Dungs DMV-D 503/11 Инструкция по монтажу онлайн [4/6] 404825

Dungs DMV-D 503/11 Инструкция по монтажу онлайн [4/6] 404825
4 … 6
Equipment variants of
DMV.../11 double solenoid valve,
single-stage mode
DMV-D
DMV-DLE
Sieve
Microlter element, two-layer
Refer to pressure losses
Gas pressure switch can be mounted:
on ange
downstream of sieve
downstream of valve 2 to adapter
downstream of valve 2
Valve V1, double-seat
Valve V2, single-seat
Valve V2, double-seat
Valves opening separately
Flange
Rp 3/8
Rp 1/2
Rp 3/4
Rp 1
Rp 1 1/4
Rp 1 1/2
Rp 2
G 1/2 ignition gas ange can be mounted
G 3/4 ignition gas ange can be mounted
= standard
() = on request
-- = not possible
Flow losses in (m
3
/h) air when in-
stalling the microlter element
Pressure loss [mbar]
2
5
10
20
40
70
DMV 503/11
()
DMV 503/11
0.15
0.25
0.30
0.33
0.36
0.39
DMV 507/11
()
DMV 507/11
1.20
1.70
1.80
1.90
2.30
2.50
DMV 512/11
()
DMV 512/11
9.0
11.0
13.2
16.0
18.4
22.5
DMV 520/11
()
DMV 520/11
17.5
21.5
27,0
34.5
45.0
56.0
DMV 525/11
DMV 525/11
Скачать