SMMS Slim Duct Type
Installation Manual
SMMS Slim Duct Type
Installation Manual
1 Precautions for Safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this
manual.
WARNING
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions
to install the air conditioner.
• Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in
water leakage, electric shock or fire.
• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally
high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or
an injury to your body.
• Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the
OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with
the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the intake grille of
the indoor unit or service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, set the circuit breaker to the OFF position.
Otherwise, electric shocks may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work
is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of
50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the unit. You may injure yourself if you do so. If the fin must be touched for some
reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor
unit and result in injury.
• When work is performed at heights, use a ladder which complies with the ISO 14122 standard, and follow the
procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
• Before cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a
“Work in progress” sign near the circuit breaker before proceeding with the work.
• Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with
the work. Parts and other objects may fall from above, possibly injuring a person below. While carrying out the work,
wear a helmet for protection from falling objects.
• The refrigerant used by this air conditioner is the R410A.
• The air conditioner must be transported in stable condition. If any part of the product is broken, contact the dealer.
• When the air conditioner must be transported by hand, carry it by two or more people.
• Do not move or repair any unit by yourself. There is high voltage inside the unit. You may get electric shock when
removing the cover and main unit.
Selection of installation location
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration
of refrigerant leakage occur in the room does not exceed the critical level.
• Do not install in a location where flammable gas leaks are possible. If the gas leak and accumulate around the unit,
it may ignite and cause a fire.
• To transport the air conditioner, wear shoes with additional protective toe caps.
• To transport the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if
the bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive
electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise
it may cause imperfect combustion.
Installation
• Suction duct length must be longer than 850 mm.
• When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must
be used.
• Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is
not enough, the unit may fall down resulting in injury.
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may
cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.
• Carry out the specified installation work to guard against the possibility of high winds and earthquake. If the air
conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas
comes in contact with fire, noxious gas may generate.
• Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.
• Helmet must be worn to protect your head from falling objects.
Especially, when you work under an inspection opening, helmet must be worn to protect your head from falling
objects from the opening.
• The unit can be accessed from the service panel shown in the figure.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor
is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is
over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a
crack in the flare nut after a long period, which may result in refrigerant leakage.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows
near a fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge
the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge
the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air
conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the
work properly may result in electric shocks and / or electrical leaks.
• To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide
protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and
laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage,
smoking and / or a fire.
• Connect earth wire. (Grounding work)
Incomplete grounding causes an electric shock.
• Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires.
• After completing the repair or relocation work, check that the earth wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local
regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is
extended may give rise to smoking and / or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
5-EN 6-EN
+00EH99879301_01EN.book Page 3 Tuesday, March 15, 2011 8:42 PM
Содержание
- Installation manual 1
- Accessory parts 4 2
- Adoption of new refrigerant 2
- Applicable controls 16 2
- Contents 2
- Definition of qualified installer or qualified service person the air conditioner must be installed maintained repaired and removed by a qualified installer or qualified service person when any of these jobs is to be done ask a qualified installer or qualified service person to do them for you a qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below 2
- Drain piping 8 2
- Duct design 10 2
- Electrical connection 14 2
- Generic denomination air conditioner 2
- Installation 7 2
- Maintenance 19 2
- Original instruction 2
- Please read this installation manual carefully before installing the air conditioner 2
- Precautions for safety 3 2
- Refrigerant piping 13 2
- Selection of installation place 5 2
- Smms slim duct type installation manual smms slim duct type installation manual 2
- Specifications 26 2
- Test run 18 2
- Thank you for purchasing this toshiba air conditioner please read carefully through these instructions that contain important information which complies with the machinery directive directive 2006 42 ec and ensure that you understand them after completing the installation work hand over this installation manual as well as the owner s manual attached to the outdoor unit provided with the outdoor unit to the user and ask the user to keep them in a safe place for future reference 2
- This air conditioner uses r410a an environmentally friendly refrigerant 2
- Troubleshooting 21 2
- Caution 3
- Electrical shock hazard 3
- Moving parts do not operate unit with grille removed 3
- Open the service valves before the operation otherwise there might be the burst 3
- Stop the unit before the servicing 3
- Warning 3
- Warning indications on the air conditioner unit 3
- Electrical wiring 4
- General 4
- Installation 4
- Precautions for safety 4
- Refrigerant piping 4
- Selection of installation location 4
- Smms slim duct type installation manual smms slim duct type installation manual 4
- The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual 4
- Warning 4
- Accessory parts 5
- Caution 5
- Avoid installing in the following places 6
- Installation space 6
- Installation under high humidity atmosphere 6
- Selection of installation place 6
- Arranging the to back air intake type 7
- Filter cleaning sign term setting 7
- Service space 7
- Smms slim duct type installation manual 7
- The lighting term setup of the filter sign notification of filter cleaning of the remote controller can be changed according to the condition of installation for setup method refer to filter sign setting in the applicable controls of this manual 7
- Caution 8
- External dimensions 8
- Installation 8
- Installation of hanging bolt 8
- Controller sold separately 9
- Drain piping 9
- Flexible hose 9
- Installation of indoor unit 9
- Installation of remote 9
- Wireless remote controller 9
- After the electric work has finished pour water during cool mode operation if the electric work has not yet finished pull out the float switch connector cn34 red from the electrical control box and check draining by plugging the single phase 220 240 v power to the terminal blocks r l and s n if doing so the drain pump motor operates test water drain while checking the operation sound of the drain pump motor if the operation sound changes from continuous sound to intermittent sound water is normally drained after the check the drain pump motor runs connecting the float switch connector in case of check by pulling out the float switch connector be sure to return the connector to the original position 10
- Caution 10
- Check the draining 10
- Connect a hard socket locally procured to the hard socket of the attached supplied flexible hose connect a drain pipe locally procured to the connected hard socket 10
- Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage it takes some time until the adhesive is dried and hardened refer to the manual of the adhesive do not apply stress to the joint with the drain pipe during this time period 10
- Connecting drain pipe 10
- Drain up 10
- In the test run check that water drain is properly performed and water does not leak from the connecting part of the pipes check draining also when installed in heating period by using a pitcher or hose pour water 1500 2000 cc into the discharge port before installation of the ceiling panel pour water gradually so that water does not spread on the motor of the drain pump 10
- Pour water gently so that it does not spread around inside the indoor unit which may cause a malfunction 10
- Requirement 10
- Smms slim duct type installation manual smms slim duct type installation manual 10
- When a down gradient cannot be secured for the drainpipe drain up piping is possible the height of the drain pipe must be 850 mm or less from the bottom of the ceiling take the drain pipe out of the drain pipe joint with the indoor unit in 300 mm or less and bend up the pipe vertically immediately after the pipe is bent up vertically lay the pipe making a down gradient set downward grading immediately after raising up vertically 10
- Arrangement 11
- Duct design 11
- Perform heat insulating 11
- Caution 12
- Connecting method of the duct 12
- Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop 12
- Mount an air filter to the air intake side otherwise decrease of capacity may be caused 12
- Smms slim duct type installation manual smms slim duct type installation manual 12
- 00eh99879301_01en book page 12 tuesday march 15 2011 8 42 pm 13
- Fan characteristics 13
- Filter attached 13
- No filter 13
- Airtight test air purge etc 14
- Caution 14
- Connecting refrigerant piping 14
- Flaring 14
- Flaring diameter size a unit mm 14
- Heat insulation process 14
- Height difference 14
- Open the valve fully 14
- Permissible piping length and 14
- Pipe size 14
- Projection margin in flaring b unit mm 14
- Refrigerant piping 14
- Electrical connection 15
- Power supply wire and communication wires specifications 15
- An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit 16
- Before remove the electrical control box cover remove the cover plate and air filter remove the cover of the electrical control box by taking off the mounting screws 2 positions and pushing the hooking section the cover of the electrical control box remains hanged to the hinge tighten the screws of the terminal block and fix the wires with cord clamp attached to the electrical control box do not apply tension to the connecting section of the terminal block set a loop for the connecting wire of the storing part of the indoor unit electric parts otherwise the electrical control box cannot be drawn out in service time mount the cover of the electrical control box without pinching wires 16
- Requirement 16
- Smms slim duct type installation manual smms slim duct type installation manual 16
- Wire connection 16
- Wiring between indoor and outdoor units 16
- Wiring example 16
- Address setup 17
- Applicable controls 17
- Basic procedure for changing 17
- Change the settings while the air conditioner is not working stop the air conditioner before making settings 17
- If the code no is not 01 push button to clear the display content and repeat the procedure from the beginning no operation of the remote controller is accepted for a while after button is pushed while air conditioners are operated under the group control all is displayed first when is pushed the indoor unit number displayed following all is the header unit 17
- Push and hold button and temp button simultaneously for at least 4 seconds after a while the display flashes as shown in the figure confirm that the code no is 01 17
- Remote controller wiring 17
- Requirement 17
- Set up the addresses as per the installation manual supplied with the outdoor unit 17
- Settings 17
- Smms slim duct type installation manual 17
- Strip off approx 9 mm the wire to be connected 17
- Wiring diagram 17
- External static pressure settings 18
- Test run 19
- Maintenance 20
- After cleaning push 21
- Caution 21
- Maintenance list 21
- Mount the air filter 21
- Periodic maintenance 21
- Turn on the circuit breaker then push the button on the remote controller to start the operation 21
- Confirmation and check 22
- Confirmation of error log 22
- Troubleshooting 22
- Check code list 23
- Check method 23
- On the wired remote controller central control remote controller and the interface p c board of the outdoor unit i f a check display lcd remote controller or 7 segment display on the outdoor interface p c board to display the operation is provided therefore the operation status can be known using this self diagnosis function a trouble or position with error of the air conditioner can be found as shown in the table below 23
- Smms slim duct type installation manual 23
- The following list shows each check code find the check contents from the list according to part to be checked in case of check from indoor remote controller see wired remote controller display in the list in case of check from outdoor unit see outdoor unit 7 segment display in the list in case of check from ai net central control remote controller see ai net central control display in the list in case of check from indoor unit with a wireless remote controller see sensor block display of receiving unit in the list lighting flashing goes off ai net artificial intelligence ipdu intelligent power drive unit alt flashing is alternately when there are two flashing led sim simultaneous flashing when there are two flashing led 23
- Smms slim duct type installation manual smms slim duct type installation manual 24
- Smms slim duct type installation manual 25
- Error detected by tcc link central control device 26
- Smms slim duct type installation manual smms slim duct type installation manual 26
- Declaration of conformity 27
- Specifications 27
- Check of concentration limit 28
- Important 28
- Note 1 28
- Note 2 28
- Note 3 28
- Warnings on refrigerant leakage 28
- Confirmation of indoor unit setup 29
- Indoor unit setup check sheet 29
- Prior to delivery to the customer check the address and setup of the indoor unit which has been installed in this time and fill the check sheet table below data of four units can be entered in this check sheet copy this sheet according to the no of the indoor units if the installed system is a group control system use this sheet by entering each line system into each installation manual attached to the other indoor units 29
- Requirement 29
- Smms slim duct type installation manual 29
Похожие устройства
- Toshiba MMD-AP0124SPH-E Брошюра
- Toshiba MMD-AP0246BH-E Инструкция по эксплуатации
- Toshiba MMD-AP0246BH-E Брошюра
- Toshiba MMD-AP0276BH-E Инструкция по эксплуатации
- Toshiba MMD-AP0276BH-E Брошюра
- Toshiba MMD-AP0096BHP-E Инструкция по эксплуатации
- Toshiba MMC-AP0184H-E Инструкция по эксплуатации
- Toshiba MMC-AP0184H-E Брошюра
- Toshiba MMD-AP0186BHP-E Инструкция по эксплуатации
- Toshiba MMC-AP0274H-E Инструкция по эксплуатации
- Toshiba MMC-AP0274H-E Брошюра
- Toshiba MMC-AP0244H-E Инструкция по эксплуатации
- Toshiba MMC-AP0244H-E Брошюра
- Toshiba MMC-AP0364H-E Инструкция по эксплуатации
- Toshiba MMC-AP0364H-E Брошюра
- Toshiba MMD-AP0126BHP-E Инструкция по эксплуатации
- Toshiba TCB-SC642TLE2 Инструкция по эксплуатации
- Toshiba TCB-SC642TLE2 Брошюра
- Toshiba TCB-SC642TLE2 Каталог пультов управления Toshiba (англ.)
- Toshiba MMD-AP0156BH-E Инструкция по эксплуатации