ABB ACS550-01-012A-4+B055 Краткое руководство онлайн

ACS550
Quick Start Guide
ACS550-01 Drives (0.75…160 kW),
IP21 / UL Type 1 Enclosure
Overview
The installation of the ACS550 adjustable
speed AC drive follows the outline below.
Application
This guide provides a quick reference for
installing ACS550-01 drives having a standard
enclosure.
Note: This guide does not provide detailed
installation, safety or operational
instructions. See ACS550 User’s Manual for
complete information.
Prepare for installation
WARNING! The ACS550 should ONLY be
installed by a qualified electrician.
Unpack the drive
Note: Lift the ACS550 by its chassis and not by its
cover.
1. Unpack the drive.
2. Check for any damage.
3. Check the contents against the order / shipping
label.
Check
• Motor compatibility – Motor type, nominal
current, frequency and voltage range must
match drive specifications.
• Suitable environment – Drive requires heated,
indoor controlled environment that is suitable
for the selected enclosure.
• Wiring – Follow local codes for wiring, circuit
protection and EMC requirements.
Refer to User’s Manual and confirm that all
preparations are complete.
Drive identification
Use the following chart to interpret the type
code found on the drive label.
Collect motor data
Collect the following data from the motor
nameplate for later use in the ACS550 startup:
• Voltage __________________________
• Nominal motor current ______________
• Nominal frequency _________________
• Nominal speed ____________________
• Nominal power ____________________
Tools required
Screwdrivers, wire stripper, tape measure,
mounting screws or bolts and drill.
Prepare the mounting location
The drive requires a
smooth, vertical, solid
surface, free from heat and
moisture, with free space for
air flow – 200 mm (8 in)
above and below.
1. Mark the mounting points
using the template.
2. Drill the mounting holes.
Remove the front cover
1. Remove the
control panel, if
attached.
2. Loosen the
captive screw
at the top.
3. Pull near the
top to remove
the cover.
Mount the drive
1. Position the ACS550 and
use screws or bolts to
securely tighten all four
corners.
Note: Lift the ACS550 by its
metal chassis.
2. Non-English speaking
locations: Attach a
warning sticker in the appropriate language
over the existing warning on the top of the
module.
Install the wiring
Wiring power
1. Open the appropriate
knockouts in the gland box.
2. Install the cable clamps for
the power/motor cables.
3. On the input power cable,
strip the sheathing back far
enough to route individual wires.
4. On the motor cable,
strip the sheathing
back far enough to
expose the copper wire
shield so that the
shield can be twisted
into a bundle. Keep the
bundle not longer than
five times its width to minimize noise radiation.
– 360° grounding under the clamp is
recommended for the motor cable to minimize
noise radiation. In this case, remove the
sheathing at the cable clamp.
5. Route both cables through the clamps.
6. Connect the bundle created from the motor
cable shield to the GND terminal.
7. Strip and connect the power/motor wires and
the power ground wire to the drive terminals
using the torques given in the table below. See
Power connections below or, for more detail,
see User’s Manual.
8. Install conduit/gland box and tighten the cable
clamps.
WARNING! To disconnect the internal EMC
filter, remove the screws marked with “-”, or
replace the screws marked with “ ” with the
provided polyamide screws, depending on
the frame size.
9. Install the cable clamp(s) for
the control cable(s). (Power/
motor cables and clamps
not shown in the figure.)
PREPARE for installation
PREPARE mounting location
REMOVE the front cover
MOUNT the drive
INSTALL wiring
CHECK installation
REINSTALL the cover
APPLY power
START-UP
Serno
ACS550-01-08A8-4
*2030700001*
U1 3~ 380...480 V
I2N/ I2hd 8.8/6.9 A
PN/Phd 4.0/3.0 kW
ACS550-01-08A8-4+J404+…
AC, Standard Drive – 550 series
See Ratings in User’s Manual for details
Construction (region specific)
Output current rating
Voltage rating
2 = 208…240 V AC
4 = 380…480 V AC
6 = 500…600 V AC
Examples of options:
No specification = IP21 / UL type 1
B055 = IP54 / UL type 12
UL type 12 is not available for type
ACS550-01-290A-4.
0J400 = No control panel
J404 = ACS-CP-C Basic Control Panel
01 = Setup/parts for IEC install./compliance
U1 = Setup/parts for US install./compliance
Options
X0002
1
3
IP2000
1
2
IP2002
1
2
Frame
size
Tightening torque
N·m
lb·ft
R1, R2 1.4
1
R3 2.5
1.8
R4 5.6; PE: 2
4; PE 1.5
R5 15
11
R6 40; PE: 8
30; PE: 6
System type R1...R3 R4 R5...R6
EM1 EM3 EM1 EM3 F1 F2
IT system
----
Corner grounded TN
system
-
1
2
X0004
3
IP2001
4
8
6
7
7
X0005
8
9
X0006
Содержание
- Acs550 1
- Acs550 01 drives 0 5 160 kw ip21 ul type 1 enclosure 1
- Application 1
- Collect motor data 1
- Drive identification 1
- Install the wiring 1
- Mount the drive 1
- Overview 1
- Prepare for installation 1
- Prepare the mounting location 1
- Quick start guide 1
- Remove the front cover 1
- Tools required 1
- Unpack the drive 1
- Wiring power 1
- Align the cover and slide it on 2 tighten the captive screw 3 install the control panel 2
- Always reinstall the front cover before turning power on 2
- Apply input power when power is applied to the acs550 the green led comes on 2
- Apply power 2
- Assistant control panel 2
- Basic control panel 2
- Before applying power perform the following checks 2
- Check installation 2
- Command is on 2
- Connect the ground shield bundle for digital and analog i o cables at x1 1 ground only at the drive end 2
- Control connections 2
- In start up enter motor data collected earlier and if needed edit parameters that define how the drive operates and communicates 2
- Inputs is 30 v 2
- Install the conduit gland box cover 1 screw 2
- Note before increasing motor speed check that 2
- Note for common parameters and menu items use the help key to display descriptions if you encounter alarms or faults use the help key or refer to chapter diagnostics in 2
- Power connections 2
- Power connections wiring the controls 2
- Reinstall the cover 2
- Route control cable s through clamp s and tighten clamp s 2
- Start up 2
- Strip and connect the individual control wires to the drive terminals use a tightening torque of 0 n m 0 lb ft see control connections below or for more information see user s manual 2
- Strip control cable sheathing and twist the copper shield into a bundle 2
- The basic control panel does not include the start up assistant refer to section how to start up the drive in user s manual and manually enter any parameter changes desired 2
- The motor is running in the desired direction 2
- The start up assistant steps through typical start up selections and runs automatically upon the initial power up at other times use the steps below to run the start up assistant 2
- Use the menu key to access the main menu 2 select assistants 3 select start up assistant 4 follow the screen instructions to configure the system 2
- User s manual 2
- Warning the acs550 will start up automatically at power up if the external run 2
- Warning the maximum voltage for digital 2
- Wiring the controls 2
Похожие устройства
- ABB ACS550-01-012A-4+B055 Установочная схема
- Junkers Ceraclass Excellence ZSC 24 - 3 MFA Инструкция по эксплуатации
- ABB MFDT-01 Руководство пользователя
- Junkers Ceraclass Excellence ZSC 28 - 3 MFA Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZSC 35 - 3 MFA Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZWC 24 - 3 MFA Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZWC 28 - 3 MFA Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZWC 35 - 3 MFA Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZSC 24 - 3 MFК Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZSC 28 - 3 MFК Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZWC 24 - 3 MFК Инструкция по эксплуатации
- Junkers Ceraclass Excellence ZWC 28 - 3 MFК Инструкция по эксплуатации
- Junkers EUROLINE ZS 23-1 KE 23 Инструкция по эксплуатации
- Junkers EUROLINE ZS 23-1 KE 31 Инструкция по эксплуатации
- Junkers EUROLINE ZW 23-1 KE 23 Инструкция по эксплуатации
- Junkers EUROLINE ZW 23-1 KE 31 Инструкция по эксплуатации
- ABB ACH550-01-012A-4 Габаритный чертёж
- ABB ACH550-01-012A-4 Инструкция по установке
- ABB ACH550-01-012A-4 Руководство по реформированию конденсатора
- ABB ACH550-01-012A-4 Руководство пользователя