09: Maximum battery discharge time setting
Interface
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999
min. UPS will shut down to protect battery if the discharge time
arrives before the battery is under voltage. The default value is
990 min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
10: Programmable output setting
Interface
Setting
Parameter 3: Set programmable output. You may choose the
following three options:
ON: Programmable output is manually switched on timelessly.
OFF: Programmable output is manually switched off. However, if
UPS restarts, this setting will automatically go to “ATO” status.
ATO: Programmable output is automatically turned on or cut off
according to battery or load status. When the battery voltage is
lower than the setting point, or shutdown time arrives, the
programmable output will be cut off automatically. After the utility
is recovering, the output will turn on automatically. If overload
happens, the programmable output also will be cut off
automatically. If it happens 3 times, the programmable output will
be cut off until it is manually switched on.
11: Shutdown point for programmable output
Interface
Setting
Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the
programmable output terminal will be cut off. The default value is
30 minutes.
Parameter 2: 002
Set shutdown voltage for programmable output.
Parameter 3: Shutdown voltage in V.
Setting range is from 11.2 to 13.6. If the battery voltage is less
than the setting point, the programmable output will be cut off.
The default value is 11.2V.
12: Neutral loss detection
Interface
Setting
Parameter 2:
N.L: Indicates neutral loss detection function.
Parameter 3:
DIS: Disable the neutral loss detection function. The UPS will not
detect the neutral loss or not.
ATO: The UPS will automatically detect the neutral is lost or not. If
neutral loss is detected, an alarm will be generated, if the UPS is
turned on, it will transfer to battery mode. When neutral is
restored and detected, the alarm will be muted automatically, and
the UPS will go back to normal mode automatically.
CHE: The UPS will automatically detect the neutral loss. If neutral
Содержание
- Table of contents p.3
- 1 transportation and storage p.4
- Safety and emc instructions p.4
- 3 installation p.4
- 2 preparation p.4
- Connection warnings p.5
- 6 standards p.6
- 5 operation p.6
- Installation and operation p.7
- Diagram1 10k 10kl rear panel diagram 2 15kl 20kl rear panel p.7
- 2 rear panel view p.7
- 1 unpacking and inspection p.7
- Output terminal p.10
- Input output terminal p.10
- Diagram 15 battery pack rear panel p.10
- Diagram 13 15kr l 20kr l rear panel diagram 14 15kr l 20k l p.10
- Diagram 11 10kr l rear panel diagram 12 10kr l input p.10
- 3 single ups installation p.11
- 4 ups installation for parallel system p.14
- Wiring diagram of parallel system for 10k 10kl p.15
- Wiring diagram of parallel system for 15k l 20k l p.16
- Wiring diagram of parallel system for 30k p.17
- Share current cable connection p.18
- Parallel communication port connection p.18
- For optimal computer system protection install ups monitoring software to fully configure ups shutdown p.19
- 5 software installation p.19
- 4 single ups operation p.22
- 3 audible alarm p.22
- 5 parallel operation p.25
- 6 abbreviation meaning in lcd display p.26
- 7 lcd setting p.27
- 8 operating mode status description p.37
- 9 fault code p.42
- 10 warning indicator p.43
- Utility extremely unbalanced p.43
- Bypass unstable p.43
- 11 warning code p.43
- Trouble shooting p.44
- Storage and maintenance p.46
- 2 maintenance p.46
- 1 storage p.46
- Specifications p.47
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Knight PRO + RM 6KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Изучите настройки максимального времени разряда, программируемого выхода и обнаружения потери нейтрали для надежной работы вашего источника бесперебойного питания.