20
420010334900 Max Gas 350 - 500 PR
EN
FIRING HEAD AND AIR SETTING
Error code table
Red blink code of «AL» at Possible cause
signal lamp (LED)) term. 10
2 blinks on No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
3 blinks on «LP» faulty
- Loss of air pressure signal after «t10», - «LP» welded in normal position
4 blinks on Extraneous light when burner is started up
5 blinks on Time out «LP»
- «LP» welded in working position
6 blinks on Free
7 blinks on Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
8 blinks on Free
9 blinks on Free
10 blinks off Wiring error or internal error, output contacts, other faults.
14 blinks on CPI contact not closed
MINIMAL ADJUSTMENT CAPACITY GAS
+
-
1
1 LIATED
3
3 LIATE
D
+
-
Head position : see the pre-calibrated diagram.
- To carry the burner in
low flame (using selector
on the electrical control
panel).
- To act on the screw in
figure (Detail 3).