Ecoflam MAX GAS 500 PR ТL - MB-DLE 415 350/500 [16/76] Max gas 350 500 pr

Ecoflam MAX GAS 350 PR ТC - MB-DLE 412 350/500 [16/76] Max gas 350 500 pr
16
420010334900 Max Gas 350 - 500 PR
EN
15010050 200
200100 300 400
250 300 350 400 450 500 550 600
0
1
2
3
4
5
6
7
8
9
mbar
kW
kcal/h
x 1000
MAX GAS 350
MAX GAS 500
500
WORKING FIELDS
Max Gas 350 Max Gas 500
Termal power max. kW 350 500
kcal/h 301.00 430.000
Termal power min. kW 70 70
kcal/h 60.200 60.200
TECHNICAL DATA
OPERATING FEATURES
Model : Max Gas 350 - 500 Gas family
G20 G25 G31 G30
Max. gas pressure* mbar 300 300 300 300
Min. gas pressure* mbar 17 17 17 17
Fuel L.C.V. kcal/Nm
3
8.570 7.370 22.260 29.320
Model : Max Gas 350
Gas flow rate max. 35,12 Nm
3
/h 40,84 Nm
3
/h 13,52 Nm
3
/h 10,26 Nm
3
/h
min. 7,02 Nm
3
/h 8,17 Nm
3
/h 2,70 Nm
3
/h 2,05 Nm
3
/h
Model : Max Gas 500
Gas flow rate max. 50,17 Nm
3
/h 58,34 Nm
3
/h 19,32 Nm
3
/h 14,66 Nm
3
/h
min. 7,02 Nm
3
/h 8,17 Nm
3
/h 2,70 Nm
3
/h 2,05 Nm
3
/h
Output
Backpressure in comb. chamber
OVERALL DIMENSIONS
* : Minimum/maximum gas inlet pressures depend by the gas train matched to the burner. The values are written on the gas trains manual.
Gas family : AT I
2H,
I
3B/P
BE I
2E(R)B,
I
3P
DE I
2E,
I
3B/P
DK I
2H,
I
3B/P
SE I
2H,
I
3B/P
ES I
2H,
I
3P
FI I
2H,
I
3B/P
FR I
2Er,
I
3B/P
GB I
2H,
I
3B/P
NL I
2L,
I
3B/P
GR I
2H,
I
3B/P
IE I
2H,
I
3B/P
IT I
2H,
I
3B/P
PT I
2H,
I
3B/P
MODEL A B C D D1 E F G I L M N O
MAX GAS 350 PR 510 302 208 175 335 466 157 280 185/200 185/200 M8 62 101
MAX GAS 500 PR 510 302 208 175 335 466 157 280 185/200 185/200 M8 62 101
D = SHORT HEAD D1= LONG HEAD
C
I
B
A
L
581
0
02
185
200
N
E
D-D1
O
G
F
M

Содержание

Похожие устройства

Скачать