Cyberpower UTC800E [2/2] On battery voltage s vac

Cyberpower UTC600E [2/2] On battery voltage s vac
Cyber Power Systems, Inc. All Rights Reserved.
www.cyberpower.com
Model Name
UTC650E
UTC650EI
UTC850E
UTC850EI
General
UPS Topology
Line-interactive
Line-interactive
Line-interactive
Line-interactive
Input
Generator Compatibility
Yes
Yes
Yes
Yes
Nominal Input Voltage (
Vac)
230
±
10%
230
±
10%
230
±
10%
230
±
10%
Input Voltage Range (Vac)
165 ~ 290
165 ~ 290
165 ~ 290
165 ~ 290
Input Frequency (Hz)
50
±
5, 60
±
5
50
±
5, 60
±
5
50
±
5, 60
±
5
50
±
5, 60
±
5
Input Frequency Detection
Auto-sensing
Auto-sensing
Auto-sensing
Auto-sensing
Rated Input Current (A)
2.73
2.73
3.64
3.64
Input Connector Type
Schuko
Schuko
Schuko
Schuko
Output
Capacity (VA)
650
650
850
850
Capacity (Watts)
360
360
425
425
On Battery Waveform
Simulated Sine Wave
Simulated Sine Wave
Simulated Sine Wave
Simulated Sine Wave
On Battery Voltage(s) (Vac)
230
±
10%
230
±
10%
230
±
10%
230
±
10%
On Battery Frequency (Hz)
50
±
1%, 60
±
1%
50
±
1%, 60
±
1%
50
±
1%, 60
±
1%
50
±
1%, 60
±
1%
Automatic Voltage Regulation (AVR)
Single Boost, Single Buck
Outlet(s)
- Total
2
4
2
4
Outlet Type
Schuko x 2
IEC C13 x 4
Schuko x 2
IEC C13 x 4
Outlet(s)
- Battery Backup
2
4
2
4
Typical Transfer Time (
ms)
4
4
4
4
Battery
Runtime at 60W (min)
28
28
30
30
Runtime at 90W (min)
16
16
20
20
Typical Recharge Time (Hours)
8
8
8
8
User
-replaceable
No
No
No
No
Battery Type
Sealed Lead-acid
Sealed Lead-acid
Sealed Lead-acid
Sealed Lead-acid
Surge Protection & Filtering
EMI/RFI Filtration
Yes
Yes
Yes
Yes
Management & Communications
LED Indicators
Power On, Line Mode, Battery Mode, Low Battery
Audible Alarms
Battery Mode, Low Battery, Overload, UPS Fault
Physical
Form Factor
Tower
Tower
Tower
Tower
Physical Size
- UPS Module
Dimensions (WxHxD) (mm.)
84 x 159 x 252
84 x 159 x 252
84 x 159 x 252
84 x 159 x 252
Weight (kg.)
3.8
3.8
4.2
4.2
Environmental
Operating Temperature (
°C)
0 ~ 40
0 ~ 40
0 ~ 40
0 ~ 40
Operating Relative Humidity
(
Non-condensing) (%)
0 ~ 90
0 ~ 90
0 ~ 90
0 ~ 90
Online Thermal Dissipation (BTU/
hr
)
40
40
40
40
Certifications
Certifications
CE, EAC
CE, EAC
CE, EAC
CE, EAC
RoHS
Yes
Yes
Yes
Yes
#All specifications are subject to change without notice. © 2017 Cyber Power Systems, Inc. All Trademarks are the property of
their owners.