Nibe F470 Инструкция по эксплуатации онлайн
Содержание
- Exhaust air heat pump 1
- Nibe f470 1
- User manual 1
- In event of disturbances in comfort 2
- Disturbances in comfort 62 3
- F470 at your service 31 3
- Important information 2 3
- Item register 73 3
- Table of contents 3
- Technical data 67 6 glossary 68 3
- The heat pump the heart of the house 8 3
- Certification that the installation is carried out according to instructions in nibe s installer manual and applicable regulations 4
- Important information 4
- Installation data 4
- Serial number must always be given 4
- Safety information 5
- Always give the product s serial number 14 digits when reporting a fault 6
- Serial number 6
- The serial number can be found at the bottom right of the front cover and in the info menu menu 3 6
- Contact information 7
- Nibe ab sweden box 14 hannabadsvägen 5 se 285 21 markaryd se 8
- Tel 46 0 433 73 000 fax 46 0 433 73 190 e mail info nibe se www nibe se 8
- Excellent properties for f470 9
- F470 an excellent choice 9
- Nibe f470 chapter 2 the heat pump the heart of the house 8 10
- The heat pump the heart of the house 10
- The temperatures are only examples and may vary between different installations and time of year 10
- A exhaust air heat pump uses the heat that is in the building s ventilation air to heat up the accommodation the conversion of the ventilation air s energy to accommodation heating occurs in three different circuits from the outgoing ventilation air 1 free heating energy is retrieved from the accommodation and transported to the heat pump in the refrigerant circuit 2 the heat pump increases the retrieved heat s low temperature to a high temperature in the heating medium circuit 3 the heat is distributed around the house 11
- Heat pump function 11
- Contact with f470 12
- External information 12
- Display unit 13
- Change a setting that has not been confirmed 14
- Change page in multiple page instructions for example help text and service info 14
- Confirm selections of sub menus options set values page in the start guide 14
- Emergency mode 14
- Go back to the previous menu 14
- Increase and decrease the values 14
- Scroll in menus and between options 14
- Standby 14
- Display of temperature and other operating information and access to the alarm log see page 50 15
- Heat pump 15
- Hot water 15
- Indoor climate 15
- Menu 1 15
- Menu 2 15
- Menu 3 15
- Menu 4 15
- Menu system 15
- Nibe f470 chapter 2 the heat pump the heart of the house 15
- Setting and scheduling hot water production see page 45 15
- Setting and scheduling the indoor climate see page 31 15
- Setting time date language display operating mode etc see page 54 15
- When the door to the heat pump is opened the menu system s four main menus are shown in the display as well as certain basic information 15
- The following symbols can appear in the display during operation 16
- Nibe f470 chapter 2 the heat pump the heart of the house 17
- Operation 17
- Select one of the sub menus by marking it and then pressing the ok button 17
- Selecting menu 17
- To advance in the menu system select a main menu by marking it and then pressing the ok button a new window then opens with sub menus 17
- To move the cursor turn the control knob to the left or the right the marked position is brighter and or has a turned up tab 17
- Maintenance of f470 21
- Regular checks 21
- F470 copper 24
- F470 stainless steel 24
- Nibe f470 chapter 2 the heat pump the heart of the house 22 24
- Luftningsskruv 28
- Saving tips 28
- In the past it has been calculated that an average swedish household has an approximate annual consumption of 5000 kwh domestic electricity year in today s society it is usually between 6000 12 00 kwh year 30
- Increasing the indoor temperature one degree increases the energy consump tion by approx 5 30
- Check the accommodation s energy meter regularly preferably once a month this will indicate any changes in power consumption 31
- Example a family with 2 children live in a house with 1 flat screen tv 1 di gital box 1 dvd player 1 tv games console 2 computers 3 stereos 2 bulbs in the wc 2 bulbs in the bathroom 4 bulbs in the kitchen 3 bulbs outside a washing machine tumble drier fridge freezer oven vacuum cleaner en gine block heater 6240 kwh domestic electricity year 31
- Newly built houses undergo a drying out process for a year the house can then consume significantly more energy than it would thereafter after 1 2 years the heating curve should be adjusted again as well as the heating curve 31
- Newly built houses usually have twin energy meters use the difference to calculate your domestic electricity 31
- Offset and the building s thermostat valves because the heating system as a rule requires a lower temperature once the drying process is complete 32
- F470 at your service 33
- Overview 33
- Set the indoor climate 33
- Temperature 33
- Ventilation 35
- Heating 36
- Scheduling 36
- Ventilation 37
- Advanced 39
- Heating curve 39
- An offset of the heating curve means that the supply temperature changes as much for all the outdoor temperat ures e g that a curve offset of 2 steps increases the supply temperat ure by 5 c at all outdoor temperat ures 40
- Caution 40
- Curve and read off how the flow line temperature changes at different outdoor temperatures here 40
- Curve coefficient 40
- Curve offset 40
- In the event of making fine adjustments for the indoor temperature the heat curve must be offset up or down instead this is done in menu 1 temper ature 40
- Nibe f470 chapter 3 f470 at your service 38 40
- The heating curve is set when the heating installation is installed but may need adjusting later thereafter the heating curve should not need further adjustment 40
- The optimum slope depends on the climate conditions in your location if the house has radiators or under floor heating and how well insulated the house is 40
- The slope of the heating curve indic ates how many degrees the supply temperature is to be increased re duced when the outdoor temperature drops increases a steeper slope means a higher supply temperature at a certain outdoor temperature 40
- External adjustment 42
- Min flow line temp 43
- Default value 2 44
- Default value 4 h 44
- Factor system 44
- Fan return time 44
- Here you can set a factor that determines how much the supply temperature is to be affected by the difference between the desired room temperature and the actual room temperature a higher value gives a greater change of the heating curve s set offset 44
- Here you select the return time for temporary speed change speed 1 4 on the ventilation in menu 1 44
- If several climate systems are installed the above settings can be made for the relevant systems 44
- Menu 1 44
- Nibe f470 chapter 3 f470 at your service 42 44
- Return time is the time it takes before ventilation speed returns to normal 44
- Room sensor settings 44
- Room sensors to control the room temperature can be activated here 44
- Setting range 0 6 44
- Setting range 1 99 h 44
- Speed 1 4 44
- Caution 45
- Change in curve 45
- Curve 0 in menu 1 must be selected for this curve to apply 45
- Default value 0 c 45
- It is important that the correct heating curve is selected so that the room temperature is experienced as even 45
- Menu 1 45
- Nibe f470 chapter 3 f470 at your service 45
- Outdoor temp point 45
- Own curve 45
- Point offset 45
- Select a change in the heating curve at a certain outdoor temperature here a one degree change in room temperature requires one increment for under floor heating and approximately two to three increments for the radiator system 45
- Setting range 0 80 c 45
- Setting range 10 10 c 45
- Setting range 40 30 c 45
- Supply temperature 45
- The heat curve is affected at 5 c from set outdoor temp point 45
- You can create your own heating curve here if there are special requirements by setting the desired supply temperatures for different outdoor temperatures 45
- Night cooling 46
- Overview 47
- Set the hot water capacity 47
- Temporary lux 47
- Comfort mode 48
- Scheduling 48
- Advanced 50
- Periodic increases 50
- Hot water recirc 51
- Get information 52
- Overview 52
- Service info 52
- Add heat info 53
- Compressor info 53
- Alarm log 54
- Information about an alarm 54
- Menu 3 54
- Nibe f470 chapter 3 f470 at your service 52 54
- To facilitate fault finding the heat pump operating status at alarm alerts is stored here you can see information for the 10 most recent alarms 54
- To view the run status in the event of an alarm mark the alarm and press the ok button 54
- Indoor temp log 55
- Adjust the heat pump 56
- Overview 56
- Plus functions 56
- Op mode 57
- Choose the language that you want the information to be displayed in here 59
- Language 59
- Menu 4 59
- My icons 59
- Nibe f470 chapter 3 f470 at your service 59
- Set time and date and display mode here 59
- Time date 59
- You can select what icon should be visible when the door to f470 is closed you can select up to 3 icons if you se lect more the ones you selected first will disappear the icons are displayed in the order you selected them 59
- Holiday setting 60
- Advanced 61
- Auto mode setting 61
- Factory setting user 62
- Schedule blocking 62
- Disturbances in comfort 64
- Info menu 64
- Manage alarm 64
- Basic actions 65
- Low hot water temperature or a lack of hot water 65
- Troubleshooting 65
- High room temperature 66
- Low room temperature 66
- High or distracting ventilation 67
- High supply air temperature 67
- Low or a lack of ventilation 67
- Low supply air temperature 67
- Low system pressure 67
- The compressor does not start 67
- Detailed technical specifications for this product can be found in the installa tion manual www nibe eu 69
- Technical data 69
- Additional heat 70
- Calculated flow line temperature 70
- Circulation pump 70
- Climate system 70
- Compressor 70
- Condenser 70
- Disturbances in comfort 70
- Glossary 70
- Domestic hot water 71
- Electrical addition 71
- Emergency mode 71
- Evaporator 71
- Exhaust air 71
- Exhaust air devices 71
- Expansion valve 71
- Expansion vessel 71
- Extract air 71
- Filtering time 71
- Flow pipe 72
- Heat exchanger 72
- Heat factor 72
- Heating curve 72
- Heating medium 72
- Heating medium side 72
- Hot water heater 72
- Mixing valve 72
- Outdoor air 72
- Outside sensor 73
- Pressostat 73
- Radiator 73
- Refrigerant 73
- Return pipe 73
- Return temp 73
- Room sensor 73
- Safety valve 73
- Supply air 74
- Supply air device 74
- Supply temperature 74
- Item register 75
- 1 5 0 1 80
Похожие устройства
- Nibe F470 Инструкция по монтажу
- Nibe F370 Инструкция по эксплуатации
- Nibe F370 Инструкция по установке
- Fluke 189 Начало работы
- Fluke 189 Руководство по калибровке
- Fluke 189 Краткое руководство
- Rucelf ЩРУ 3Н-25 Инструкция по эксплуатации
- Rucelf ЩРУ 3Н-36 Инструкция по эксплуатации
- Rucelf ЩРУ 3Н-48 Инструкция по эксплуатации
- Rucelf ЩРУ 1В-9 Инструкция по эксплуатации
- Rucelf ЩРУ 1В-12 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-12 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-18 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-25 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-36 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-48 Инструкция по эксплуатации
- Rucelf ЩУ 2 Инструкция по эксплуатации
- Rucelf ЩУ1/1-2-6 Инструкция по эксплуатации
- Rucelf ЩРВ 09 Инструкция по эксплуатации
- Rucelf ЩРВ 12 Инструкция по эксплуатации