FSP Knight PRO + RM 6K — руководство по обслуживанию и замене батарей UPS [16/26]
![FSP Knight RM 10K [16/26] 5 abbreviation meaning in lcd display](/views2/1380738/page16/bg10.png)
15
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try
to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact
the distributor or service people immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output
immediately to avoid more risk or danger.
12. Operation of changing battery numbers
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance
bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the input breaker, and switch off the battery breaker (only available for long-run model),
or disconnect battery wire for standard model.
4) Remove the cabinet cover, and then modify the jumpers (JP1, JS3) on the control board to set the
battery numbers as following table:
Battery Number
JP1
JS3
pin1 & pin2
pin3 & pin4
Pin5 & pin6
pin7 & pin8
16
X
X
0
0
0
17
X
X
1
1
0
18
X
X
0
0
1
19
X
X
1
0
1
20
X
X
1
1
1
Note:1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the cover back, and
switch on the battery breaker for long-run model.
6) Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance
Bypass mode, turn the maintenance switch to “UPS” position and then turn on the UPS.
3-5. Abbreviation Meaning in LCD Display
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode
SUB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved
Содержание
- Table of contents p.3
- 3 installation p.4
- 2 preparation p.4
- Safety and emc instructions p.4
- 1 transportation and storage p.4
- 5 standards p.5
- 4 operation p.5
- Installation and operation p.6
- 1 unpacking and inspection p.6
- 2 rear panel view p.6
- 3 single ups installation p.8
- Operations p.11
- 2 led indicators and lcd panel p.11
- 1 button operation p.11
- 4 single ups operation p.13
- 3 audible alarm p.13
- 5 abbreviation meaning in lcd display p.16
- 6 lcd setting p.17
- 7 operating mode status description p.22
- 9 warning indicator p.23
- 8 fault code p.23
- Trouble shooting p.24
- 2 maintenance p.25
- 1 storage p.25
- Storage and maintenance p.25
- Specifications p.26
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Proline 3/1 10KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Узнайте, как правильно проверять и обслуживать источники бесперебойного питания. Следуйте инструкциям по замене батарей и устранению неисправностей для безопасной работы.