Summer performances Size : RT4D 180
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 92.8 90 88.7 86.7 84.7 83.4
Compressors power input (kW) 21.2 23.5 24.5 26.2 27.9 29.2
26 °C / 19.5 °C
Cooling capacity (kW) 97.7 94.6 93.3 91.3 89.3 87.8
Compressors power input (kW) 21.4 23.8 24.9 26.5 28.3 29.6
29 °C / 22 °C
Cooling capacity (kW) 105.8 102.6 101.3 99.2 97 95.5
compressors power input (kW) 21.9 24.3 25.4 27.1 29 30.3
31 °C / 24 °C
Cooling capacity (kW) 112.7 109.3 107.9 105.6 103.3 101.7
Compressors power input (kW) 22.3 24.8 25.9 27.6 29.5 30.9
Winter performances Size : RT4D 180
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 65.4 67.9 71.8 76.9 84.8 91.2
Compressors power input (kW) 19.3 19.5 19.8 20.2 20.9 21.5
18 °C / 40 %
Heating capacity (kW) 65.6 68.1 71.9 77 84.8 91.2
Compressors power input (kW) 20.1 20.3 20.6 21 21.7 22.4
20 °C / 40 %
Heating capacity (kW) 65.8 68.3 72.1 77.1 84.8 91.1
Compressors power input (kW) 20.9 21.1 21.4 22 22.6 23.3
22 °C / 40 %
Heating capacity (kW) 66 68.4 72.2 77.2 84.8 91
Compressors power input (kW) 21.7 21.9 22.3 22.7 23.6 24.3
Summer performances Size : RT4D 180
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 100.8 97.7 96.3 94.2 92.0 90.6
Compressors power input (kW) 19.45 21.56 22.48 24.04 25.60 26.79
26 °C / 19.5 °C
Cooling capacity (kW) 106.1 102.7 101.3 99.2 97.0 95.4
Compressors power input (kW) 19.63 21.83 22.84 24.3 25.96 27.16
29 °C / 22 °C
Cooling capacity (kW) 114.9 111.4 110.0 107.7 105.3 103.7
Compressors power input (kW) 20.09 22.29 23.30 24.86 26.61 27.80
31 °C / 24 °C
Cooling capacity (kW) 122.4 118.7 117.2 114.7 112.2 110.4
Compressors power input (kW) 20.46 22.75 23.76 25.32 27.06 28.35
Winter performances Size : RT4D 180
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 68.60 71.23 75.32 80.67 88.96 95.67
Compressors power input (kW) 18.17 18.36 18.64 19.02 19.68 20.24
18 °C / 40 %
Heating capacity (kW) 68.81 71.44 75.42 80.77 88.96 95.67
Compressors power input (kW) 18.93 19.11 19.40 19.77 20.43 21.09
20 °C / 40 %
Heating capacity (kW) 69.02 71.65 75.63 80.9 88.96 95.56
Compressors power input (kW) 19.68 19.87 20.15 20.7 21.28 21.94
22 °C / 40 %
Heating capacity (kW) 69.23 71.75 75.74 80.98 88.96 95.46
Compressors power input (kW) 20.43 20.62 21.00 21.37 22.22 22.88
Units Performance Data - RT4D 180