FSP Proline 3/1 10K — настройки защиты и функций инвертора для источников бесперебойного питания [35/48]
![FSP Proline 3/1 30K Инструкция по эксплуатации онлайн [35/48] 319489](/views2/1380774/page35/bg23.png)
32
09: Maximum battery discharge time setting
Interface
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999
min. UPS will shut down to protect battery if the discharge time
arrives before the battery is under voltage. The default value is
990 min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
10: Inverter outputs parallel function
Interface
Setting
When the output is not set to the single phase, this menu will be
reserved, “ ” will be displayed in parameter 2 and parameter
3.
Parameter 2:
OP.P: Indicates parallel functions for three phase inverter
outputs.
Parameter 3:
DIS: Disable inverter output parallel function. If selected, three
phase inverter outputs must NOT be connected. It is default
setting.
ENA: Enable parallel function to allow connecting three inverter
outputs in parallel to get only one phase output with 100% of UPS
total capacity. When this function is enabled, inverter outputs
MUST be connected and the JS5 on the inverter control board
MUST be shorted to set the inverter outputs to the single phase.
11: Reserved
Interface
Setting
Reserve for future options.
12: Neutral loss detection
Interface
Setting
Parameter 2:
N.L: Indicates neutral loss detection function.
Parameter 3:
DIS: Disable the neutral loss detection function. The UPS will not
detect the neutral loss or not.
ATO: The UPS will automatically detect the neutral is lost or not. If
neutral loss is detected, an alarm will be generated. If the UPS is
turned on, it will transfer to battery mode. When neutral is
restored and detected, the alarm will be muted automatically and
the UPS will go back to normal mode automatically.
CHE: The UPS will automatically detect the neutral loss. If neutral
loss is detected, an alarm will be generated. If the UPS is turned
on, it will transfer to battery mode. When neutral is restored, the
Содержание
- Table of contents p.3
- 1 transportation and storage p.4
- Safety and emc instructions p.4
- 3 installation p.4
- 2 preparation p.4
- Connection warnings p.5
- 6 standards p.6
- 5 operation p.6
- Installation and operation p.7
- Diagram1 10k 10kl rear panel diagram 2 15kl 20kl rear panel p.7
- 2 rear panel view p.7
- 1 unpacking and inspection p.7
- Output terminal p.10
- Input output terminal p.10
- Diagram 15 battery pack rear panel p.10
- Diagram 13 15kr l 20kr l rear panel diagram 14 15kr l 20k l p.10
- Diagram 11 10kr l rear panel diagram 12 10kr l input p.10
- 3 single ups installation p.11
- 4 ups installation for parallel system p.14
- Wiring diagram of parallel system for 10k 10kl p.15
- Wiring diagram of parallel system for 15k l 20k l p.16
- Wiring diagram of parallel system for 30k p.17
- Share current cable connection p.18
- Parallel communication port connection p.18
- For optimal computer system protection install ups monitoring software to fully configure ups shutdown p.19
- 5 software installation p.19
- 4 single ups operation p.22
- 3 audible alarm p.22
- 5 parallel operation p.25
- 6 abbreviation meaning in lcd display p.26
- 7 lcd setting p.27
- 8 operating mode status description p.37
- 9 fault code p.42
- 10 warning indicator p.43
- Utility extremely unbalanced p.43
- Bypass unstable p.43
- 11 warning code p.43
- Trouble shooting p.44
- Storage and maintenance p.46
- 2 maintenance p.46
- 1 storage p.46
- Specifications p.47
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 20KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Knight PRO + RM 6KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Узнайте, как настроить максимальное время разряда батареи и функции параллельного подключения инверторов для оптимальной работы источников бесперебойного питания.