Acson MAC058A [10/11] Trouble shooting
![Acson AC058A [10/11] Trouble shooting](/views2/1409744/page10/bga.png)
1-9
TROUBLE SHOOTING
If any malfunction occurrs, immediately switch off the power supply to the unit, and contact a local dealer if necessary. Some
simple trouble shooting tips are given below.
SYMTOMS POSSIBLE CAUSES REMEDIAL ACTION
1. Compressor does
not start.
2. Fan does not work.
3. Air cooled mini
chiller does work,
but cools
unsuffuciently.
4. PCB display ‘CO’.
5. PCB display ‘PO’.
6. PCB display ‘FL’.
7. PCB, display ‘HP’.
8. PCB display ‘LP’.
9. PCB display ‘E3’.
* No power supply.
* Fuses blown or automatic circuit break-
down open.
* Thermal relay tripped.
* Defective contactor or coil.
* Unit is stopped because safety device has
tripped.
* Loose wires.
* Compressor faulty.
* No power supply.
* Fan motor faulty.
* Thermostat setting too high.
* Condenser coil dirty.
* Obstacle blocking air inlet or outlet of the
unit.
* Insufficient refrigerant in the system.
* Improper water flow rate.
* Water source contains contamination.
* Compressor thermal relay tripped.
* Terminal loose.
* Pump thermal relay tripped.
* Terminal loose.
* Flow switch connection loose.
* Wrong terminal in flow switch.
* Water volume not enough.
* Flow switch blade too short or too long.
* Discharged pressure too high
* Overcharge.
* Coil dirty.
* Condenser Fan does not work
* Expansion valve stuck in open position
* Suction pressure too low
* Undercharge
* Gas Leak
* Water flow rate too low
* Antifreeze protection activated.
* Water flow rate too low
* Bubble in the heat exchanger
* Check power supply.
* Look for short circuit or grounded wires in
motor windings. Replace fuses and reset cir-
cuit breakers when the fault has been cor-
rected. Check tightness and soundness of all
electrical connections.
* Reset the thermal relay and carefully monitor
units operation when it is restarted.
* Repair or replace.
* Determine the type of safety shut down and
correct the default before the unit is restarted.
* Check wire connections and tighten terminal
screws.
* Contact local dealer.
* Check power supply.
* Contact local dealer.
* Reset thermostat.
* Contact local dealer.
* Remove the obstacle.
* Contact local dealer.
* Contact local dealer.
* Contact local dealer.
* Reset the thermal relay and carefully monitor
units operation when it is restarted.
* Tighten terminal screws.
* Reset the thermal relay and carefully monitor
units operation when it is restarted.
* Tighten terminal screws.
* Tighten terminal screws.
* Change the terminal.
* Add water into the system.
* Replace flow switch.
* Reset the pressure switch and observe the units
operation when it is restarted.
* Contact local dealer.
* Clean the coil with chemical detergent.
* Contact local dealer.
* Replace it.
* Reset the pressure switch and observe the units
operation when it is restarted.
* Contact local dealer.
* Contact local dealer.
* Adjust the flow rate.
* Check the temperature setting.
* Adjust the flow rate.
* Increase the water volume.
CK20AN-ENG 20/07/2000, 14:529
Содержание
- Air cooled mini chiller 2
- Before using your air conditioner please read this instruction manual carefully and keep it for future reference 2
- Installation manual 2
- Models 2
- Reference model 2
- This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit special adjustment may be necessary to suit local requirements 2
- Caution 3
- Contents 3
- Do not install or use the air conditioner unit in a laundry room 3
- Do not install the unit where leakage of flammable gas may occur 3
- Do not overcharge the unit 3
- Ensure that the drainage piping is connected properly 3
- Ensure that the units panel is closed after service or installation 3
- Important 3
- Please take note of the following important points when installing 3
- Safety precautions 3
- Warning 3
- Unit installation 5
- Electrical wiring connection 7
- Refrigerant circuit 7
- Water filling 7
- Chiller control operation guide 9
- Trouble shooting 10
- Jalan pengapit 15 19 p o box 7072 40702 shah alam selangor darul ehsan malaysia 11
- Oyl manufacturing company sdn bhd 11
Похожие устройства
- Acson AMAC040AR Инструкция по эксплуатации
- Acson MAC040AR Инструкция по эксплуатации
- Acson AMAC050AR Инструкция по эксплуатации
- Acson AMAC058AR / MAC058AR Инструкция по эксплуатации
- Acson AMAC075B / MAC075B Инструкция по эксплуатации
- Acson AMAC100B / MAC100B Инструкция по эксплуатации
- Acson AMAC125B / MAC125B Инструкция по эксплуатации
- Acson AMAC075BR / MAC075BR Инструкция по эксплуатации
- Acson AMAC100BR / MAC100BR Инструкция по эксплуатации
- Acson AMAC125BR / MAC125BR Инструкция по эксплуатации
- Logitech SPEAKER LAPDESK N700 Краткая инструкция
- Logitech SPEAKER LAPDESK N550 Брошюра
- Logitech SPEAKER LAPDESK N550 Краткая инструкция
- Logitech Cooling Pad Краткая инструкция
- Prestigio Nobile PER3162BN Black Руководство пользователя
- Prestigio MultiPad 10.1 Ultimate PMP7100D_DUO Руководство пользователя
- Prestigio MultiPad 8.0 HD Black PMP5588C_Duo Руководство пользователя
- Philips hd 9320/21 Руководство пользователя
- Philips 47PFL7403D/10 Брошюра
- Philips 47PFL7403D/10 Краткая инструкция