DMV-D/11 Two single-stage solenoid valves normally closed, fast opening, fast closing. Manual limitation of ow-
ing gas volume by main volume setting (D) at valve 1 (V1). Main volume setting (D) of DMV-D 503/11
at valve 2 (V2).
DMV-DLE/11
Two single-stage solenoid valves normally closed, slow opening (L), fast closing. Opening time setting
(E) with fast stroke section at valve 2 (V2). Manual limitation of owing gas volume by main volume
setting (D) at valve 1 (V1). Main volume setting (D) of DMV-D 503/11 at valve 2 (V2).
Specications
Nominal diameters
Flange with pipe thread as
per ISO 7-1
Max. operating pressure
Solenoid valve V1
Solenoid valve V2
Closing time
Opening time
Fast stroke
Main volume restrictor
Materials of gas conveying parts
Ambient temperature
Installation position
Dirt trap
Measuring gas connection
Ignition gas connection
Burner pressure monitor p
Br
Voltage/frequency
Rating / power consumption
Degree of protection
Switch-on duration
Electrical connection
Radio interference
Closed position signal contact
DMV 503 DMV 507 DMV 512, 520 DMV 525
Rp 3/8,Rp 1/2 Rp 1/2,Rp 3/4,Rp 1 Rp 1,Rp 1 1/4,Rp 1 1/2,Rp 2 Rp 2
and their combinations
500 mbar (50 kPa)
Automatic shut-o valve as per EN 161: Class A, Group 2
Automatic shut-o valve as per EN 161: Class A, Group 2
< 1 s
DMV-D…/11: < 1 s
DMV-DLE…/11: approx. 20 s at room temperature +20 °C and without fast stroke
Adjustable
DMV-D.../11 and DMV-DLE adjustable at V1, DMV-503/11 at V2
Housing: aluminium, steel, no non-ferrous metals
Seals at valve seat: NBR basis, suitable for gases as per G260/l
-15 °C to +60 °C
Solenoid vertically upright to lying horizontally
Sieve installed. To protect the complete gas train we recommend you to install
an upstream gas lter (refer to Datasheet 11.02)
G 1/8 DIN ISO 228 on both sides upstream of V1, between V1 and V2, down-
stream of V2 at input and output anges.
Pressure switch can be mounted to input and output anges. By mounting a
pressure switch, measuring/ignition gas connection can be partly excluded.
G 1/2 ignition gas ange as per ISO 228, possible on both sides between V1 and V2
Connection downstream of V2
GW...A2 pressure switch can be mounted to the adapter laterally and to the ange
50 - 60 Hz, 220 V - 240 V AC, -15 % +10 %, further voltages on request
Other preferred voltages: 50 - 60 Hz, 110 V - 120 V AC, 24 V - 28 V DC
at 230 V AC, +20 °C: refer to type overview
IP 54
100 %
Plug connection as per DIN EN 175301-803, PG* 11 cable gland on request
(* = heavy-gauge conduit thread)
Degree of interference N
Type K01/1 (DIN tested), can be mounted to V1 and V2, DMV-503/11 only to V2
Содержание
- Dmv d 11 dmv dle 11 1
- Double solenoid valve rp 3 8 rp 2 nominal diameters 1
- 0 7 1 7 1 0 6
- 0 8 2 8 1 4 6
- 1 6 0 7 1 0 6
- Density kg 6
- Dichte des verwendeten gases spec weight of gas used poids spécifique du gaz utilisé peso specifico del gas utilizzato 6
- Dichte luft spec weight air poids spécifique de l air peso specifico aria 6
- Dmv d 11 dmv dle 11 6
- Double solenoid valve flow diagram rp 3 8 rp 2 nominal diameters 6
- Gas type 6
- Head offices and factory karl dungs gmbh co kg siemensstraße 6 10 d 73660 urbach germany telephone 49 0 7181 804 0 fax 49 0 7181 804 166 6
- Nat gas city gas lpg air 6
- Postal address karl dungs gmbh co kg postfach 12 29 d 73602 schorndorf germany e mail info dungs com internet www dungs com 6
- We reserve the right to make any changes in the interest of technical progress 6
Похожие устройства
- Dungs DMV-D 5080/11 Сертификат
- Dungs DMV-D 5100/11 Инструкция по эксплуатации
- Dungs DMV-D 5100/11 Инструкция по монтажу
- Dungs DMV-D 5100/11 Сертификат
- Dungs DMV-D 5125/11 Инструкция по эксплуатации
- Dungs DMV-D 5125/11 Инструкция по монтажу
- Dungs DMV-D 5125/11 Сертификат
- Dungs DMV-DLE 503/11 Инструкция по эксплуатации
- Dungs DMV-DLE 503/11 Инструкция по монтажу
- Dungs DMV-DLE 503/11 Сертификат
- Dungs DMV-DLE 507/11 Инструкция по эксплуатации
- Dungs DMV-DLE 507/11 Инструкция по монтажу
- Dungs DMV-DLE 507/11 Сертификат
- Dungs DMV-DLE 512/11 Инструкция по эксплуатации
- Dungs DMV-DLE 512/11 Инструкция по монтажу
- Dungs DMV-DLE 512/11 Сертификат
- Dungs DMV-DLE 520/11 Инструкция по эксплуатации
- Dungs DMV-DLE 520/11 Инструкция по монтажу
- Dungs DMV-DLE 520/11 Сертификат
- Dungs DMV-DLE 525/11 Инструкция по эксплуатации