Danfoss MCD 202-007-T4-xxx [11/24] Mcd 200 design guide

Danfoss MCD 201-075-T6-xxx [11/24] Mcd 200 design guide
MCD 200 Design Guide
MCD 200 Series
Overview
the actual time the MCD 202 "current limits". The
ramp-up time will be reduced and is determine d by
the motor speed on reapplication of the start signal.
What is the remote start and stop
input impedance?
Are any special precautions necessary
during installation?
The 01/02 input impedance is approximately 400
k
@ 300 VAC and 5.6 k @24VAC/VDC.All
control wiring, for long runs, should be either twisted
pair or shielded cable with the screen earthed at
one en d. Control wiring should be separated from
power cables by a minimum distance of 300 mm.
If long ca ble runs cannot be avoided, the
best a ssurance against noise interference is
to install an interposing relay in close proximity
to the M CD 200 soft starter.
Why is it necessary to apply control voltage
before (or with) mains voltage?
There is a possibility the soft starter could arrive
at site with the internal bypass relays in "closed"
state. On first application of control voltage, the
bypass relays are commanded to open. If mains
voltage is applied w ithout control voltage, this step
is missed, and the motor may start DOL without
war ning (see Product Note for more detail) .
What are the under- & over-frequency trip
points for MCD 200 soft starters?
The trip points are 40 Hz and 72 Hz. If the
frequency falls below 40 Hz o r rises above 72 Hz,
the soft starter will trip (x 6 Ready LED flashes).
These trip points are not adjustable.
A supply frequency trip will also occur if all
three phases from the mains supply are lost,
or fall below approximately 120 VAC while
the soft starter is running.
A supply frequency trip will occur if the line
contactor drops out during running.
Will the motor start DOL if the start ramp
of MCD 201 open loop soft starter is
set to "full voltage"?
No, the MCD 201 wi ll still provide a limited soft
start. The voltage is ramped up from 0 to 100%
in approximately 0.25 seconds.