Parameter listing and descriptions 177
ACH550-01 User's Manual
0176 SAVED AMOUNT 1 0.0…999.9
Energy saved in local currency (remainder when the total saved energy
is divided by 1000). See the note on page 293.
To find out the total saved energy in currency units, add the value of
parameter 0177 multiplied by 1000 to the value of parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123.4
0177
SAVED AMOUNT 2 = 5
Total saved energy = 5 · 1000 + 123.4 = 5123.4 currency units.
The counter value is accumulated till it reaches 999.9 after which the
counter rolls over and starts again from 0.0 and the counter value of
signal 0177 is incremented by one.
Can be reset with parameter 4509
ENERGY RESET (resets all energy
calculators at the same time).
Local energy price is set with parameter 4502
ENERGY PRICE.
•See Group 45: ENERGY SAVING.
0177 SAVED AMOUNT 2 0…65535
Energy saved in local currency in thousand currency units. Eg value 5
means 5000 currency units. See the note on page 293.
The counter value is accumulated till it reaches 65535 (the counter
does not roll over).
See parameter 0176
SAVED AMOUNT 1.
0178 SAVED CO2 0…6553.5 tn
Reduction on carbon dioxide emissions in tn. See the note on page 293.
The counter value is accumulated till it reaches 6553.5 (the counter
does not roll over).
Can be reset with parameter 4509
ENERGY RESET (resets all energy
calculators at the same time).
CO2 conversion factor is set with parameter 4507
CO2 CONV FACTOR.
•See Group 45: ENERGY SAVING.