The following information is required for selecting the appropriate
model :
1. Required cooling capacity in kW.
2. Chilled water inlet / outlet temperatures.
3. Outdoor air temperature.
4. Altitude (in metres) above sea level.
N.B. : the cooling capacity is determined by the following formula :
Cooling capacity (kW) = [Water flow (l/h) x Delta T (K)] / 860
Selection example
Data :
- Required cooling capacity : 21 kW.
- Outlet water temperature : 6 °C.
- Inlet water temperature : 11 °C.
- Outdoor air temperature : 30 °C.
- Altitude : 0 m.
In the performance table on Page 13, the model 20 will supply
cooling capacity of 21.7 kW with a power consumption of 6.8 kW.
Comment : Interpolation is authorised for conditions
differing from those indicated in the performance table.
However, extrapolation is prohibited.
The water flow will be equal to (21.7 kW / 5 K) x 860 = 3732 l/h.
Determine the unit’s available pressure from the curves on
pages 17 and 18 or the evaporator water pressure drops from the
curves on pages 19 and 20.