6) Put the terminal block cover back to the rear panel of the UPS.
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring
connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the
standard internal battery to the external battery. The battery type and voltage and numbers may be
different. If you connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If
not, please install it carefully. Switch off the battery breaker before installation.
Warning:
● For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for
other external battery pack, make sure a DC breaker or other protection device between UPS and
external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before
installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection
with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the
battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the
correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The current spec, color, position, connection and
conductance reliability of wire should be checked carefully.
● Make sure the utility input & output wiring is correct. The current spec, color, position, connection and
conductance reliability of wire should be checked carefully. Make sure the L/N terminal is correct, not
reverse or short-circuited.
Содержание
- Table of contents p.3
- 3 installation p.4
- 2 preparation p.4
- Safety and emc instructions p.4
- 1 transportation and storage p.4
- 5 standards p.5
- 4 operation p.5
- Installation and operation p.6
- 1 unpacking and inspection p.6
- 2 rear panel view p.6
- 3 single ups installation p.8
- Operations p.11
- 2 led indicators and lcd panel p.11
- 1 button operation p.11
- 4 single ups operation p.13
- 3 audible alarm p.13
- 5 abbreviation meaning in lcd display p.16
- 6 lcd setting p.17
- 7 operating mode status description p.22
- 9 warning indicator p.23
- 8 fault code p.23
- Trouble shooting p.24
- 2 maintenance p.25
- 1 storage p.25
- Storage and maintenance p.25
- Specifications p.26
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Proline 3/1 10KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Следуйте инструкциям по установке блока питания UPS, чтобы избежать электрических опасностей. Убедитесь в правильности подключения и соблюдении всех мер безопасности.