p.17
- Requirement p.17
- Remote controller wiring p.17
- Push and hold button and temp button simultaneously for at least 4 seconds after a while the display flashes as shown in the figure confirm that the code no is 01 p.17
- If the code no is not 01 push button to clear the display content and repeat the procedure from the beginning no operation of the remote controller is accepted for a while after button is pushed while air conditioners are operated under the group control all is displayed first when is pushed the indoor unit number displayed following all is the header unit p.17
- External static pressure settings p.18
- Test run p.19
- Maintenance p.20
- Mount the air filter p.21
- Maintenance list p.21
- Caution p.21
- After cleaning push p.21
- Turn on the circuit breaker then push the button on the remote controller to start the operation p.21
- Periodic maintenance p.21
- Troubleshooting p.22
- Confirmation of error log p.22
- Confirmation and check p.22
- The following list shows each check code find the check contents from the list according to part to be checked in case of check from indoor remote controller see wired remote controller display in the list in case of check from outdoor unit see outdoor unit 7 segment display in the list in case of check from ai net central control remote controller see ai net central control display in the list in case of check from indoor unit with a wireless remote controller see sensor block display of receiving unit in the list lighting flashing goes off ai net artificial intelligence ipdu intelligent power drive unit alt flashing is alternately when there are two flashing led sim simultaneous flashing when there are two flashing led p.23
- Smms slim duct type installation manual p.23
- On the wired remote controller central control remote controller and the interface p c board of the outdoor unit i f a check display lcd remote controller or 7 segment display on the outdoor interface p c board to display the operation is provided therefore the operation status can be known using this self diagnosis function a trouble or position with error of the air conditioner can be found as shown in the table below p.23
- Check method p.23
- Check code list p.23
- Smms slim duct type installation manual smms slim duct type installation manual p.24
- Smms slim duct type installation manual p.25
- Smms slim duct type installation manual smms slim duct type installation manual p.26
- Error detected by tcc link central control device p.26
- Specifications p.27
- Declaration of conformity p.27
- Warnings on refrigerant leakage p.28
- Note 3 p.28
- Note 2 p.28
- Note 1 p.28
- Important p.28
- Check of concentration limit p.28
- Smms slim duct type installation manual p.29
- Requirement p.29
- Prior to delivery to the customer check the address and setup of the indoor unit which has been installed in this time and fill the check sheet table below data of four units can be entered in this check sheet copy this sheet according to the no of the indoor units if the installed system is a group control system use this sheet by entering each line system into each installation manual attached to the other indoor units p.29
- Indoor unit setup check sheet p.29
- Confirmation of indoor unit setup p.29
Похожие устройства
-
Toshiba MMK-AP0074MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0094MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0124MH-EИнструкция по эксплуатации -
Toshiba MMD-AP0156BH-EБрошюра -
Toshiba MMD-AP0156BH-EИнструкция по эксплуатации -
Toshiba MMD-AP0126BHP-EИнструкция по эксплуатации -
Toshiba MMC-AP0364H-EБрошюра -
Toshiba MMC-AP0364H-EИнструкция по эксплуатации -
Toshiba MMC-AP0244H-EБрошюра -
Toshiba MMC-AP0244H-EИнструкция по эксплуатации -
Toshiba MMC-AP0274H-EБрошюра -
Toshiba MMC-AP0274H-EИнструкция по эксплуатации
Узнайте, как правильно установить многоканальные кондиционеры, чтобы избежать утечек хладагента и обеспечить безопасность. Важные рекомендации и требования.