Danfoss VLT Refrigeration Drive FC-103P75KT4 [106/138] General specifications and troubleshooting

Danfoss VLT Refrigeration Drive FC-103P75KT4 [106/138] General specifications and troubleshooting
8 General Specifications and Troubleshooting
8.1 General Specifications
Mains supply 200-240 V AC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P3K7
3.7
IP20/Chassis
(A2+A3 may be converted to IP21 using a conversion kit. (See
also Mechanical mounting and IP21/Type 1 Enclosure kit in the
Design Guide.))
A2 A2 A2 A3 A3
IP55/Type 12 A4/A5 A4/A5 A4/A5 A5 A5
IP66/NEMA 4X A4/A5 A4/A5 A4/A5 A5 A5
Typical Shaft Output [HP] at 208 V 1.5 2.0 2.9 4.0 4.9
Output current
Continuous
(3x200-240 V) [A]
6.6 7.5 10.6 12.5 16.7
Intermittent
(3x200-240 V) [A]
7.3 8.3 11.7 13.8 18.4
Continuous
kVA (208 V AC) [kVA]
2.38 2.70 3.82 4.50 6.00
Max. input current
Continuous
(3x200-240 V) [A]
5.9 6.8 9.5 11.3 15.0
Intermittent
(3x200-240 V) [A]
6.5 7.5 10.5 12.4 16.5
Additional specifications
Estimated power loss
at rated max. load [W]
4)
63 82 116 155 185
IP20, IP21 max. cable cross
section (mains, motor, brake and
load sharing) [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
IP55, IP66 max. cable cross
section (mains, motor, brake and
load sharing) [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
Max. cable cross section with
disconnect
6, 4, 4 (10, 12, 12)
Weight enclosure IP20 [kg] 4.9 4.9 4.9 6.6 6.6
Weight enclosure IP21 [kg] 5.5 5.5 5.5 7.5 7.5
Weight enclosure IP55 [kg]
(A4/A5)
9.7/13.5 9.7/13.5 9.7/13.5 13.5 13.5
Weight enclosure IP66 [kg]
(A4/A5)
9.7/13.5 9.7/13.5 9.7/13.5 13.5 13.5
Efficiency
3)
0.96 0.96 0.96 0.96 0.96
Table 8.1 Mains Supply 200-240 V AC
General Specifications and ...