Indoor Unit
Installation
5. Mount the indoor unit. You will need two
people to lift and secure it. Insert suspension
bolts into the unit’s hanging holes. Fasten
them using the included washers and nuts
(See Fig. 3.5).
Fig. 3.5
NOTE: The bottom of the unit should be
24mm (0.9”) higher than the ceiling board.
Generally, L (indicated in Fig. 3.6) should be
half the length of the suspension bolt or long
enough to prevent the nuts from coming o.
Fig. 3.6
CAUTION
Ensure that the unit is completely level.
Improper installation can cause the drain pipe
to back up into the unit or water leakage.
Wall
Ceiling board
Main body
24mm (0.9”)
L
NOTE: Ensure that the indoor unit is level.
The unit is equipped with a built-in drain
pump and oat switch. If the unit is tilted
against the direction of condensate ows
(the drainpipe side is raised), the oat switch
may malfunction and cause water to leak.
Water level
Fig. 3.7
NOTE FOR NEW HOME INSTALLATION
When installing the unit in a new home, the
ceiling hooks can be embedded in advance.
Make sure that the hooks do not come loose
due to concrete shrinkage. After installing the
indoor unit, fasten the installation paper
template onto the unit with bolts (M6X12) to
determine in advance the dimension and
position of the opening on the ceiling.
Follow the instructions above for the
remainder of the installation.
Installation template
M6 x 12 Bolts
Main body
Fig. 3.8