Danfoss MCD 201-045-T6-xxx [18/24] N motor thermistor protection

Danfoss MCD 201-037-T6-xxx [18/24] N motor thermistor protection
MCD 200 Design Guide
Description of choice:
FWD ANY
MCD
MCD
L1
L2
L3
L1
L2
L3
177HA239.10
The MCD 202 itself is phase rotation insensitive.
This function allows motor rotation to be limited to
one direction o nly. Set the protection according
to application requirements.
8 Auxiliary Relay Function (Terminals 23, 24)
Value:
Trip, Run
Trip
Function:
Sets the functionality of the Auxiliary Relay
(Terminals 23,24).
Description of choice:
Set as required, using the combined Phase
Rotation/Aux Relay adjustment.
177HA240.11
U
e
RUN
Main
Contactor
Motor Thermistor Protection
05
06
05
06
Or
177HA279.10
Motor thermistor cut out value = 2.8 k .
Indication
1L13L25L3
2T14T26T3
Ready
Run
177HA260.10
LED OFF ON FLASH
Ready No control
power
Ready Starter
tripped
Run Motor not
running
Motor
running at
full speed
Motor
starting or
stopping
Fault Finding
Ready LED Description
x1
Power Circuit Fau lt:
Check mains supply L1, L2 & L3,
motor circuit T1, T2 & T3 and soft
starter SCRs.
x2
Excess Start Time:
Check load, increase start current
or adjust Excess Start Time setting.
x3
Motor Overload:
Allow motor to cool, reset soft
starter and restart. (MCD 202
cannot be reset until motor has
cooled adequately).
x4
Motor Thermistor:
Check motor ventilation and
thermistor connection 05 & 06.
Allow motor to cool.
x5
Phase Im b ala nce:
Check line current L1, L2 & L3.
x6
Supply Frequency:
Check supply frequency is in range
x7
Phase Rotation:
Check for correct phase rotation.
x8
Network Comms F ailure (betwe en
accessory module and network):
Check network connections and
settings.
x9
Starter Comms Failure (between
starter and accessory m o dule):
Remove and refit accesso ry
module.
MG.17.C2.02 - VLT is a registered Danfoss trademark
18