Cuenod C.210 GX 507/8 T2 [8/56] Settings diffusers and injectors

Cuenod C.120 GX 507 T2 [8/56] Settings diffusers and injectors
03/2008 - Art. Nr. 13 013 477C8
Propane gas
Natural gases
Start-up
Settings
Diffusers and injectors
Factory setting
5 slots open to the outside (arrow) +1
slot inside on 1 diffuser A, according to
shutter E position.
Check that all 6 pierced screws F
M5x6 - Ø 3 (front injection) are present.
5 slots open to the outside (arrow) and
0 slot inside on 5 diffusers B, according
to shutter E position.
Recommended setting
3 slots open to the outside (arrow) +1
slot inside on 3 diffusers A according to
shutter E position (turn 180°).
Fix all 6 unpierced screws M5x6 found in
a bag on strut.
3 slots open to the outside (arrow) +0
slots inside on 3 diffusers B according to
shutter position E.