Nibe F470 [15/84] Pipe and ventilation connections
![Nibe F470 [15/84] Pipe and ventilation connections](/views2/1378806/page15/bgf.png)
General pipe connections
Pipe installation must be carried out in accordance with
current norms and directives.
The system requires a low-temperature design of the ra-
diator circuit. At lowest dimensioned outdoor temperature
(DUT) the highest recommended temperatures are 55 °C
on the flow line and 45 °C on the return line.
Overflow water from the evaporator collection tray and
safety valves goes via non-pressurised collecting pipes to
a drain so that hot water splashes cannot cause injury.
The entire length of the overflow water pipe must be in-
clined to prevent water pockets and must also be frost
proof.
NOTE
The pipe system needs to be flushed out before
the heat pump is connected so that any debris
cannot damage component parts.
Maximum boiler and radiator volumes
H
The volume of the pressure expan-
sion vessel (CM1) is 10 litres and it
is pressurised as standard to 0.5 bar
((5 mvp). As a result, the maximum
permitted height "H" between the
vessel and the highest radiator is 5
metres; see figure.
If the standard initial pressure in the
pressure vessel is not high enough
it can be increased by adding air via
the valve in the expansion vessel.
The initial pressure of the expansion
vessel must be stated in the inspection document. Any
change in the initial pressure affects the ability of the
expansion vessel to handle the expansion of the water.
The maximum system volume excluding the boiler is 219
litres at the above pre-pressure.
System diagram
F470 consists of a heat pump, water heater, immersion
heater, fans, circulation pump and control system.F470
is connected to the ventilation system and heating medi-
um circuit.
When the exhaust air at room temperature passes
through the evaporator, the refrigerant evaporates be-
cause of its low boiling point. In this way the energy in
the room air is transferred to the refrigerant.
The refrigerant is then compressed in a compressor,
causing the temperature to rise considerably.
The warm refrigerant is led to the condenser. Here the
refrigerant gives off its energy to the boiler water,
whereupon the refrigerant changes state from gas to li-
quid.
The refrigerant then goes via filters to the expansion valve,
where the pressure and temperature are reduced.
The refrigerant has now completed its circulation and
returns to the evaporator.
;/;/;/;/;/
Connection, heating medium flowXL 1
Connection, heating medium returnXL 2
Connection, cold waterXL 3
Connection, hot waterXL 4
Connection, dockingXL 8
13Chapter 4 | Pipe and ventilation connectionsNIBE™ F470
4 Pipe and ventilation connections
Содержание
- Exhaust air heat pump 1
- Installer manual 1
- Nibe f470 1
- In event of disturbances in comfort 2
- Accessories 61 3
- Commissioning and adjusting 29 3
- Control introduction 35 3
- Control menus 39 3
- Delivery and handling 8 3
- Disturbances in comfort 59 3
- Electrical connections 19 3
- Important information 2 3
- Item register 79 3
- Pipe and ventilation connec tions 13 3
- Service 55 3
- Table of contents 3
- Technical data 62 3
- The heat pump design 10 3
- Handling 4
- Important information 4
- Marking 4
- Safety information 4
- Safety precautions 4
- Symbols 4
- This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capab ilities or lack of experience and knowledge if they have been given supervision or in struction concerning use of the appliance in a safe way and understand the hazards involved children shall not play with the appliance cleaning and user maintenance shall not be made by children without su pervision rights to make any design or technical modifications are reserved nibe 2013 4
- Country specific information 7
- Serial number 7
- Current regulations require the heating installation to be inspected before it is commissioned the inspection must be carried out by a suitably qualified person fill in the page for information about installation data in the user manual 8
- Inspection of the installation 8
- Contact information 9
- For countries not mention in this list please contact nibe sweden or check www nibe eu for more information 9
- Assembly 10
- Delivery and handling 10
- Installation area 10
- Transport 10
- Front cover 11
- Insulation top 11
- Location 11
- Removing parts of the insula tion 11
- Removing the covers 11
- Side covers 11
- Supplied components 11
- F470 copper 12
- Nibe f470 chapter 3 the heat pump design 10 12
- The heat pump design 12
- Chapter 3 the heat pump design nibe f470 13
- F470 stainless steel 13
- Cooling components 14
- Designations in component locations according to standard iec 81346 1 and 81346 2 14
- Electrical components 14
- Hvac components 14
- Miscellaneous 14
- Not visible in the image 14
- Only heat pumps with copper vessel 14
- Only heat pumps with stainless steel vessel 14
- Pipe connections 14
- Sensors etc 14
- Ventilation 14
- General pipe connections 15
- Maximum boiler and radiator volumes 15
- Pipe and ventilation connections 15
- System diagram 15
- Copper 16
- Dimensions and pipe connec tions 16
- Pipe dimensions 16
- Setting out dimensions 16
- Stainless steel 16
- A mixing valve must also be installed if the factory setting for hot water is changed national regulations must be observed the setting is made in menu 5 page 51 17
- Cold and hot water 17
- Connecting cold and hot water 17
- Connecting the climate system 17
- Heating medium side 17
- Symbol key 17
- When connecting to a system with thermostats on all radiators underfloor heating coils a relief valve must be fitted or a thermostat must be removed to ensure suffi cient flow 17
- Connecting hot water circulation 18
- Extra hot water heaters 18
- Installation alternative 18
- Supply air battery 18
- Two or more climate systems 18
- Exhaust air duct kitchen fan 19
- General ventilation connection 19
- Adjusting ventilation 20
- Ventilation flow 20
- Electrical connections 21
- General 21
- Miniature circuit breaker 21
- Temperature limiter 21
- Accessibility electrical connection 22
- Cable lock 22
- Connections 23
- Power connection 23
- Tariff control 23
- Connecting external operating voltage for the control system 24
- Outside sensor 24
- Room sensor 25
- Electrical addition maximum output 26
- If the current sensors are connected the heat pump monitors the phase currents in the event of a phase 26
- Overload the power is reconnected to another other phases 26
- Setting maximum output in the electrical addition is done in menu 5 2 26
- Settings 26
- The immersion heater can be set to a maximum of 10 5 kw 12 kw at 3x230v delivery setting is 5 kw 26
- The immersion heater output is divided into steps accord ing to the table 26
- The table displays the maximum phase current for the relevant electrical step for the heat pump 26
- 3 4 5 6 27
- Emergency mode 27
- External connection options 27
- Load monitor 27
- Optional connections 27
- Possible selection for aux inputs 28
- Possible selection for aux output potential free variable relay 29
- Connecting accessories 30
- Instructions for connecting accessories are provided in the manual accompanying the accessory see page 61 for the list of the accessories that can be used with f470 30
- Commissioning and adjusting 31
- Filling and venting 31
- Filling the climate system 31
- Filling the hot water heater 31
- Preparations 31
- Venting the climate system 31
- Start guide 32
- Start up and inspection 32
- 10 20 30 40 50 60 70 80 33
- 10 20 30 40 50 60 70 80 90 33
- Chapter 6 commissioning and adjusting nibe f470 33
- Effekt watt 33
- Even if ventilation is roughly set at installation it is import ant that a ventilation adjustment is ordered and permit ted 33
- Luftflöde l s 33
- Order a ventilation adjustment to complete the setting 33
- Setting the ventilation 33
- The factory setting for ventilation on the heat pump is high ventilation must be set according to applicable norms the supply air flow is adjusted so that it is 80 of the exhaust air flow the setting is made in menu 5 33
- Tillgängligt tryck pa 33
- Supply air battery 34
- Chapter 6 commissioning and adjusting nibe f470 35
- Commissioning without fans 35
- Enter menu 4 op mode and select add heat only 35
- F470 copper 35
- F470 stainless steel 35
- Select operating mode auto or manual when the heat pump is to run on recovery again 35
- Setting the pump speed 35
- The heat pump can be run without recovery as only an electric boiler to produce heat and hot water for ex ample before the ventilation installation is complete 35
- The speed of the circulation pump gp1 is set using the switch gp1 sf4 on the pump so that it achieves the projected flow for the house 35
- Then enter menu 5 fan sp exhaust air and reduce the fan speed to 0 also go to menu 5 fan sp supply air and reduce the fan speed on the supply air fan to 0 35
- Post adjustment venting 36
- Control introduction 37
- Display unit 37
- Advanced settings these settings are not available to the end user the menu is visible by pressing the back button for 7 seconds see page 51 38
- Display of temperature and other operating information and access to the alarm log see page 47 38
- Menu 1 indoor climate 38
- Menu 2 hot water 38
- Menu 3 info 38
- Menu 4 heat pump 38
- Menu 5 service 38
- Menu system 38
- Setting and scheduling hot water production see page 45 38
- Setting and scheduling the indoor climate see page 39 38
- Setting time date language display operating mode etc see page 48 38
- Symbols in the display 38
- The following symbols can appear in the display during operation 38
- When the door to the heat pump is opened the menu system s four main menus are shown in the display as well as certain basic information 38
- Operation 39
- Selecting menu 39
- Selecting options 39
- Setting a value 39
- Help menu 40
- Scroll through the windows 40
- Control menus 41
- Menu 1 indoor climate 41
- Menu 1 temperature 41
- Overview 41
- Menu 1 heating 42
- Menu 1 scheduling 42
- Menu 1 ventilation 42
- Menu 1 advanced 43
- Menu 1 heating curve 43
- Menu 1 ventilation 43
- Menu 1 external adjustment 45
- Menu 1 fan return time 45
- Menu 1 min flow line temp 45
- Menu 1 own curve 45
- Menu 1 room sensor settings 45
- Menu 1 night cooling 46
- Menu 1 point offset 46
- Menu 2 comfort mode 47
- Menu 2 hot water 47
- Menu 2 scheduling 47
- Menu 2 temporary lux 47
- Overview 47
- Menu 2 advanced 48
- Menu 2 hot water recirc 48
- Menu 2 periodic increases 48
- Menu 3 add heat info 49
- Menu 3 alarm log 49
- Menu 3 compressor info 49
- Menu 3 indoor temp log 49
- Menu 3 info 49
- Menu 3 service info 49
- Overview 49
- Menu 4 heat pump 50
- Menu 4 op mode 50
- Menu 4 plus functions 50
- Menu 4 sms 50
- Overview 50
- Menu 4 advanced 51
- Menu 4 auto mode setting 51
- Menu 4 holiday setting 51
- Menu 4 language 51
- Menu 4 my icons 51
- Menu 4 time date 51
- Menu 4 factory setting user 52
- Menu 4 schedule blocking 52
- Menu 5 hot water settings 53
- Menu 5 operating settings 53
- Menu 5 service 53
- Overview 53
- Menu 5 2 internal electrical addition 54
- Menu 5 9 other settings 54
- Menu 5 alarm actions 54
- Menu 5 fan sp exhaust air 54
- Menu 5 fan sp supply air 54
- Menu 5 max flow line temperature 54
- Menu 5 accessory settings 55
- Menu 5 extra climate system 55
- Menu 5 factory setting service 55
- Menu 5 forced control 55
- Menu 5 quick start 55
- Menu 5 soft in outputs 55
- Menu 5 start guide 55
- Menu 5 system settings 55
- Menu 5 0 change log 56
- Menu 5 floor drying function 56
- Draining the climate system 57
- Draining the water heater 57
- Emergency mode 57
- Service 57
- Service actions 57
- Help for starting the heating medium pump gp1 only applies to f470 copper 58
- Helping the circulation pump to start 58
- Insert a screwdriver and turn the pump motor around 58
- It is usually easier to start the circulation pump with f470 running switch sf1 set to helping the circulation pump to start is performed with f470 running be pre pared for the screwdriver to jerk when the pump starts 58
- Loosen the venting screw qm5 with a screwdriver hold a cloth around the screwdriver blade as a small amount of water may run out 58
- Luftningsskruv 58
- Open the service cover 58
- Screw in the venting screw qm5 58
- Shut off f470 by setting the switch sf1 to 58
- Start f470 by setting the switch sf1 to and check whether the circulation pump works 58
- Temperature sensor data 58
- Usb service outlet 59
- Basic actions 61
- Disturbances in comfort 61
- Info menu 61
- Low hot water temperature or a lack of hot water 61
- Low room temperature 61
- Manage alarm 61
- Troubleshooting 61
- High or distracting ventilation 62
- High room temperature 62
- Low or a lack of ventilation 62
- Low system pressure 62
- The compressor does not start 62
- Accessories 63
- Base extension ef 45 63
- Communications module sms 40 63
- Docking kit deh 63
- Extra shunt group ecs 40 ecs 41 63
- Room unit rmu 40 63
- Solar 41 63
- Top cabinet 63
- Dimensions and setting out coordinates 64
- Technical data 64
- Undvik rördragning inom markerat område 64
- Technical specifications 65
- A20 12 exhaust air flow150 66
- A20 12 w35 exhaust air flow 200 66
- A20 12 w45 exhaust air flow 150 66
- A20 12 w55 exhaust air flow 110 66
- The value can vary with the room s damping capacity these values apply with a damping of 4 db 66
- The value varies with the selected fan curve for more extensive sound data including sound to channels visit www nibe eu 66
- A20 12 exhaust air flow150 68
- A20 12 w35 exhaust air flow 200 68
- A20 12 w45 exhaust air flow 150 68
- A20 12 w55 exhaust air flow 110 68
- The value can vary with the room s damping capacity these values apply with a damping of 4 db 68
- The value varies with the selected fan curve for more extensive sound data including sound to channels visit www nibe se 68
- Electrical circuit diagram 69
- Item register 81
- 1 5 0 0 84
Похожие устройства
- Nibe F370 Инструкция по эксплуатации
- Nibe F370 Инструкция по установке
- Fluke 189 Начало работы
- Fluke 189 Руководство по калибровке
- Fluke 189 Краткое руководство
- Rucelf ЩРУ 3Н-25 Инструкция по эксплуатации
- Rucelf ЩРУ 3Н-36 Инструкция по эксплуатации
- Rucelf ЩРУ 3Н-48 Инструкция по эксплуатации
- Rucelf ЩРУ 1В-9 Инструкция по эксплуатации
- Rucelf ЩРУ 1В-12 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-12 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-18 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-25 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-36 Инструкция по эксплуатации
- Rucelf ЩРУ 3В-48 Инструкция по эксплуатации
- Rucelf ЩУ 2 Инструкция по эксплуатации
- Rucelf ЩУ1/1-2-6 Инструкция по эксплуатации
- Rucelf ЩРВ 09 Инструкция по эксплуатации
- Rucelf ЩРВ 12 Инструкция по эксплуатации
- Rucelf ЩРВ 18 Инструкция по эксплуатации