Toshiba MMK-AP0074MH-E [80/102] Wiring connection for the flow selector unit

Toshiba MMK-AP0074MH-E [80/102] Wiring connection for the flow selector unit
80
SMMS High-Wall Type
Installation Manual
– 25 –
Wiring connection
How to connect the power supply wiring
and control wiring
1. Remove the air intake grille.
Open the air intake grille upward and pull it
toward you.
2. Remove the four screws securing the front
panel.
3. Slightly open the lower part of the front
panel then pull the upper part of the front
panel toward you to remove it from the rear
plate.
4. Remove the terminal cover.
5. Insert the power supply wire and control
wire (according to the local rule) into the
pipe hole on the wall.
6. Take the power supply wire and the control
wire out of the cable slot on the rear panel
so that it protrudes about 150 mm from the
front.
7. Insert the power supply wire fully into the
terminal block and secure it tightly with
screws. Tightening torque: 1.2 N·m (0.12
kgf·m) Secure the earth line with the earth
screw.
8. Insert the control wire fully into the control /
wired remote controller terminal block ,
, , and secure it tightly with screws.
9. Clamp the power supply wire and the
control wire with the cord clamp.
10.Attach the terminal cover, the front panel
and the air intake grille to the indoor unit.
CAUTION
Refer to the wiring diagram attached inside the
front panel.
Check local electrical cords and also any
specific w
iring instructions and limitations.
3
1
2
Air intake grille
Front panel
U1
NL
U2 A B
U1NLU2AB
R(L) S(N)
>
ABS
<
NL
Terminal cover
Cord clamp
Screw
Earth screw
10 mm
10 mm
40 mm
110 mm
Power supply
wire
Control wire
Terminal block
for control /
wired remote
controller wiring
Power supply
terminal block
Terminal block
Notch
Cord clamp
A B
25-EN
SMMS High-Wall Type
Installation Manual
– 26 –
EN
Wiring connection for the flow selector unit
Connect the wiring of the flow selector unit
Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor
unit.
Slit of the
terminal block
Earth line
Cord clamp
Power supply wire of
flow selector unit
Wiring cover
Terminal
block
Control wire
Screw
Control wire from
the flow selector
unit
Terminal
block
Screw
Screw
1. Remove the air intake grille.
Open the air intake grille upward and pull it toward you.
2. Remove the four screws securing the front panel.
3. Slightly open the lower part of the front panel, and then pull the upper part of the front panel
toward you to remove it from the rear plate.
4. Remove the wiring cover and cord clamp for right side of indoor unit.
5. Insert the power supply wire fully into the terminal block and secure it tightly with screws.
Tightening torque: 1.2 N·m (0.12 kgf·m)
Secure the earth line with the earth screw.
6. Connect the control wire connector of the flow selector unit to the lead with a connector to the
under of the terminal block.
7. Take the control wire outwards through the slit of the terminal block.
8. Clamp the power supply wire and control wire of the flow selector unit tight with the cord clamp.
9. Attach the wiring cover, the front panel and the air intake grille to the indoor unit.
CAUTION
Confirm that every wires are stored in the electrical control box without getting caught before attaching the
terminal cover.
26-EN

Содержание