–14–
▼ Power supply
Control wiring, Central controller wiring
• 2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central
controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and
outdoor units added with the central control system wire length.
▼ Communication line
Remote controller wiring
• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
CAUTION
The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be parallel to contact
each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control
system due to noise or other factor.
Power supply
220 V – 240 V ~, 50 Hz
220 V ~, 60 Hz
Power supply switch/circuit breaker or power supply wiring/fuse rating for indoor units should be selected by the accumulated
total current values of the indoor units.
Power supply wiring Below 50 m 2.5 mm
2
Control wiring between indoor units, and
outdoor unit (2-core shield wire)
Wire size
(Up to 1000 m) 1.25 mm²
(Up to 2000 m) 2.0 mm²
Central control line wiring (2-core shield
wire)
Wire size
(Up to 1000 m) 1.25 mm²
(Up to 2000 m) 2.0 mm²
Remote controller wiring, remote controller inter-unit
wiring
Wire size: 0.5 mm² to 2.0 mm²
Total wire length of remote controller wiring and remote
controller inter-unit wiring = L + L1 + L2 + … Ln
In case of wired type only Up to 500 m
In case of wireless type
included
Up to 400 m
Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln Up to 200 m
L1
L
L2 Ln
Indoor unit
Remote controller inter-unit wiring
Indoor unit Indoor unit Indoor unit
Remote
controller
(Max. 8 units)
Remote
controller
wiring
Wiring between indoor unit and outdoor unit
NOTE
An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the
header unit.
▼ Wiring example
U1 U2
U1 U2 U3 U4L1 L2 L3 N U5 U6
LN AB
AB
U1 U2 U3 U4L1 L2 L3 N U5 U6
U1 U2LN AB
AB
U1 U2LN AB
AB
U1 U2LN AB
Outdoor Power supply
380 V - 415 V ~, 50 Hz
380 V ~, 60 Hz
Circuit breaker,
Power switch
Remote controller
Indoor unit
Outdoor Power supply
380 V - 415 V ~, 50 Hz
380 V ~, 60 Hz
Remote controller Remote controller
Indoor unit Indoor unit Indoor unit
Circuit breaker Circuit breaker
Header outdoor
unit
Follower outdoor
unit
Control wiring between outdoor units
Control wiring between indoor and outdoor units
Control wiring between indoor units
Indoor power supply
220 V - 240 V ~, 50 Hz
220 V ~, 60 Hz
Earth Earth Earth Earth
Group control
Pull boxPull boxPull box
Earth
terminal
Earth
terminal
27-EN 28-EN
Содержание
- Accessory parts p.2
- Contents p.2
- This air conditioner uses r410a an environmentally friendly refrigerant p.2
- Applicable controls 5 p.2
- Thank you for purchasing this toshiba air conditioner please read carefully through these instructions that contain important information which complies with the machinery directive directive 2006 42 ec and ensure that you understand them after completing the installation work hand over this installation manual as well as the owner s manual provided to the user and ask the user to keep them in a safe place for future reference p.2
- Adoption of new refrigerant p.2
- Test run 7 p.2
- Specifications 4 p.2
- Selection of installation place p.2
- Refrigerant piping 2 p.2
- Precautions for safety p.2
- Please read this installation manual carefully before installing the air conditioner p.2
- Original instruction p.2
- Maintenance 8 p.2
- Installation p.2
- Generic denomination air conditioner p.2
- Electrical connection 3 p.2
- Duct design 1 p.2
- Drain piping p.2
- Definition of qualified installer or qualified service person the air conditioner must be installed maintained repaired and removed by a qualified installer or qualified service person when any of these jobs is to be done ask a qualified installer or qualified service person to do them for you a qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the following table p.2
- Troubleshooting 9 p.2
- Warning indications on the air conditioner unit p.3
- Warning p.3
- Stop the unit before the servicing p.3
- Open the service valves before the operation otherwise there might be the burst p.3
- Caution p.3
- Burst hazard p.3
- Installation p.4
- Warning p.4
- The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual p.4
- Selection of installation location p.4
- Refrigerant piping p.4
- Precautions for safety p.4
- General p.4
- Electrical wiring p.4
- Accessory parts p.5
- Caution p.5
- Selection of installation place p.6
- Installation under high humidity atmosphere p.6
- Avoid installing in the following places p.6
- Installation space p.7
- Installation p.7
- Filter cleaning sign term setting p.7
- External dimensions p.7
- Caution p.7
- Mount the supplied rail to the bottom then set the filter p.8
- Mount the filter stopper p.8
- Mount the filter rail so that the hooks fit into the corresponding holes note that the upper and lower filter rails are not identical p.8
- Installation of indoor unit p.8
- Installation of hanging bolt p.8
- Changing from back air intake to under air intake p.8
- Caution p.8
- Treatment of ceiling p.8
- Slide and push the filters until it stop p.8
- Remove the suction board cover attached to the bottom and screw it to the back of unit p.8
- Remove the filters on back of unit p.8
- Mounting filter rails and filters p.8
- Pipe material size and insulator p.9
- Gravitational drainage p.9
- Drain up p.9
- Drain piping p.9
- Connecting drain pipe p.9
- Check the draining p.10
- When the electrical and wiring work has not been completed p.10
- When the electrical and wiring work has been completed p.10
- Heat insulating process p.10
- Connecting method of the duct p.10
- Caution p.10
- High tap 50pa p.11
- High tap 40pa p.11
- High tap 30pa standard filter pressure loss p.11
- High tap 30pa p.11
- High tap 120pa p.11
- High tap 100pa p.11
- Fan characteristics p.11
- External static pressure pa p.11
- Upper limit of external static pessure 120pa lower limit of external static pessure 120pa p.11
- En 20 en p.11
- Upper limit of external static pessure 120pa p.11
- Ap0306 type ap0336 type ap0486 ap0566 type p.11
- Standard filter pressure loss p.11
- Ap0076 type ap0096 ap0126 type ap0156 ap0186 type ap0246 ap0276 type p.11
- Lower limit of external static pessure 120pa p.11
- Air volume p.11
- Low tap 120pa high tap 100pa p.11
- 480 580 680 780 880 980 p.11
- Low tap 120pa p.11
- 300 400 500 600 700 800 p.11
- 1200 1400 1600 1800 2000 2200 2400 2600 p.11
- High tap 80pa p.11
- 1100 1300 1500 1700 1900 2100 2300 2500 p.11
- High tap 65pa p.11
- Duct design p.12
- Arrangement p.12
- Ap0246 ap0276 ap0306 ap0366 ap0486 ap0566 p.12
- Ap0156 ap0186 p.12
- Ap0076 ap0096 ap0126 p.12
- Evacuation p.13
- Connecting refrigerant piping p.13
- Caution p.13
- Refrigerant piping p.13
- Refrigerant amount to be added p.13
- Projection margin in flaring b unit mm p.13
- Pipe size p.13
- Permissible piping length and p.13
- Open the valve fully p.13
- Height difference p.13
- Gas leak check p.13
- Flaring diameter size a unit mm p.13
- Flaring p.13
- Specifications p.14
- Power supply wire and communication wires p.14
- Indoor unit power supply p.14
- Heat insulation process p.14
- Electrical connection p.14
- Caution p.14
- Warning p.14
- Wiring example p.15
- Wiring between indoor unit and outdoor unit p.15
- The remote controller wire communication line and ac 220 240 v wires cannot be parallel to contact each other and cannot be stored in the same conduits if doing so a trouble may be caused on the control system due to noise or other factor p.15
- Remote controller wiring p.15
- Power supply p.15
- Control wiring central controller wiring p.15
- Communication line p.15
- Caution p.15
- An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit p.15
- 2 core with polarity wires are used for the control wiring between indoor unit and outdoor unit and central controller wiring to prevent noise trouble use 2 core shield wire the length of the communication line means the total length of the inter unit wire length between indoor and outdoor units added with the central control system wire length p.15
- 2 core with non polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring p.15
- Remote controller wiring p.16
- Push and hold button and temp button simultaneously for 4 seconds or more after a while the display flashes as shown in the figure confirm that the code no is 01 p.16
- Basic procedure for changing p.16
- Applicable controls p.16
- Wire connection p.16
- Settings p.16
- Settings p.17
- External static pressure p.17
- Test run p.18
- Maintenance p.19
- Troubleshooting p.20
- Confirmation of error log p.20
- Confirmation and check p.20
- The following list shows each check code find the check contents from the list according to part to be checked in case of check from indoor remote controller see wired remote controller display in the list in case of check from outdoor unit see outdoor unit 7 segment display in the list in case of check from ai net central control remote controller see ai net central control display in the list in case of check from indoor unit with a wireless remote controller see sensor block display of receiving unit in the list lighting flashing goes off ai net artificial intelligence ipdu intelligent power drive unit alt flashing is alternately when there are two flashing led sim simultaneous flashing when there are two flashing led p.21
- On the wired remote controller central control remote controller and the interface p c board of the outdoor unit i f a check display lcd remote controller or 7 segment display on the outdoor interface p c board to display the operation is provided therefore the operation status can be known using this self diagnosis function a trouble or position with error of the air conditioner can be found as shown in the following table p.21
- Check method p.21
- Check code list p.21
- Error detected by tcc link central control device p.24
- Specifications p.25
- Declaration of conformity p.25
- Warnings on refrigerant leakage p.26
- Note 3 p.26
- Note 2 p.26
- Note 1 p.26
- Important p.26
- Check of concentration limit p.26
- Requirement p.27
- Prior to delivery to the customer check the address and setup of the indoor unit which has been installed in this time and fill the check sheet following table data of four units can be entered in this check sheet copy this sheet according to the no of the indoor units if the installed system is a group control system use this sheet by entering each line system into each installation manual attached to the other indoor units p.27
- Indoor unit setup check sheet p.27
- Confirmation of indoor unit setup p.27
Похожие устройства
-
Toshiba MMK-AP0074MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0094MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0124MH-EИнструкция по эксплуатации -
Toshiba MMD-AP0156BH-EБрошюра -
Toshiba MMD-AP0156BH-EИнструкция по эксплуатации -
Toshiba MMD-AP0126BHP-EИнструкция по эксплуатации -
Toshiba MMC-AP0364H-EБрошюра -
Toshiba MMC-AP0364H-EИнструкция по эксплуатации -
Toshiba MMC-AP0244H-EБрошюра -
Toshiba MMC-AP0244H-EИнструкция по эксплуатации -
Toshiba MMC-AP0274H-EБрошюра -
Toshiba MMC-AP0274H-EИнструкция по эксплуатации