4.1 Pre-start
CAUTION
Before applying power to the unit, inspect the entire
installation as detailed in Table 4.1. Check mark those items
when completed.
Inspect for Description
Auxiliary equipment
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that may
reside on the input power side of the frequency converter or output side to the motor. Ensure
that they are ready for full speed operation.
Check function and installation of any sensors used for feedback to the frequency converter.
Remove power factor correction caps on motor(s), if present.
Cable routing
Ensure that input power, motor wiring , and control wiring are separated or in three separate
metallic conduits for high frequency noise isolation.
Control wiring
Check for broken or damaged wires and loose connections.
Check that control wiring is isolated from power and motor wiring for noise immunity.
Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated
correctly.
Cooling clearance
Measure that top and bottom clearance is adequate to ensure proper air flow for cooling.
EMC considerations
Check for proper installation regarding electromagnetic compatibility.
Environmental consider-
ations
See equipment label for the maximum ambient operating temperature limits.
Humidity levels must be 5-95% non-condensing.
Fusing and circuit
breakers
Check for proper fusing or circuit breakers.
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers
are in the open position.
Earthing (Grounding)
The unit requires an earth wire(ground wire) from its chassis to the building earth (ground).
Check for good earth connections(ground connections) that are tight and free of oxidation.
Earthing (grounding) to conduit or mounting the back panel to a metal surface is not a
suitable earth (ground).
Input and output power
wiring
Check for loose connections.
Check that motor and mains are in separate conduit or separated screened cables.
Panel interior
Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Vibration
Check that the unit is mounted solidly or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
Table 4.1 Start Up Check List
Start Up and Functional Tes... VLT® Refrigeration Drive 110-250 kW Operating Instructions
MG16F102 - VLT® is a registered Danfoss trademark 21