SAWO Dragonfire DRF3-60NS [15/20] Air ventilation

SAWO Dragonfire DRF3-60NS [15/20] Air ventilation
15
Air Ventilation
To have a soothing sauna, there should be a proper mixing of hot and cold air
inside the sauna room. Another reason for ventilation is to draw air around the
heater and move the heat to the farthest part of the sauna. The positioning of
the inlet and outlet vents may vary depending on the design of the sauna
room or preference of the owner.
The inlet vent may be installed on the wall directly below the heater (Fig. 5a).
When using the mechanical ventilation, the inlet vent may be placed at least
60 cm above the heater (Fig 5b) or on the ceiling above the heater (Fig. 5c).
Through these positions, the heavy cold air that is blown into the sauna is
mixed with the light hot air from the heater, bringing fresh air for the bathers to
breathe. The recommended size for the inlet vent is 5-10 cm.
The outlet vent should be placed diagonally opposite to the inlet. It is
recommended that the outlet vent be placed under the platform in a sauna as
far as possible from the fresh air vent. It may be installed near the floor, or led
outside through a pipe from the floor going to a vent to the sauna ceiling, or
under the door (to the washroom). In this case, the sill slot must be at least 5
cm and it is recommended that there is mechanical ventilation in the
washroom. The size of the exhaust should be twice that of the inlet.
Insulation
The sauna must have proper insulation on the walls, ceiling and door. One
square meter (m²) of un-insulated surface increases the cubic volume by
approximately 1.2m³ when determining the power requirement of the heater.
Refer to page 18 (Technical Data).
Ensure that moisture proofing is appropriate in the sauna room. The purpose
of this is to prevent spreading of moisture to the other rooms or wall structure.
Moisture proofing must be placed between heating insulation and panel.
Thermal and moisture proofing need to be installed according to the following
order from outside to inside.
The recommended minimum thickness of the thermal
insulation in the walls is 50 mm and in the ceiling 100 mm.
It is possible to use carton- or aluminum foil laminate as a
vapor barrier, which is affixed over the insulation aluminum
foil inwards.
Leave at least 20 mm air slot between vapor barrier and
inside panel
To prevent gathering of the moisture behind the panel, leave
the slot between wall panel and ceiling.
1.
2.
3.
4.
ENGLISH

Содержание

Скачать