ABB ACH550-01-06A9-4+B055 [402/476] Symbols
![ABB ACH550-01-157A-4 [402/476] Symbols](/views2/1556843/page402/bg192.png)
398 Technical data
ACH550-01 User's Manual
Symbols
Typical ratings:
Nominal rating (10% overload capability)
I
2N
continuous rms current. 10% overload is allowed for one
minute every ten minutes through the whole speed
range.
P
N
typical motor power. The kilowatt power ratings apply to
most IEC, 4-pole motors. The horsepower ratings apply
to most 4-pole NEMA motors.
Sizing
The current ratings are the same regardless of the supply
voltage within one voltage range. To achieve the rated motor
power given in the table, the rated current of the drive must be
higher than or equal to the rated motor current.
In multimotor systems, the output current of the drive must be
equal or greater than the calculated sum of the input currents of
all motors.
1 minute 9 minutes 1 minute
I
N
1.1 · I
N
Содержание
- Ach550 1
- Ach550 01 drive manuals 2
- Table of contents 5
- Document library on the internet 471 9
- Compatibility 11
- Contents of this manual 11
- Intended audience 11
- Intended use 11
- What this chapter contains 11
- Electrical safety 12
- General safety 12
- Safety instructions 12
- Use of warnings and notes 12
- Control of the drive and motor 14
- Maintenance 14
- Drive package 15
- Lifting the drive 16
- Preparing for installation 17
- What this chapter contains 17
- Drive identification 18
- Ip54 drive labels 18
- Ip21 drive labels 19
- Ach550 01 user s manual 20
- Preparing for installation 20
- Serial number 20
- Serial number is of format cyywwxxxxx where c country of manufacture yy year of manufacture ww week of manufacture 01 02 03 for week 1 week 2 week 3 xxxxx integer starting every week from 00001 20
- The contents of the drive type designation shown on the labels are described below 20
- The format of the drive serial number shown on the labels is described below 20
- Type designation 20
- Frame size 21
- Ach550 01 user s manual 23
- An example motor rating plate for an iec motor is shown below 23
- Collect the following information voltage nominal motor current nominal frequency nominal speed nominal power 23
- Motor identification 23
- Preparing for installation 19 23
- Motor compatibility 25
- Suitable environment and enclosure 26
- Suitable mounting location 27
- Wiring and emc considerations 30
- Cabling instructions 32
- Input power mains cables 32
- Motor cables 32
- Ach550 01 user s manual 33
- Allowed ce c tick 33
- Figures courtesy of draka nk cables copyright 2003 draka nk cables 33
- Preparing for installation 29 33
- Recommended ce c tick 33
- The figure below shows non recommended motor cable types 33
- The figure below shows the recommended conductor layout 33
- Effective motor cable shields 34
- Ach550 01 user s manual 35
- At the motor end the motor cable shield must be grounded 360 degrees with an emc cable gland or the shield wires must be twisted together into a bundle pigtail not longer than five times its width and connected to the pe terminal of the motor the same principle applies to cabinet installations 35
- Preparing for installation 31 35
- The figure below shows the grounding principles of cables 35
- Control cables 36
- General recommendation 36
- Analogue cables 38
- Control panel operator keypad cable 38
- Digital cables 38
- Tools required 39
- Checklist for installation preparations 40
- Ach550 01 user s manual 41
- For flange mounting mounting the drive in a cooling air duct see the appropriate flange mounting instructions 41
- Installing the drive 41
- Installing the drive 37 41
- Note the ach550 should only be mounted where all of the requirements defined in chapter preparing for installation are met and the checklist has been completed 41
- This chapter contains the mechanical and electrical installation procedure of the drive 41
- Warning before installing the ach550 ensure the input power supply to the drive is off 41
- What this chapter contains 41
- Preparing the mounting location 42
- Removing front cover ip54 43
- Removing front cover ip21 44
- Mounting the drive ip54 45
- Mounting the drive ip21 46
- Ach550 01 user s manual 47
- Installing the drive 43 47
- Overview of wiring installation r1 r4 47
- The figure below shows an overview of the terminal layout for frame sizes r1 r4 47
- Warning to avoid danger or damage to the drive on it systems corner grounded tn systems and residual current circuit breakers see section disconnecting the internal emc filter on page 45 47
- Ach550 01 user s manual 48
- Installing the drive 48
- Overview of wiring installation r5 r6 48
- The figures below show the general terminal layouts for frame sizes r5 r6 48
- Warning to avoid danger or damage to the drive on it systems corner grounded tn systems and residual current circuit breakers see section disconnecting the internal emc filter on page 45 48
- Disconnecting the internal emc filter 49
- Checking the insulation of the assembly 50
- Motor and motor cable 50
- Supply cable 50
- Power wiring ip54 51
- Ach550 01 user s manual 53
- Frame size r6 lugs 53
- Installing the drive 49 53
- Note check the cable lengths according to section wiring and emc considerations on page 26 53
- Tightening torques tightening torques 53
- Power wiring r1 r3 ip54 units with main switch option f278 54
- Ach550 01 user s manual 58
- Connect the control cables see control wiring ip54 on page 55 12 replace the front cover see re install cover ip54 on page 63 58
- Installing the drive 58
- Tightening torques 58
- Control wiring ip54 59
- Power wiring ip21 60
- Control wiring ip21 63
- Check installation 65
- Re install cover ip54 67
- Re install cover ip21 68
- Apply power 69
- Control panel compatibility 71
- Hvac control panel ach cp b features 71
- Start up and control panel 71
- What this chapter contains 71
- A 0 hz 72
- Parameters assistants changed par 72
- Start up 72
- Start up by using the start up assistant 72
- A 0 hz 74
- Ach550 01 user s manual 74
- Hvac default 74
- Parameters assistants changed par 74
- Press exit to return to the listing of parameter groups and again to return to the main menu 74
- Press menu to go to the main menu 74
- Press save to store the modified value or press cancel to leave the set mode any modifications not saved are cancelled 74
- Press the up down keys to change the parameter value 74
- Select parameters with the up down keys and press enter to go to the parameters mode 74
- Select the appropriate parameter group with the up down keys and press sel 74
- Select the appropriate parameter in a group with the up down keys press edit to change the parameter value 74
- Start up and control panel 74
- Start up by changing the parameters individually 74
- Supply fan 74
- To change the parameters follow these steps 74
- To complete the control connections by manually entering the parameters see chapter parameter listing and descriptions 74
- A 0 hz 76
- Output standard display mode 76
- Status information 76
- A 0 hz 3 77
- Operating the drive 77
- A 0 hz 78
- Ach550 01 user s manual 78
- Hvac default 78
- Parameters assistants changed par 78
- Parameters mode 78
- Press exit to return to the listing of parameter groups and again to return to the main menu 78
- Press menu to go to the main menu 78
- Press save to store the modified value or press cancel to leave the set mode any modifications not saved are cancelled 78
- Press the up down keys to change the parameter value 78
- Select parameters with the up down keys and press enter to go to the parameters mode 78
- Select the appropriate parameter group with the up down keys and press sel 78
- Select the appropriate parameter in a group with the up down keys press edit to change the parameter 78
- Start up and control panel 78
- Supply fan 78
- To change the parameters follow these steps 78
- To complete the control connections by manually entering the parameters see chapter parameter listing and descriptions 78
- A 0 hz 80
- Assistants mode 80
- Parameters assistants changed par 80
- A 0 hz 81
- Ach550 01 user s manual 81
- After completing a task the start up assistant asks if you want to continue with the next one press ok when continue is highlighted to continue with the next task select skip with the up down keys and press ok to move to the next task without doing this one or press exit to stop the start up assistant 81
- After selecting the macro specify whether you want to use the mechanical hand off auto switch 81
- Parameters assistants changed par 81
- Press menu to go to the main menu 81
- Scroll to the assistant you want to use references 1 2 is used here as an example with the up down keys and press sel 81
- Select assistants with the up down keys and press enter 81
- Start up and control panel 77 81
- The start up assistant will guide you through the start up to start an individual assistant from the menu follow these steps 81
- A 0 hz 84
- Changed parameters mode 84
- Parameters assistants changed par 84
- Drive parameter backup mode 85
- A 0 hz 88
- Ach550 01 user s manual 88
- Fault logger time date par backup 88
- Press menu to go to the main menu 88
- Scroll to upload to panel and press sel note that the drive has to be in the off mode for uploading parameters 88
- Select par backup with the up down keys and press enter 88
- Start up and control panel 88
- Text copying parameters and a progress diagram are displayed press abort if you want to stop the process 88
- Text parameter upload successful is displayed press ok to return to the par backup menu press exit twice to go to the main menu now you can disconnect the control panel 88
- To upload parameters to the control panel follow these steps 88
- A 0 hz 89
- Ach550 01 user s manual 89
- After the download stops the message parameter download successfully completed is displayed press ok to return to the par backup menu press exit twice to go to the main menu 89
- Fault logger time date par backup 89
- Press menu to go to the main menu 89
- Scroll to download full set and press sel note that the drive has to be in the off mode for downloading parameters 89
- Select par backup with the up down keys 89
- Start up and control panel 85 89
- Text downloading parameters full set is displayed press abort if you want to stop the process 89
- To download the full set of parameters to a drive follow these steps 89
- A 0 hz 90
- Ach550 01 user s manual 90
- Fault logger time date par backup 90
- Note if upload or download of parameters is aborted the partial parameter set is not implemented 90
- Press menu to go to the main menu 90
- Scroll to download application and press sel note that the drive has to be in the off mode for downloading applications 90
- Select par backup with the up down keys 90
- Start up and control panel 90
- Text downloading parameters application is displayed press abort if you want to stop the process 90
- Text parameter download successfully completed press ok to return to par backup menu press exit twice to go to the main menu 90
- To download the application partial parameter set to a drive follow these steps 90
- A 0 hz 91
- Ach550 01 user s manual 91
- After the download stops the message parameter download successfully completed is displayed press ok to return to the par backup menu press exit twice to go to the main menu 91
- Fault logger time date par backup 91
- Press menu to go to the main menu 91
- Scroll to download user set1 user set2 overr set and press sel note that the drive has to be in the off mode for downloading user sets 91
- Select par backup with the up down keys 91
- Start up and control panel 87 91
- Text downloading parameters user set 1 user set 2 override set is displayed press abort if you want to stop the process 91
- To download the user set 1 user set 2 or override set to a drive follow these steps 91
- A 0 hz 92
- Ach550 01 user s manual 92
- Change par fault logger time date 92
- Press menu to go to the main menu 92
- Scroll to clock visibility with the up down keys and press sel to change the visibility of the clock 92
- Scroll to show clock with the up down keys and press sel to make the clock visible 92
- Scroll to time date with the up down keys and press enter to go to the time and date mode 92
- Scroll to time format with the up down keys and press sel 92
- Start up and control panel 92
- The time and date mode is used for setting the time and date for the internal clock of the ach550 in order to use the timed functions of the ach550 the internal clock has to be set first date is used to determine weekdays it is shown in fault logs to set the clock follow these steps 92
- The time formats are displayed select a format with the up down keys and press sel to confirm the selection 92
- Time and date mode 92
- Ach550 01 user s manual 93
- Cancel ok 93
- Change the days months and year with the up down keys and press ok to save the values the active value is highlighted in inverted colour 93
- Change the hours and minutes with the up down keys and press ok to save the values the active value is highlighted in inverted colour 93
- Scroll to date format with the up down keys and press sel 93
- Scroll to daylight saving with the up down keys and press sel 93
- Scroll to set date with the up down keys and press sel 93
- Scroll to set time with the up down keys and press sel 93
- Start up and control panel 89 93
- The date formats are displayed select a format with the up down keys and press ok to confirm the selection 93
- Ach550 01 user s manual 94
- Press exit twice to return to the main menu 94
- Start up and control panel 94
- To disable automatic clock transitions according to the daylight saving changes select off with the up down keys and press ok to enable automatic clock transitions select the country or area whose daylight saving changes are followed and press ok if you press help you can view the beginning and end dates of the period during which daylight saving time is used in each country or area 94
- A 0 hz 95
- Ach550 01 user s manual 95
- I o settings mode 95
- Press exit three times to return to the main menu 95
- Press menu to go to the main menu 95
- Scroll to i o settings with the up down keys and press enter 95
- Scroll to the i o setting you want to view with the up down keys and press sel 95
- Select the setting you want to view with the up down keys and press ok 95
- Start up and control panel 91 95
- The i o settings mode is used for viewing and editing the i o settings to view and edit the i o settings follow these steps 95
- Time date par backup i o settings 95
- You can change the value with the up down keys and save it by pressing save if you do not want to change the setting press cancel 95
- A 0 hz 96
- Assistants changed par fault logger 96
- Fault logger mode 96
- Application macros and wiring 97
- Applications 97
- What this chapter contains 97
- A 0 hz 98
- Ach550 01 user s manual 98
- Application macros and wiring 98
- Hvac default 98
- If you want to use the mechanical hand off auto switch press ok if you do not want to use it select no with the down key and then press ok to be able to use the switch ext1 hand start command must be connected to di1 and ext2 auto start command to di6 98
- Parameters assistants changed par 98
- Press menu to go to the main menu 98
- Scroll to application and press sel 98
- Select a macro with the up down keys and press save 98
- Select assistants with the up down keys and press enter 98
- Selecting an application macro 98
- To select an application macro follow these steps 98
- Restoring defaults 99
- Hvac default 100
- Ach550 01 user s manual 101
- Application macros and wiring 97 101
- Hvac default 101
- Supply fan 102
- Ach550 01 user s manual 103
- Application macros and wiring 99 103
- Supply fan 103
- Return fan 104
- Ach550 01 user s manual 105
- Application macros and wiring 101 105
- Return fan 105
- Cooling tower fan 106
- Ach550 01 user s manual 107
- Application macros and wiring 103 107
- Cooling tower fan 107
- Condenser 108
- Ach550 01 user s manual 109
- Application macros and wiring 105 109
- Condenser 109
- Booster pump 110
- Ach550 01 user s manual 111
- Application macros and wiring 107 111
- Booster pump 111
- Pump alternation 112
- Ach550 01 user s manual 113
- Application macros and wiring 109 113
- Pump alternation 113
- Internal timer 114
- Ach550 01 user s manual 115
- Application macros and wiring 111 115
- Internal timer 115
- Internal timer with constant speeds powered roof ventilator 116
- Ach550 01 user s manual 117
- Application macros and wiring 113 117
- Internal timer with constant speeds 117
- Floating point 118
- Ach550 01 user s manual 119
- Application macros and wiring 115 119
- Floating point 119
- Dual setpoint pid 120
- Ach550 01 user s manual 121
- Application macros and wiring 117 121
- Dual setpoint pid 121
- Dual setpoint pid with constant speeds 122
- Ach550 01 user s manual 123
- Application macros and wiring 119 123
- Dual setpoint pid with constant speeds 123
- E bypass usa only 124
- Ach550 01 user s manual 125
- Application macros and wiring 121 125
- E bypass 125
- Hand control 126
- Ach550 01 user s manual 127
- Application macros and wiring 123 127
- Hand control 127
- Ach550 01 user s manual 128
- Application macros and wiring 128
- Connection examples of two wire and three wire sensors 128
- Many ach550 applications use process pi d and need a feedback signal from the process the feedback signal is typically connected to analogue input 2 ai2 the macro wiring diagrams for each macro earlier in this chapter use an externally powered sensor connections not shown the figures below give examples of connections using a two wire or three wire sensor transmitter supplied by the drive auxiliary voltage output 128
- Note the sensor is supplied through its current output and the drive feeds the supply voltage 24 v thus the output signal must be 4 20 ma not 0 20 ma 128
- Three wire sensor transmitter 128
- Two wire sensor transmitter 128
- Ach550 01 user s manual 129
- Application macros and wiring 125 129
- Connection for obtaining 0 10 v from analogue outputs 129
- To obtain 0 10 v from analogue outputs connect a 500 ohm resistor or two 1 kohm resistors in parallel between the analogue output and analogue output circuit common agnd examples for analogue output 2 ao2 are shown in the figure below 129
- Real time clock and timed functions 131
- What this chapter contains 131
- Ach550 01 user s manual 132
- Real time clock and timed functions 132
- Using the timer 132
- You can use the timed functions assistant for easy configuring for more information on the assistants see page 76 the timer is configured in four stages they are 1 enabling the timer configure how the timer is activated see page 130 2 setting the time period define the time and day when the timer operates see page 131 3 creating the timer assign the selected time period to certain timer s see page 132 4 connecting the parameters connect selected parameters to the timer see page 133 132
- Parameters connected to a timer 133
- A 0 hz 134
- Ach550 01 user s manual 134
- After selecting the new value press save to save the value 134
- Di1 inv 134
- Enabling the timer 134
- Not sel 134
- Parameters s assistants changed par 134
- Press menu to go to the main menu 134
- Real time clock and timed functions 134
- Scroll to group 36 timed functions with the up down keys and press sel 134
- Scroll to timers enable with the up down keys and press edit 134
- Select parameters with the up down keys then press enter to go to the parameters mode 134
- The current value is displayed use the up down keys to change the value if you select active 7 timed functions are always enabled 134
- The new value is displayed below the timers enable text press exit twice to return to the main menu 134
- The timer can be enabled from one of the digital inputs or inverted digital inputs to enable the timer follow these steps 134
- A 0 hz 135
- Ach550 01 user s manual 135
- Change the highlighted part of the time with the up down keys pressing next moves to the next part press save to save the time 135
- Note start or run enable can be assigned to the same digital input 135
- Parameters assistants changed par 135
- Press menu to go to the main menu 135
- Real time clock and timed functions 131 135
- Scroll to group 36 timed functions with the up down keys and press sel 135
- Scroll to start time 1 with the up down keys and press edit 135
- Select parameters with the up down keys then press enter to go to the parameters mode 135
- Setting the time period 135
- The example shows how to set a start time in addition the stop time and the start and stop days have to be set in the same manner these constitute a time period 135
- A 0 hz 136
- Ach550 01 user s manual 136
- Creating a timer 136
- Different time periods can be collected in a timer and connected to parameters the timer can act as the source of start stop and change direction commands constant speed selection and relay activation signals time periods can be in multiple timed functions but a parameter can only be connected to a single timer it is possible to create up to four timers to create a timer follow these steps 136
- Not sel 136
- Parameters assistants changed par 136
- Press menu to go to the main menu 136
- Real time clock and timed functions 136
- Scroll to group 36 timed functions with the up down keys and press sel 136
- Scroll to timer 1 src with the up down keys and press edit 136
- Select parameters with the up down keys then press enter to go to the parameters mode 136
- The current value is displayed change the value with the up down keys 136
- The new value is displayed below the start time 1 text press exit to return to the main menu continue with stop time 1 start day 1 and stop day 1 136
- A 0 hz 137
- Ach550 01 user s manual 137
- Connecting parameters 137
- Has to be connected to the timer so that the timer acts as the source of constant speed activating a parameter can only be connected to one timer to connect the parameter follow these steps 137
- Parameters assistants changed par 137
- Press menu to go to the main menu 137
- Press save to save the new value 137
- Real time clock and timed functions 133 137
- Scroll to group 12 constant speeds and press sel 137
- Scroll to parameter 1201 constant speed sel and press edit 137
- Select parameters with the up down keys then press enter to go to the parameters mode 137
- The new value is displayed below the timer 1 src text press exit to return to the main menu 137
- The parameter example 1201 137
- Ach550 01 user s manual 138
- Real time clock and timed functions 138
- Select the created timer with the up down keys and press save 138
- The new value is displayed under const speed sel press exit to return to the main menu 138
- Timer 1 138
- Example of timer use 139
- A 0 hz 141
- Ach550 01 user s manual 141
- Di3 inv 141
- Parameters assistants changed par 141
- Press menu to go to the main menu 141
- Real time clock and timed functions 137 141
- Scroll to boost sel with the up down keys and press edit 141
- Scroll to boost time with the up down keys and press edit 141
- Scroll to group 36 timed functions with the up down keys and press sel 141
- Select a digital input as the source of the boost signal with the up down keys then press save 141
- Select parameters with the up down keys then press enter to go to the parameters mode 141
- To configure the boost follow these steps 141
- Ach550 01 user s manual 142
- Change the highlighted part of the time with the up down keys pressing next moves to the next part press save to save the time 142
- Real time clock and timed functions 142
- Scroll to timer 1 src and press edit 142
- Select boost with the up down keys and press save 142
- The new value is displayed under timer 1 src press exit to return to the main menu 142
- Serial communications 143
- What this chapter contains 143
- System overview 144
- Ach550 01 user s manual 146
- Before configuring the drive for fieldbus control the drive must be connected to the fieldbus according to the instructions given in this manual and manuals embedded fieldbus efb control 146
- Embedded fieldbus efb 146
- Serial communications 146
- Setting up communication through efb 146
- Terminated station terminated station station station 146
- To reduce noise on the network terminate the rs485 network using 120 ohm resistors at both ends of the network see the diagram below 146
- Use preferably three conductors and a shield for the connection 146
- A 0 hz 147
- Bacnet 147
- Parameters assistants changed par 147
- Setting up efb with the serial communication assistant 147
- Ach550 01 user s manual 148
- Changes made to efb communication parameters group 53 do not take effect until you perform one of the following cycle the drive power off and on or set parameter 5302 to 0 and then back to a unique efb station id 148
- Continue the guided set up with the assistant 148
- Efb communication parameters 148
- Protocol selection 148
- Serial communications 148
- Ach550 01 user s manual 149
- Serial communications 145 149
- Ach550 01 user s manual 150
- Bacnet specific communication parameters 150
- Serial communications 150
- Fieldbus adapter ext fba 151
- Mechanical and electrical installation of the plug in fieldbus 151
- A 0 hz 153
- Parameters assistants changed par 153
- Setting up communication through a plug in fieldbus adapter ext fba module 153
- Setting up fba with the serial communication assistant 153
- Ach550 01 user s manual 154
- Ext fba 154
- Fba communication parameters 154
- If the name of fba parameter is not self explanatory the assistant first tells you which information is expected from you 154
- Protocol selection 154
- Select ext fba with the up down keys and press save 154
- Serial communications 154
- The assistant recognises the type of the connected fieldbus adapter module and guides you through the necessary set up 154
- The new settings will take effect when the drive is next powered up or when parameter 5127 is activated 154
- Ach550 01 user s manual 155
- Serial communications 151 155
- Ach550 01 user s manual 156
- Serial communications 156
- Ach550 01 user s manual 157
- After the fieldbus communication has been set up the drive control parameters listed in the tables below should be checked and adjusted where necessary the setting for fieldbus control description column gives the value to use when the fieldbus interface is the desired source or destination for that particular signal as well as a description of the parameter for fieldbus signal routes and message composition see manuals embedded fieldbus efb control 3afe68320658 english and bacnet protocol 3aua0000004591 english 157
- Control command source selection 157
- Drive control parameters 157
- Serial communications 153 157
- Ach550 01 user s manual 158
- Reference signal source selection 158
- Serial communications 158
- Ach550 01 user s manual 159
- Digital output signal source selection 159
- Serial communications 155 159
- Ach550 01 user s manual 160
- Analogue output signal source selection 160
- Serial communications 160
- Ach550 01 user s manual 161
- Serial communications 157 161
- System control inputs 161
- Ach550 01 user s manual 162
- Serial communications 162
- Acceleration deceleration ramp pair selection 163
- Ach550 01 user s manual 163
- Communication fault functions 163
- Serial communications 159 163
- Ach550 01 user s manual 164
- Pid control feedback source selection 164
- Serial communications 164
- Ach550 01 user s manual 165
- Serial communications 161 165
- Fault handling 166
- Parameter groups 169
- Parameter listing and descriptions 169
- What this chapter contains 169
- Ach550 01 user s manual 172
- Group 99 start up data 172
- Parameter listing and descriptions 172
- This group defines special start up data required to set up the drive enter motor information 172
- Ach550 01 user s manual 173
- Parameter listing and descriptions 169 173
- Ach550 01 user s manual 174
- Parameter listing and descriptions 174
- Ach550 01 user s manual 175
- Parameter listing and descriptions 171 175
- Ach550 01 user s manual 176
- Group 01 operating data 176
- Parameter listing and descriptions 176
- This group contains drive operating data including actual signals the drive sets the values for actual signals based on measurements or calculations you cannot set these values 176
- Ach550 01 user s manual 177
- Parameter listing and descriptions 173 177
- Ach550 01 user s manual 178
- Parameter listing and descriptions 178
- Ach550 01 user s manual 179
- Parameter listing and descriptions 175 179
- Ach550 01 user s manual 180
- Parameter listing and descriptions 180
- Ach550 01 user s manual 181
- Parameter listing and descriptions 177 181
- Ach550 01 user s manual 182
- Group 03 fb actual signals 182
- Parameter listing and descriptions 182
- This group monitors fieldbus communications see also chapter serial communications 182
- Ach550 01 user s manual 183
- Parameter listing and descriptions 179 183
- Ach550 01 user s manual 184
- Parameter listing and descriptions 184
- Ach550 01 user s manual 185
- Parameter listing and descriptions 181 185
- Ach550 01 user s manual 186
- Group 04 fault history 186
- Parameter listing and descriptions 186
- This group stores a recent history of the faults reported by the drive 186
- Ach550 01 user s manual 187
- Parameter listing and descriptions 183 187
- Ach550 01 user s manual 188
- For commands that enable start stop and direction changes locks direction or enables direction control to select between the two external locations use parameter 1102 in the next group 188
- Group 10 start stop dir 188
- Parameter listing and descriptions 188
- This group defines external sources 188
- Ach550 01 user s manual 189
- Parameter listing and descriptions 185 189
- Ach550 01 user s manual 190
- Parameter listing and descriptions 190
- Ach550 01 user s manual 191
- Code description range 191
- Di ai ext1 191
- Frequency reference hz if 9904 3 191
- Group 11 reference select 191
- Hz rpm reference type depends on parameter 9904 191
- Keypad ref sel 1 ref 1 hz rpm 2 ref 2 selects the reference controlled in local control mode 1 191
- Parameter listing and descriptions 187 191
- Speed reference rpm if 9904 1 191
- This group defines how the drive selects between command sources characteristics and sources for 191
- Ach550 01 user s manual 192
- Parameter listing and descriptions 192
- Ach550 01 user s manual 193
- Parameter listing and descriptions 189 193
- Ach550 01 user s manual 194
- Parameter listing and descriptions 194
- Ach550 01 user s manual 195
- Parameter listing and descriptions 191 195
- Ach550 01 user s manual 196
- Parameter listing and descriptions 196
- Ach550 01 user s manual 197
- Parameter listing and descriptions 193 197
- Ach550 01 user s manual 198
- Acts also as a so called fault speed which may be activated if the control signal is lost refer to parameter 3001 198
- And 3018 198
- Group 12 constant speeds 198
- Note parameter 1208 198
- Parameter 3002 198
- Parameter listing and descriptions 198
- This group defines a set of constant speeds in general you can program up to 7 constant speeds ranging from 0 500 hz or 0 30000 rpm values must be positive no negative speed values for constant speeds constant speed selections are ignored if the process pid reference is followed or the drive is in local control mode or pfa pump and fan alternation is active 198
- Ach550 01 user s manual 199
- Parameter listing and descriptions 195 199
- Ach550 01 user s manual 200
- Parameter listing and descriptions 200
- Ach550 01 user s manual 201
- Parameter listing and descriptions 197 201
- Ach550 01 user s manual 202
- Parameter listing and descriptions 202
- Ach550 01 user s manual 203
- Group 13 analogue inputs 203
- Parameter listing and descriptions 199 203
- This group defines the limits and the filtering for analogue inputs 203
- Ach550 01 user s manual 204
- Parameter listing and descriptions 204
- Ach550 01 user s manual 205
- Group 14 relay outputs 205
- Parameter listing and descriptions 201 205
- This group defines the condition that activates each of the relay outputs 205
- Ach550 01 user s manual 206
- Parameter listing and descriptions 206
- Ach550 01 user s manual 207
- Parameter listing and descriptions 203 207
- Ach550 01 user s manual 208
- Parameter listing and descriptions 208
- Ach550 01 user s manual 209
- Parameter listing and descriptions 205 209
- Ach550 01 user s manual 210
- Group 15 analogue outputs 210
- Limited to programmable minimum and maximum values of output current scaled and or inverted by defining the minimum and maximum values of the source parameter or content defining a maximum value parameter 1503 or 1509 that is less than the content minimum value parameter 1502 or 1508 results in an inverted output filtered 210
- Parameter listing and descriptions 210
- This group defines the drive s analogue current signal outputs the drive s analogue outputs can be any parameter of group 01 operating data 210
- Ach550 01 user s manual 211
- Parameter listing and descriptions 207 211
- Ach550 01 user s manual 212
- Parameter listing and descriptions 212
- Ach550 01 user s manual 213
- Group 16 system controls 213
- Parameter listing and descriptions 209 213
- This group defines a variety of system level locks resets and enables 213
- Ach550 01 user s manual 214
- Parameter listing and descriptions 214
- Ach550 01 user s manual 215
- Parameter listing and descriptions 211 215
- Ach550 01 user s manual 216
- Parameter listing and descriptions 216
- Ach550 01 user s manual 217
- Parameter listing and descriptions 213 217
- Ach550 01 user s manual 218
- Code description range 218
- Parameter listing and descriptions 218
- Ach550 01 user s manual 219
- Parameter listing and descriptions 215 219
- Ach550 01 user s manual 220
- Parameter listing and descriptions 220
- Ach550 01 user s manual 221
- Group 17 override 221
- Parameter listing and descriptions 217 221
- The following faults are ignored 221
- This group defines the source for the override activation signal the override speed frequency and pass code and how the override is enabled and disabled the override feature can be used e g in fire situations when the override di is activated the drive stops and then accelerates to the preset speed or frequency when the di is deactivated the drive stops and reboots if the start command run enable and start enable are active in the auto mode the drive starts automatically and continues normally after override mode in the hand mode the drive returns to the off mode when override is active drive runs at preset speed drive ignores all keypad commands drive ignores all commands from communication links drive ignores all digital inputs except override activation deactivation run enable and start enable drive displays alarm message 2020 221
- Changing the override parameters 222
- Commissioning the override mode 222
- Ach550 01 user s manual 223
- Parameter listing and descriptions 219 223
- Ach550 01 user s manual 224
- Parameter listing and descriptions 224
- Ach550 01 user s manual 225
- Group 20 limits 225
- Parameter listing and descriptions 221 225
- This group defines minimum and maximum limits to be followed in driving the motor speed frequency current torque etc 225
- Ach550 01 user s manual 226
- Parameter listing and descriptions 226
- Ach550 01 user s manual 227
- Parameter listing and descriptions 223 227
- Ach550 01 user s manual 228
- Parameter listing and descriptions 228
- Ach550 01 user s manual 229
- Group 21 start stop 229
- Parameter listing and descriptions 225 229
- This group defines how the motor starts and stops the ach550 supports several start and stop modes 229
- Ach550 01 user s manual 230
- Parameter listing and descriptions 230
- Ach550 01 user s manual 231
- Parameter listing and descriptions 227 231
- Ach550 01 user s manual 232
- Group 22 accel decel 232
- Parameter listing and descriptions 232
- This group defines ramps that control the rate of acceleration and deceleration you define these ramps as a pair one for acceleration and one for deceleration you can define two pairs of ramps and use a digital input to select one of these 232
- Ach550 01 user s manual 233
- Parameter listing and descriptions 229 233
- Ach550 01 user s manual 234
- Parameter listing and descriptions 234
- Ach550 01 user s manual 235
- Group 23 speed control 235
- Parameter listing and descriptions 231 235
- This group defines variables used for speed control operation 235
- Ach550 01 user s manual 236
- Parameter listing and descriptions 236
- Ach550 01 user s manual 237
- Parameter listing and descriptions 233 237
- Ach550 01 user s manual 238
- Parameter listing and descriptions 238
- Ach550 01 user s manual 239
- Parameter listing and descriptions 235 239
- Ach550 01 user s manual 240
- Group 25 critical speeds 240
- Parameter listing and descriptions 240
- This group defines up to three critical speeds or ranges of speeds that are to be avoided due for example to mechanical resonance problems at certain speeds 240
- Ach550 01 user s manual 241
- Parameter listing and descriptions 237 241
- Ach550 01 user s manual 242
- Group 26 motor control 242
- Parameter listing and descriptions 242
- This group defines variables used for motor control 242
- Ach550 01 user s manual 243
- Parameter listing and descriptions 239 243
- Ach550 01 user s manual 244
- Parameter listing and descriptions 244
- Ach550 01 user s manual 245
- Parameter listing and descriptions 241 245
- Ach550 01 user s manual 246
- Group 29 maintenance trig 246
- Parameter listing and descriptions 246
- This group defines usage levels and trigger points when usage reaches the set trigger point a notice displayed on the control panel operator keypad signals that maintenance is due 246
- Ach550 01 user s manual 247
- Parameter listing and descriptions 243 247
- Ach550 01 user s manual 248
- Group 30 fault functions 248
- Parameter listing and descriptions 248
- This group defines situations that the drive should recognise as potential faults and how the drive should respond if the fault is detected 248
- Ach550 01 user s manual 249
- Parameter listing and descriptions 245 249
- Ach550 01 user s manual 250
- Parameter listing and descriptions 250
- Ach550 01 user s manual 251
- Parameter listing and descriptions 247 251
- Ach550 01 user s manual 252
- Parameter listing and descriptions 252
- Ach550 01 user s manual 253
- Parameter listing and descriptions 249 253
- Ach550 01 user s manual 254
- Parameter listing and descriptions 254
- Ach550 01 user s manual 255
- Group 31 automatic reset 255
- Parameter listing and descriptions 251 255
- This group defines conditions for automatic resets an automatic reset occurs after a particular fault is detected the drive holds for a set delay time and then restarts automatically you can limit the number of resets in a specified time period and you can set up automatic resets for a variety of faults 255
- Ach550 01 user s manual 256
- Parameter listing and descriptions 256
- Ach550 01 user s manual 257
- Group 32 supervision 257
- Parameter listing and descriptions 253 257
- This group defines supervision for up to three signals from group 01 operating data supervision monitors a specified parameter and energises a relay output if the parameter passes a defined limit use group 14 relay outputs to define the relay and whether the relay activates when the signal is too low or too high 257
- Ach550 01 user s manual 258
- Parameter listing and descriptions 258
- Ach550 01 user s manual 259
- Parameter listing and descriptions 255 259
- Ach550 01 user s manual 260
- Group 33 information 260
- Parameter listing and descriptions 260
- This group provides access to information about the drive s current programs versions and test date 260
- A 0 hz 261
- A 0 hz 3 261
- Ach550 01 user s manual 261
- Group 34 panel display 261
- Parameter listing and descriptions 257 261
- This group defines the content for control panel operator keypad display centre area when the control panel is in the output mode 261
- Ach550 01 user s manual 262
- Parameter listing and descriptions 262
- Ach550 01 user s manual 263
- Code description range 263
- Dsp for 263
- Output1 max sets the maximum value displayed for the first display parameter note parameter is not effective if parameter 3404 263
- Output1 min sets the maximum value displayed for the first display parameter note parameter is not effective if parameter 3404 263
- Output1 unit 0 127 selects the units used for the first display parameter note parameter is not effective if parameter 3404 263
- Output2 dsp form 0 9 defines the decimal point location for the second display parameter see parameter 3404 263
- Output2 unit 0 127 selects the units used for the second display parameter see parameter 3405 263
- Parameter listing and descriptions 259 263
- Signal2 max defines the maximum expected value for the second display parameter see parameter 3403 263
- Signal2 min defines the minimum expected value for the second display parameter see parameter 3402 263
- Signal2 param 100 178 selects the second parameter by number displayed on the control panel see parameter 3401 263
- Ach550 01 user s manual 264
- Parameter listing and descriptions 264
- Group 35 motor temp meas 265
- Ach550 01 user s manual 267
- Parameter listing and descriptions 263 267
- Ach550 01 user s manual 268
- Parameter listing and descriptions 268
- Ach550 01 user s manual 269
- Group 36 timed functions 269
- Parameter listing and descriptions 265 269
- This group defines the timed functions the timed functions include four daily starts stops four weekly starts stops overrides four timers for collecting selected periods together a timer can be connected to multiple time periods and a time period can be in multiple timers 269
- Ach550 01 user s manual 270
- Parameter listing and descriptions 270
- Ach550 01 user s manual 271
- Parameter listing and descriptions 267 271
- Ach550 01 user s manual 272
- Parameter listing and descriptions 272
- Ach550 01 user s manual 273
- Parameter listing and descriptions 269 273
- Ach550 01 user s manual 274
- Group 37 user load curve 274
- Parameter listing and descriptions 274
- This group defines supervision of user adjustable load curves motor torque as a function of frequency the curve is defined by five points 274
- Ach550 01 user s manual 275
- Defines the torque value of the second underload curve definition point 275
- Parameter listing and descriptions 271 275
- Ach550 01 user s manual 276
- Correspondence with the obsolete underload supervision 276
- Nominal frequency of the motor if you want to emulate the behaviour of an old underload curve with parameters as in the shaded columns set the new parameters as in the white columns in the tables 276
- Nominal torque of the motor 276
- Obsolete the underload protection is activated curves 1 3 reach maximum at the motor rated frequency set by parameter 9907 276
- Parameter listing and descriptions 276
- Provided five selectable curves shown in the figure below 276
- The now obsolete parameter 3015 276
- The parameter characteristics were as described below if the load drops below the set curve for longer than the time set by parameter 3014 276
- Ach550 01 user s manual 277
- Eu 50 hz 277
- Parameter listing and descriptions 273 277
- Us 60 hz 277
- Overview of pid controllers 278
- Pid controller basic set up 278
- Ach550 01 user s manual 279
- Must be set to value 19 279
- Note in order to activate and use the pid controller parameter 1106 279
- Parameter listing and descriptions 275 279
- Pid controller advanced 280
- Ach550 01 user s manual 281
- Group 40 process pid set 1 281
- Parameter listing and descriptions 277 281
- This group defines a set of parameters used with the process pid pid1 controller typically only parameters in this group are needed 281
- Ach550 01 user s manual 282
- Parameter listing and descriptions 282
- Ach550 01 user s manual 283
- Parameter listing and descriptions 279 283
- Ach550 01 user s manual 284
- Parameter listing and descriptions 284
- Ach550 01 user s manual 285
- Parameter listing and descriptions 281 285
- Ach550 01 user s manual 286
- Parameter listing and descriptions 286
- Ach550 01 user s manual 287
- Parameter listing and descriptions 283 287
- Ach550 01 user s manual 288
- Parameter listing and descriptions 288
- Ach550 01 user s manual 289
- Parameter listing and descriptions 285 289
- Ach550 01 user s manual 290
- Parameter listing and descriptions 290
- Ach550 01 user s manual 291
- Parameter listing and descriptions 287 291
- Ach550 01 user s manual 292
- Parameter listing and descriptions 292
- Ach550 01 user s manual 293
- Parameter listing and descriptions 289 293
- Group 41 process pid set 2 294
- Ach550 01 user s manual 295
- Group 42 ext trim pid 295
- Parameter listing and descriptions 291 295
- This group defines the parameters used for the external pid controller pid2 of the ach550 the operation of parameters 4201 4221 is analogous with process pid controller pid1 set 1 parameters 4001 4021 295
- Ach550 01 user s manual 296
- Parameter listing and descriptions 296
- Ach550 01 user s manual 297
- And 0178 297
- Are derived from subtracting the drive s energy consumed from the direct on line dol consumption calculated on the basis of parameter 4508 297
- As such the accuracy of the values is dependent on the accuracy of the power estimate entered in that parameter 297
- Group 45 energy saving 297
- Parameter listing and descriptions 293 297
- This group defines the setup of calculation and optimization of energy savings note the values of the saved energy parameters 0174 297
- Ach550 01 user s manual 298
- Group 51 ext comm module 298
- Parameter listing and descriptions 298
- This group defines set up variables for an external fieldbus communication module refer to the communication module documentation for more information on these parameters 298
- Ach550 01 user s manual 299
- Parameter listing and descriptions 295 299
- Ach550 01 user s manual 300
- Group 52 panel comm 300
- Parameter listing and descriptions 300
- This group defines the communication settings for the control panel port on the drive normally when using the supplied control panel operator keypad there is no need to change settings in this group in this group parameter modifications take effect on the next power up 300
- Ach550 01 user s manual 301
- Parameter listing and descriptions 297 301
- Ach550 01 user s manual 302
- Group 53 efb protocol 302
- Parameter listing and descriptions 302
- This group defines set up variables used for an embedded fieldbus efb communication protocol refer to the communication protocol documentation for more information on these parameters 302
- Ach550 01 user s manual 303
- Parameter listing and descriptions 299 303
- Ach550 01 user s manual 304
- Parameter listing and descriptions 304
- Ach550 01 user s manual 305
- Group 64 load analyzer 305
- Is shown in ten classes 2 peak value logger one signal in group 1 can be logged for the peak maximum value the peak value of the signal peak time time when the peak value was detected as well the frequency current and dc voltage at the peak time are shown 3 amplitude logger 2 one signal in group 1 can be logged for amplitude distribution the base value 100 value can be set by the user the first logger cannot be reset the other two loggers can be reset by a user defined method they are also reset if either of the signals or the peak value filter time is changed 305
- Parameter listing and descriptions 301 305
- This group defines the load analyzer which can be used for analyzing the customer s process and sizing the drive and the motor the peak value is logged at 2 ms level and the distribution loggers are updated on 0 s 200 ms time level three different values can be logged 1 amplitude logger 1 the measured current is logged continuously the distribution as a percentage of the nominal current 305
- Ach550 01 user s manual 306
- Parameter listing and descriptions 306
- Ach550 01 user s manual 307
- Parameter listing and descriptions 303 307
- Ach550 01 user s manual 308
- Parameter listing and descriptions 308
- Group 81 pfa control 309
- Ach550 01 user s manual 310
- Parameter listing and descriptions 310
- Ach550 01 user s manual 311
- Parameter listing and descriptions 307 311
- Ach550 01 user s manual 312
- Parameter listing and descriptions 312
- Ach550 01 user s manual 313
- Parameter listing and descriptions 309 313
- Ach550 01 user s manual 314
- Parameter listing and descriptions 314
- Ach550 01 user s manual 315
- Parameter listing and descriptions 311 315
- Ach550 01 user s manual 316
- Parameter listing and descriptions 316
- Ach550 01 user s manual 317
- Parameter listing and descriptions 313 317
- Ach550 01 user s manual 318
- Parameter listing and descriptions 318
- Ach550 01 user s manual 319
- Parameter listing and descriptions 315 319
- Ach550 01 user s manual 320
- Parameter listing and descriptions 320
- Ach550 01 user s manual 321
- Parameter listing and descriptions 317 321
- Ach550 01 user s manual 322
- Parameter listing and descriptions 322
- Ach550 01 user s manual 323
- Parameter listing and descriptions 319 323
- Ach550 01 user s manual 324
- Parameter listing and descriptions 324
- Ach550 01 user s manual 325
- Parameter listing and descriptions 321 325
- Ach550 01 user s manual 326
- Parameter listing and descriptions 326
- Ach550 01 user s manual 327
- Parameter listing and descriptions 323 327
- Ach550 01 user s manual 328
- Parameter listing and descriptions 328
- Ach550 01 user s manual 329
- Parameter listing and descriptions 325 329
- Ach550 01 user s manual 330
- Parameter listing and descriptions 330
- Ach550 01 user s manual 331
- Group 98 options 331
- Parameter listing and descriptions 327 331
- This group configures for options in particular enabling serial communication with the drive 331
- Ach550 01 user s manual 332
- Complete parameter list 332
- Parameter listing and descriptions 332
- The following table lists all parameters and their default values for all application macros the user can enter desired parameter values under the user column 332
- Ach550 01 user s manual 333
- Parameter listing and descriptions 329 333
- Ach550 01 user s manual 334
- Parameter listing and descriptions 334
- Ach550 01 user s manual 335
- Parameter listing and descriptions 331 335
- Ach550 01 user s manual 336
- Parameter listing and descriptions 336
- Ach550 01 user s manual 337
- Parameter listing and descriptions 333 337
- Ach550 01 user s manual 338
- Parameter listing and descriptions 338
- Ach550 01 user s manual 339
- Parameter listing and descriptions 335 339
- Ach550 01 user s manual 340
- Parameter listing and descriptions 340
- Ach550 01 user s manual 341
- Parameter listing and descriptions 337 341
- Ach550 01 user s manual 342
- Parameter listing and descriptions 342
- Ach550 01 user s manual 343
- Parameter listing and descriptions 339 343
- Ach550 01 user s manual 344
- Parameter listing and descriptions 344
- Ach550 01 user s manual 345
- Parameter listing and descriptions 341 345
- Ach550 01 user s manual 346
- Parameter listing and descriptions 346
- Ach550 01 user s manual 347
- Parameter listing and descriptions 343 347
- Ach550 01 user s manual 348
- Parameter listing and descriptions 348
- Ach550 01 user s manual 349
- Parameter listing and descriptions 345 349
- Ach550 01 user s manual 350
- Parameter listing and descriptions 350
- Ach550 01 user s manual 351
- Parameter listing and descriptions 347 351
- Ach550 01 user s manual 352
- Parameter listing and descriptions 352
- Ach550 01 user s manual 353
- Parameter listing and descriptions 349 353
- Ach550 01 user s manual 354
- Parameter listing and descriptions 354
- Ach550 01 user s manual 355
- Parameter listing and descriptions 351 355
- Ach550 01 user s manual 356
- Parameter listing and descriptions 356
- Ach550 01 user s manual 357
- Parameter listing and descriptions 353 357
- Ach550 01 user s manual 358
- Parameter listing and descriptions 358
- Ach550 01 user s manual 359
- Parameter listing and descriptions 355 359
- Ach550 01 user s manual 360
- Parameter listing and descriptions 360
- Ach550 01 user s manual 361
- Parameter listing and descriptions 357 361
- Ach550 01 user s manual 362
- Parameter listing and descriptions 362
- Ach550 01 user s manual 363
- Parameter listing and descriptions 359 363
- Ach550 01 user s manual 364
- Parameter listing and descriptions 364
- Ach550 01 user s manual 365
- Parameter listing and descriptions 361 365
- Ach550 01 user s manual 366
- Parameter listing and descriptions 366
- Ach550 01 user s manual 367
- Parameter listing and descriptions 363 367
- Ach550 01 user s manual 368
- Parameter listing and descriptions 368
- Ach550 01 user s manual 369
- Parameter listing and descriptions 365 369
- Ach550 01 user s manual 370
- Parameter listing and descriptions 370
- Ach550 01 user s manual 371
- Parameter listing and descriptions 367 371
- Diagnostics and maintenance 373
- What this chapter contains 373
- Diagnostics displays 374
- Red faults 374
- Correcting faults 375
- Fault listing 375
- Flashing green alarms 375
- May be shorter 375
- The following table lists the faults by code number and describes each the fault name is the long form shown on the control panel display when the fault occurs the fault names shown in the fault logger mode see page 92 and the fault names for parameter 0401 375
- Fault resetting 384
- Flashing red led 384
- Red led 384
- Alarm listing 385
- Correcting alarms 385
- History 385
- Ach550 01 user s manual 386
- Diagnostics and maintenance 386
- Ach550 01 user s manual 387
- Diagnostics and maintenance 383 387
- Ach550 01 user s manual 388
- Diagnostics and maintenance 388
- Ach550 01 user s manual 389
- Diagnostics and maintenance 385 389
- Maintenance intervals 390
- Heatsink 391
- Main fan replacement 391
- Main fan replacement frame sizes r1 r4 392
- Main fan replacement frame size r5 393
- Main fan replacement frame size r6 394
- Frame sizes r1 r4 395
- Frame sizes r5 and r6 395
- Internal enclosure fan replacement 395
- Capacitors 396
- Reforming 396
- Replacement 396
- Battery 397
- Cleaning 397
- Control panel 397
- Ratings 399
- Technical data 399
- What this chapter contains 399
- Iec ratings 380 480 v drives 400
- Iec ratings 208 240 v drives 401
- Sizing 402
- Symbols 402
- V drives 403
- Altitude derating 404
- Single phase supply derating 404
- Switching frequency derating 404
- V drives 404
- Input power mains cable fuses and circuit breakers 405
- Line current harmonics 405
- Ach550 01 user s manual 406
- Fuses 380 480 v drives 406
- Technical data 406
- Ach550 01 user s manual 407
- Fuses 208 240 v drives 407
- Note the use of ultra rapid fuses is recommended but normal hrc fuses abb tmax moulded case circuit breakers mccb or abb s200 b c miniature circuit breakers mcb are sufficient see section circuit breakers on page 404 407
- Technical data 403 407
- Abb s200 b c miniature circuit breakers mcb and manual motor starters 408
- Ach550 01 user s manual 408
- Circuit breakers 408
- Technical data 408
- The tables below list abb circuit breakers that can be used instead of fuses recommended depending on the type designation tmax moulded case circuit breakers mccb or s200 b c miniature circuit breakers mcb manual motor starters or both are given 408
- Abb tmax moulded case circuit breakers mccb 409
- Ach550 01 user s manual 409
- Technical data 405 409
- Ach550 01 user s manual 410
- Dimension the cables according to local safety regulations appropriate input voltage and the load current of the drive note the cable must be less than the maximum limit defined by the terminal size check the maximum wire size according to the table in section input power and motor connection terminals on page 408 the following table gives copper and aluminium cable types for different load currents these recommendations apply only for the conditions listed at the top of the table 410
- Input power mains cable 410
- Technical data 410
- Ach550 01 user s manual 411
- Technical data 407 411
- Ach550 01 user s manual 412
- Input power and motor connection terminals 412
- Input power mains and motor cable minimum and maximum sizes per phase as well as grounding pe cable maximum sizes accepted at the cable terminals and the tightening torques are listed in the following table note see the recommended cable sizes for different load currents in section input power mains cable on page 406 412
- Technical data 412
- Input power mains connection 413
- Motor connection 414
- Ach550 01 user s manual 415
- Motor cable length 415
- Technical data 411 415
- The tables below show the maximum motor cable lengths for 400 v drives with different switching frequencies examples for using the table are also given 415
- Under heading operational limits the basic unit columns define the cable lengths with which the basic drive unit works without problems within the drive specification without installing 415
- Examples for using the table 416
- Group 35 motor temp meas 417
- Motor thermal protection 417
- Control connections 418
- Ach550 01 user s manual 419
- Hardware description 419
- Technical data 415 419
- Ach550 01 user s manual 420
- Note for safety reasons the fault relay signals a fault when the ach550 is powered down 420
- Note terminals 3 6 and 9 are at the same potential 420
- Technical data 420
- Ach550 01 user s manual 421
- For using an external power supply see the diagrams below 421
- Technical data 417 421
- The terminals on the control board as well as on the optional modules attachable to the board fulfil the protective extra low voltage pelv requirements stated in en 50178 provided that the external circuits connected to the terminals also fulfil the requirements and the installation site is below 2000 m 6562 ft you can wire the digital input terminals in either a pnp or npn configuration 421
- Communications 422
- Efficiency 422
- Losses cooling data and noise 422
- Ach550 01 user s manual 423
- Air flow 380 480 v drives 423
- Technical data 419 423
- The following table lists the requirements for the cooling air flow data for 380 480 v drives at full load in all ambient conditions listed in ambient conditions on page 440 423
- Ach550 01 user s manual 424
- Air flow 208 240 v drives 424
- Dimensions and weights 424
- Technical data 424
- The dimensions and mass for the ach550 depend on the frame size and enclosure type if unsure of frame size find first the type designation on the drive labels then look up this type designation in section ratings on page 395 to determine the frame size pages 426 438 show the dimensional drawings of the different frame sizes for each degree of protection a complete set of dimensional drawings for ach550 drives can be found on the hvac info guide 3afe68338743 english 424
- The following table lists the requirements for the cooling air flow data for 208 240 v drives at full load in all ambient conditions listed in ambient conditions on page 440 424
- Ach550 01 user s manual 425
- Mounting dimensions 425
- Technical data 421 425
- Weights and mounting screws 426
- Control panel operator keypad dimensions and mounting 427
- Ip54 panel mounting kit 427
- Ip66 panel extension cable kit 428
- Opmp 01 cabinet panel mounting kit 429
- Frame size r1 ip54 ul type 12 430
- Frame size r2 ip54 ul type 12 431
- Frame size r3 ip54 ul type 12 432
- Frame size r4 ip54 ul type 12 433
- Frame size r5 ip54 ul type 12 434
- Frame size r6 ip54 ul type 12 435
- Frame size r1 ip21 ul type 1 437
- Frame size r2 ip21 ul type 1 438
- Frame size r3 ip21 ul type 1 439
- Frame size r4 ip21 ul type 1 440
- Frame size r5 ip21 ul type 1 441
- Frame size r6 ip21 ul type 1 442
- Ach550 01 user s manual 444
- Ambient conditions 444
- Technical data 444
- The following table lists the ach550 environmental requirements 444
- Materials 445
- Applicable standards 446
- Ce marking 446
- Markings 446
- C tick marking 447
- Compliance with iec en 61800 3 2004 447
- Compliance with iec en 61800 3 2004 a1 2012 447
- Compliance with the european emc directive 447
- Compliance with the european low voltage directive 447
- Ul marking 447
- Eac marking 448
- Iec en 61800 3 2004 definitions 448
- Compliance with the iec en 61800 3 2004 a1 2012 449
- First environment drives of category c2 449
- Second environment drives of category c3 449
- Document library on the internet 475
- Further information 475
- Product and service inquiries 475
- Product training 475
- Providing feedback on abb drives manuals 475
- Contact us 476
Похожие устройства
- ABB ACH550-01-06A9-4+B055 Управление встроенной полевой шиной
- Corsair iCUE 465X RGB Black (CC-9011188-WW) Инструкция по эксплуатации
- ABB ACH550-01-06A9-4 BACnet протокол
- ABB ACH550-01-06A9-4 Дополнение по установке
- ABB ACH550-01-06A9-4 Руководство пользователя
- ABB ACH550-01-06A9-4 Управление встроенной полевой шиной
- ABB ACH550-02-602A-4 BACnet протокол
- ABB ACH550-02-602A-4 Руководство пользователя
- ABB ACH550-02-602A-4 Управление встроенной полевой шиной
- ABB ACH550-02-645A-4 BACnet протокол
- ABB ACH550-02-645A-4 Руководство пользователя
- ABB ACH550-02-645A-4 Управление встроенной полевой шиной
- Corsair iCUE 220T RGB Airflow White (CC-9011174-WW) Инструкция по эксплуатации
- Corsair Obsidian Series 750D (CC-9011078-WW) Инструкция по эксплуатации
- Corsair Carbide Series 678C Black (CC-9011167-WW) Инструкция по эксплуатации
- Corsair Carbide Series 678C White (CC-9011170-WW) Инструкция по эксплуатации
- Corsair Carbide Series SPEC-DELTA RGB (CC-9011166-WW) Инструкция по эксплуатации
- Corsair Carbide Series 275Q (CC-9011164-WW) Инструкция по эксплуатации
- Corsair Carbide Series SPEC‐06 White (CC-9011145-WW) Инструкция по эксплуатации
- Corsair Carbide Series SPEC‐06 Black (CC-9011144-WW) Инструкция по эксплуатации