Ecoflam OILFLAM 200.1 AB ТC [22/84] Oilflam 80 200 ab

Ecoflam OILFLAM 170.1 AB ТL [22/84] Oilflam 80 200 ab
- 22 -
EN
420010488900 OILFLAM 80.1÷200.1 AB
SIEMENS LMO 44 CONTROL INFORMATION SYSTEM
In case of burner lockout, it is possible to read which cause originated it. Proceed as follows: with the burner in lockout
mode (red LED switched on) keep pressed the lockout button for more than 3 sec. then release it. The red LED will blink
according to the following error code list:
I
I
I
I - Low Flame
II - High Flame (with possible HIGH/LOW automatic switching through a second thermostat connected to
terminal board, as for scheme).
ADJUSTEMENT OF PUMP PRESSURE
-
D
+
ADJUSTEMENT OF PRESSURE IN PREPURGING PHASE
Error Code Possible cause
2 blinks No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner,
no fuel - Faulty ignition
3 blinks Free
4 blinks Extraneous light on burner start-up
5 blinks Free
6 blinks Free
7 blinks Too many losses of flame during operation (limitation of the number of repetitions)
- Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner
8 blinks Time supervision oil pre-heater
9 blinks Free
10 blinks Wiring error or internal error, output contacts

Содержание

Скачать