Airedale Ultima FreeCool UFC 250 [12/46] Installation data

Airedale Ultima FreeCool UFC 225 [12/46] Installation data
ULTIMA FREECOOL Chillers
Chillers
12
Installation & Maintenance Manual : 903-125 IM E 05/04/A
Installation Data
Employ lifting specialists.
Local codes and regulations relating to the lifting of this type of equipment
should be observed.
Use the appropriate spreader bars/lifting slings with the holes/lugs provided.
Attach lifting chains to the 4 lifting lugs provided, each chain must be capable of
lifting the whole chiller.
Lifting hole/lug dimension: 40mm
Lift the unit slowly and evenly.
UNIT LIFTING
If the unit is dropped, it should immediately be checked for damage and reported
to Airedale Service.
CAUTION
Only use lifting points provided.
The unit should be lifted from the base and where possible, with all packing and
protection in position. If any other type of slinging is used, due care should be taken to
ensure that the slings do not crush the casework or coil.
8 – 18 Fans
J
2300
HK
L
20 Fans
J H K
L
J
5000mm Min
2300
HJK L (min)
8 FANS mm 425 3150 1370 3200
10 FANS mm 425 3480 1890 3500
12 FANS mm 425 4105 2115 4200
14 FANS mm 1100 4035 2535 4200
16 FANS mm 1100 4885 2535 5000
18 FANS mm 1075 5585 2660 5800
LIFTING DIMENSIONS
20 FANS (8 lifting points) mm 1125 2850 2775 5000