CHILLER CONTROL OPERATION GUIDE
1. ON/OFF Toggle switch
Push up to start the chiller.
Push down to switch off the chiller for servicing and maintenance.
2. Water Entering Temperature °C (Factory Setting)
Cooling Mode, setting : 12°C
Heating Mode, setting : 40°C
3. Antifreeze Protection for Cooling Mode
Setting : 2°C
4. Temperature Setting
For cooling mode, press the SW1 button switch once. The green LED will blink for a few seconds. Adjust the small
variable resitor (VR3) to the required water entering temperature of between (10°C - 15°C) by
using a suitable tool.
For extremely low water temperature (obtained by adding glycol), set the water entering temperature to between 3°C to
9°C by adjusting the DIP switch (SW2).
Set
SW2
Temperature °C
SW 2-3 SW2-2 SW2-1
Set by VR3 0 0 0
3001
4010
5011
6100
7101
8110
9111
1 = ON
0 = OFF
If the DIP switch is set to (0,0,0), the setting temperature
will be determined by the VR3 setting. Otherwise,
For heating mode, press the SW1 button switch twice
and then the red LED will blink for a few seconds.
Adjust the variable resistor (VR1) by setting it to the
required water entering temperature which (35°C ~ 50°C)
for heating mode.
To prevent water from freezing in the system, adjust the
variable resistor VR2. The setting range is between +3°C
to -4°C.
S1
COMP
L
RL 1 RL 2
NEUTRAL
RL 3
RL 6
RL 5 RL 7
RL 4 RL 8
PCB
AHTR
OF
PUMP
4WV
TH4
TH3
TH2
TH1
AL 1
AL 2
S 2
S 3
S 4
+ 12V
+ 12V
COOL
HEAT
HP
LP
FL
SW 1
VR 1
VR 3
VR 2
OV
S5
S6
PUMP O/L
COMP O/L
SW 2
L
OUTDOOR DEFROST SENSOR SOCKET. (LENGTH 1.0M)
OUTDOOR AIR TEMP. SENSOR. (LENGTH 0.6M)
LEAVING WATER / ANTIFREEZE SENSOR. (LENGTH 1.0M)
ENTERING WATER SENSOR. (LENGTH 0.6M)
CK20AN-ENG 20/07/2000, 14:528
Скачать