CAPACITOR REFORMING
Inspection Instruction
3AFE 6873 5190
00522808_G.DOC
Dept.
Project
ORANGE
Status Date
05.May 2010
Author
Haapala Mari
Status
APPROVED/DAVIDSAINEN JANNE
Revision
G
Page
1 / 5
GUIDE FOR CAPACITOR REFORMING IN ACS50, ACS55,
ACS150, ACS310, ACS350, ACS355, ACS550, ACH550 and
R1-R4 OINT-/SINT-boards.
1 Reforming
The drive DC link capacitors need to be reformed (re-aged) if the drive has been non-
operational for more than one year. Without reforming, capacitors may be damaged
when the drive starts to operate. The reforming methods introduced in this instruction
require that the drive has been stocked clean and dry. It is recommended to reform the
capacitors once a year.
1.1 How to check the drive’s age
Check the date of manufacture for the drive from the serial number shown on the drive
labels. The serial number defines the year and week when the drive was manufactured.
There are two formats of serial numbers. Check which format the drive has and
determine the date of manufacture:
Format 1:
YWWXXXXX (8 digits)
Y = year (...6,7,8,9,A,B... for ...2006, 2007, 2008, 2009, 2010, 2011...)
WW = week
Format 2:
XYYWWXXXXX (10 digits)
YY = year (...06,07,08,09,10... for ...2006, 2007, 2008, 2009, 2010...)
WW = week