Ecoflam MAX GAS 70 P TW ТC - MB-DLE 405 [9/44] Installation must be carried out in compliance with the local provisions

Ecoflam MAX GAS 105 P TW ТC - MB-DLE 403 [9/44] Installation must be carried out in compliance with the local provisions
9
420010266501 Max Gas 40 P - 70 P - 105 P - 120 P
EN
Longueur chambre de combustion
d = diamètre chambre de combustion
12
24 40 70 100 190 480 1200 2450
0,1
0,2
0,3
0,4
0,5
0,6
1,0
2,0
3,0
4,0
d=0,5
(b)
(a)
kW
d=0,8
d=0,7
d=0,6
d=0,4
d=0,3
d=0,225
Installation must be carried out in compliance with the local provisions
The burners have been certified in combustion
chambers according to EN 676 standards. Consult
the burner manufacturer if the combustion cham-
ber of the boiler in which the burner is to be instal-
led has smaller dimensions.
STARTING-UP THE BURNER
PRELIMINARY CHECKS
Before starting up the boiler check the following: - gas type and feed pressure; - gas valves closed; - the seals in the pipe
fittings; - gas pipe breather and input pressure; - that the cable complies with the diagram and the phase and neutral
wires correspond; - that the burner shuts down when the boiler thermostat opens; - the seal of the boiler furnace which
prevents air from entering; - the seal on the flue-boiler pipe fitting; - the condition of the flue (sealed, free from blocka-
ge, etc ). If all these conditions are present, start the burner. The control device starts the motor to carry out prewashing
of the combustion chamber. During this prewash period (about 30 seconds) the device checks that air pressure is correct
via the air pressure switch. At the end, it supplies power to the transformer and opens the gas valves. The flame must be
lit and stabilize within 3 seconds, which is the device's safety time limit. Check to ensure the flame is lit before placing
any control instrument in the flue. Adjust and check the gas flow necessary for the boiler at the meter. Adjust the air
flow according to the gas flow to obtain correct combustion.
IMPORTANT ADVICE
All adjustable parts must be fixed by the installer after making adjustments. Check flue combustion after each adjusti-
ment. The CO
2
values must be approx. 9.7 (G20) 9.6 (G25 11.7 (13B) 11.7 (13P) axld the CO must be less than 75
ppm.
CB
A
E
D-D1
F
G
M
126
151
I
L
NP
O
MODEL A B C D D1 E F G I L M N O P
MAX GAS 40 P 288 143 145 85 185 153 89 160 92/107 92/107 M8 54 73 -
MAX GAS 70 P 303 155 148 85 185 204 89 160 100/120 100/120 M8 52 71 82
MAX GAS 105 P 317 169 148 140 220 204 89 160 100/120 100/120 M8 52 71 82
MAX GAS 120 P 317 169 148 160 240 204 98 160 100/120 100/120 M8 52 71 82
D = SHORT HEAD D1= LONG HEAD