Airwell Westherm 65 [10/16] Installation cont d

Airwell Westherm 70 [10/16] Installation cont d
Page 9
English
6 - Installation (cont'd)
6.3 - Installation Instructions
1. Unpack the unit and install the fixing brackets on it (see
drawings below).
2. The unit must be installed with a minimum distance of
150 mm between motor and wall, so that air flow is not
impeded and removal of fan motor assembly can be
easily realized (see drawing A).
3. For vertical mounting unit, fix it directly to the suitable
supports or hang it to the ceiling by threaded rods or
strengthened screws supplied by the installer (see
drawings A & B).
4. The ceiling units with down flow air discharge must be
suspended via 4 hangers fixed onto fixing brackets
located on the sides of the unit (see drawing C).
5. Secure the unit in its final position and level it with a
spirit level to assure proper operation.
Remark : the fixing accessories shown such as supports,
rods or brackets are not supplied by manufacturer.
150
A B C
It is highly recommended, or even compulsory in certain case,
to fit the unit with the optional fan guard. Make sure the unit is in
conformity with applicable safety regulations.
Warning