- 22 -
EN
420010404000 Maxflam D 10-20
-
+
-
+
AIR REGULATION SUCTION SIDE
123
FIRING HEAD SETTING
ADJUSTMENT DATA
NOZZLE PUMP OUTPUT FIRING HEAD SETTING AIR DAMPER ADJUSTMENT
gph spry bar kg/h Pos. Pos.
1.00 60°HO 23 6 1 2,20
1.25 60°HO 23 8 1 2,80
1.50 60°HO 23 9,5 1 3,50
2.00 60°HO 21 12 2 4,50
1.50 60°HO 23 9,5 1 3,50
2.00 60°HO 23 12,50 2 4,50
2.50 60°HO 23 15,80 2 5,50
3.00 60°HO 23 20 3 8
Maxflam D 10
Maxflam D 20
- At the end of the prepurging, the control box shut off the solenoid valve “O” while opening the 1st stage
valve (for example valve “A”), allowing the burner ignition in Low Flame.
- In order to have a correct combustion, adjust the combustion air flow (see figure).
- The fuel pressure during burners working shall be set to 23 bars.
-
L
+
ADJUSTEMENT OF PRESSURE IN PREPURGING PHASE