FSP Proline 3/1 20K — инструкции по установке и подключению источников бесперебойного питания [14/48]
![FSP Proline 3/1 20K [14/48] 4 ups installation for parallel system](/views2/1380774/page14/bge.png)
11
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring
connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the
standard internal battery to the external battery. The battery type and voltage may be different. If you
connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If
not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection
with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the
battery pack is correct.
● Pay highly attention to the polarity marking on external battery terminal block, and make sure the
correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The wire current spec, color, position,
connection and conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The wire current spec, color, position, connection
and conductance reliability should be checked carefully. Make sure the L/N site is correct, not reverse
and short-circuited.
● Before turning on the UPS, be sure the breaker of the battery pack is on.
● UPS will alert while the external battery breaker is not on. If so, turn on the external battery breaker and
press “test” button on the UPS to release the audible alert.
2-4. UPS Installation for Parallel System
If the UPS is only available for single operation, you may skip this section to the next.
1) Install and wires the UPSs according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a major output breaker. Then this major output breaker will directly
connect to the loads.
4) Each UPS is connected to an independent battery pack.
NOTE: The parallel system can not use one battery pack. Otherwise, it will cause system permanent failure.
5) Refer to the following wiring diagram:
Содержание
- Table of contents p.3
- 1 transportation and storage p.4
- Safety and emc instructions p.4
- 3 installation p.4
- 2 preparation p.4
- Connection warnings p.5
- 6 standards p.6
- 5 operation p.6
- Installation and operation p.7
- Diagram1 10k 10kl rear panel diagram 2 15kl 20kl rear panel p.7
- 2 rear panel view p.7
- 1 unpacking and inspection p.7
- Output terminal p.10
- Input output terminal p.10
- Diagram 15 battery pack rear panel p.10
- Diagram 13 15kr l 20kr l rear panel diagram 14 15kr l 20k l p.10
- Diagram 11 10kr l rear panel diagram 12 10kr l input p.10
- 3 single ups installation p.11
- 4 ups installation for parallel system p.14
- Wiring diagram of parallel system for 10k 10kl p.15
- Wiring diagram of parallel system for 15k l 20k l p.16
- Wiring diagram of parallel system for 30k p.17
- Share current cable connection p.18
- Parallel communication port connection p.18
- For optimal computer system protection install ups monitoring software to fully configure ups shutdown p.19
- 5 software installation p.19
- 4 single ups operation p.22
- 3 audible alarm p.22
- 5 parallel operation p.25
- 6 abbreviation meaning in lcd display p.26
- 7 lcd setting p.27
- 8 operating mode status description p.37
- 9 fault code p.42
- 10 warning indicator p.43
- Utility extremely unbalanced p.43
- Bypass unstable p.43
- 11 warning code p.43
- Trouble shooting p.44
- Storage and maintenance p.46
- 2 maintenance p.46
- 1 storage p.46
- Specifications p.47
Похожие устройства
-
FSP Proline 3/3 30KИнструкция по эксплуатации -
FSP Proline 3/3 20KИнструкция по эксплуатации -
FSP Proline 3/3 15KИнструкция по эксплуатации -
FSP Proline 3/3 10KИнструкция по эксплуатации -
FSP Proline 3/1 30KИнструкция по эксплуатации -
FSP Proline 3/1 15KИнструкция по эксплуатации -
FSP Proline 3/1 10KИнструкция по эксплуатации -
FSP Knight PRO + RM 6KИнструкция по эксплуатации -
FSP Knight PRO + RM 10KИнструкция по эксплуатации -
FSP Knight PRO+ 1KИнструкция по эксплуатации -
FSP Knight PRO+ 2KИнструкция по эксплуатации -
FSP Knight PRO+ 3KИнструкция по эксплуатации
Подробные рекомендации по установке и подключению ИБП, включая важные предупреждения и советы по безопасности. Обеспечьте надежную работу вашего оборудования.