Ecoflam BLU 3000.1 PR TL - VGD 40.065 [13/40] Description of the control panel of the burner

Ecoflam BLU 3000.1 PR TC - VGD 40.065 [13/40] Description of the control panel of the burner
13
420010290100 BLU 3000.1 PR - BLU 4000.1 PR
EN
FIRING HEAD DISASSEMBLY
The ionization current is checked by inserting a
microammeter with an end of scale of 50 µA (d.c.) in
series with the ionization probe. A faulty position of the
electrode can lead to a reduction in the ionization cur-
rent and cause a safety cut-out of the burner due to a
flame detection failure. In this case, check the position
of the electrode, its electric connection and the earthing
of the burner.
24
min. 6 µA
LANDIS LFL1.622
Microamperometro
fondo scala 50 µA
IONIZATION CURRENT
Microammeter
50 µA end of scale
A
B
C
E
D
F
0
AUTO
0
I
A - selector :
0 =
operating elements locked in an
intermediate position
1 =
operation on maximum capacity
2 =
operation on minimum capacity
3 =
automatic operation
B - working lamp
C - termal lock-out lamp
D - fuse
E - main switch I / O
F - reset key
DESCRIPTION OF THE CONTROL PANEL OF THE BURNER