Alfa Laval Gemini M3-G Инструкция по эксплуатации онлайн

Alfa Laval Gemini M6-MG Инструкция по эксплуатации онлайн
Cross-contamination safe double wall plates
M-Series/BaseLine Gemini Plate Heat Exchanger
Application
General cooling/heating for pharmaceutical, brewery and
beverage applications when a mix-proof design is required.
To secure the cross-contamination safe feature, water or
water-like fluids is recommended.
Working principles
Channels are formed between the plates and the corner ports
are arranged so that the two media flow through alternate
channels. A unique distribution area provides an efficient flow
over the plate surface. The heat is transferred through the
plate between the channels, and complete counter-current
flow is created for highest possible efficiency. The chevron
corrugation of the plates provides the passage between the
plates, supports each plate against the adjacent one and
enhances the turbulence. The high turbulence resulting in
efficient heat transfer and high surface shear forces to
minimise fouling and the build-up of biofilm. The plates are
reversible and have parallel flow, which means that only one
type of gasket is needed.
Heat exchanger design
The plate heat exchanger consists of a pack of corrugated
metal plates with portholes for the passage of the two fluids
between which heat transfer will take place.
The plate pack is assembled between a fixed frame plate
and a movable pressure plate and compressed by tightening
bolts. The plates are fitted with a gasket, which seals the inter-
plate channel and directs the fluids into alternate channels.
The number of plates is determined by the flow rate, physi-
cal properties of the fluids, pressure drop and temperature
program. The plate corrugations promote fluid turbulence and
support the plates against differential pressure.
The plate and the pressure plate are suspended from an
upper carrying bar and located by a lower guiding bar, both
of which are fixed to a support column. Connections may be
located in the frame plate and/or in the pressure plate.
Gemini plates
The Gemini plates consist of two plates with a small air gap
in between. Contact to the atmosphere is safeguarded around
the whole periphery of the plates. The Gemini double wall
plates will give a cross-contamination safe design, as a crack
in a plate will not result in mixing of the two media.
Скачать