Vacon NXS0018-6A2L0SSS [4/12] Ratings and dimensions
![Vacon NXS0004-6A2L0SSS [4/12] Ratings and dimensions](/views2/1563540/page4/bg4.png)
Function Availability
IP21 Standard
IP54 (FR10 only) Optional (H: +20mm)
Integrated fuses Standard
Integrated load switch Optional
EMC ltering L Standard
EMC ltering T Optional
Integrated brake chopper (cabling top entry) Optional (H: +122 mm)
Ratings and dimensions
Mains voltage 500-690 V, 50/60 Hz, 3~, Wall-mounted units
Mains voltage 500-690 V, 50/60 Hz, 3~, Standalone units
Hardware configurations, Standalone units
AC drive type
Loadability Motor shaft power
Enclosure
Dimensions
W x H x D [mm]
Low (+40°C) High (+50°C)
Maximum
current I
S
400 V supply
Rated
continuous
current I
L
[A]
10%
overload
current [A]
Rated
continuous
current I
H
[A]
50%
overload
current [A]
10% overl.
P [kW]
50% overl.
P [kW]
NXS 0004 6 A 2 L 0 SSS 4.5 5.0 3.2 4.8 6.4 3 2.2 FR6 195 x 519 x 237
NXS 0005 6 A 2 L 0SSS 5.5 6.1 4.5 6.8 9.0 4 3 FR6 195 x 519 x 237
NXS 0007 6 A 2 L 0 SSS 7.5 8.3 5.5 8.3 11.0 5.5 4 FR6 195 x 519 x 237
NXS 0010 6 A 2 L 0 SSS 10 11.0 7.5 11.3 15.0 7.5 5.5 FR6 195 x 519 x 237
NXS 0013 6 A 2 L 0 SSS 13.5 14.9 10 15.0 20.0 11 7.5 FR6 195 x 519 x 237
NXS 0018 6 A 2 L 0 SSS 18 19.8 13.5 20.3 27 15 11 FR6 195 x 519 x 237
NXS 0022 6 A 2 L 0 SSS 22 24.2 18 27.0 36 18.5 15 FR6 195 x 519 x 237
NXS 0027 6 A 2 L 0 SSS 27 29.7 22 33.0 44 22 18.5 FR6 195 x 519 x 237
NXS 0034 6 A 2 L 0 SSS 34 37 27 41 54 30 22 FR6 195 x 519 x 237
NXS 0041 6 A 2 L 0 SSS 41 45 34 51 68 37.5 30 FR7 237 x 591 x 257
NXS 0052 6 A 2 L 0 SSS 52 57 41 62 82 45 37.5 FR7 237 x 591 x 257
NXS 0062 6 A 2 L 0 SSS 62 68 52 78 104 55 45 FR8 291 x 758 x 344
NXS 0080 6 A 2 L 0 SSS 80 88 62 93 124 75 55 FR8 291 x 758 x 344
NXS 0100 6 A 2 L 0 SSS 100 110 80 120 160 90 75 FR8 291 x 758 x 344
NXS 0125 6 A 2 L 0 SSF 125 138 100 150 200 110 90 FR9 480 x 1150 x 362
NXS 0144 6 A 2 L 0 SSF 144 158 125 188 213 132 110 FR9 480 x 1150 x 362
NXS 0170 6 A 2 L 0 SSF 170 187 144 216 245 160 132 FR9 480 x 1150 x 362
NXS 0208 6 A 2 L 0 SSF 208 229 170 255 289 200 160 FR9 480 x 1150 x 362
AC drive type
Loadability Motor shaft power
Enclosure
Dimensions
W x H x D [mm]
Low (+40°C) High (+40°C)
Maximum
current I
S
690 V supply
Rated
continuous
current I
L
[A]
10%
overload
current [A]
Rated
continuous
current I
H
[A]
50%
overload
current [A]
10% overl.
P [kW]
50% overl.
P [kW]
NXS 0261 6 A 2 L 0 SSA 261 287 208 312 375 250 200 FR10 595 x 2018 x 602
NXS 0325 6 A 2 L 0 SSA 325 358 261 392 470 315 250 FR10 595 x 2018 x 602
NXS 0385 6 A 2 L 0 SSA 385 424 325 488 585 355 315 FR10 595 x 2018 x 602
NXS 0416 6 A 2 L 0 SSA* 416 458 325 488 585 400 315 FR10 595 x 2018 x 602
NXS 0460 6 A 2 L 0 SSA 460 506 385 578 693 450 355 FR11 794 x 2018 x 602
NXS 0502 6 A 2 L 0 SSA 502 552 460 690 828 500 450 FR11 794 x 2018 x 602
NXS 0590 6 A 2 L 0 SSA* 590 649 502 753 904 560 500 FR11 794 x 2018 x 602
For all VACON® NXS drives, overloadability is dened as follows:
High: 1.5 x I
H
(1 min/10 min) @ 50°C; Low: 1.1 x I
L
(1 min/10 min) @ 40°C; I
S
for 2 sec every 20 sec.
* Max. ambient temperature of +35˚C
4 Danfoss Drives · DKDD.PB.913.A1.02
Содержание
- Features 2
- Vacon nxs is a compact ac drive in the power range of 0 7 560 kw and supply voltages of 208 690 v for heavy use in machines buildings and all branches of industry 2
- Vacon nxs the reliable choice 2
- Danfoss drives dkdd pb 13 a1 2 3
- Mains voltage 380 500 v 50 60 hz 3 standalone units 3
- Mains voltage 380 500 v 50 60 hz 3 wall mounted units 3
- Ratings and dimensions 3
- Danfoss drives dkdd pb 13 a1 2 4
- Hardware configurations standalone units 4
- Mains voltage 500 690 v 50 60 hz 3 standalone units 4
- Mains voltage 500 690 v 50 60 hz 3 wall mounted units 4
- Ratings and dimensions 4
- A2 00 00 00 5
- Danfoss drives dkdd pb 13 a1 2 5
- Mains voltage 208 240 v 50 60 hz 3 wall mounted units 5
- Type code key 5
- Vacon nxs 0003 5 a 2 h 1 s s s a1 a2 00 00 00 5
- An external 24 v supply option enables communication with the control unit even if the mains supply is switched off e g fieldbus communication and parameter settings 6
- Danfoss drives dkdd pb 13 a1 2 6
- Option boards 6
- Removable terminals snap in card installation automatic card identification and instructions on the drive help making quick connections if necessary the inputs outputs and fieldbus boards can be added in the field the vacon nxs is simply the most flexible frequency converter series on the market 6
- The vacon nxs units are delivered with opt a1 and opt a2 boards if the i o is not specified in many countries boards opt a1 and opt a3 are used as standard i o as the galvanically isolated thermistor input is often required 6
- There are no fixed inputs or outputs in the vacon nxs there are five slots a b c d and e for i o boards and a suitable board can be selected for each slot see the table below 6
- Vacon nxs control unit 6
- Danfoss drives dkdd pb 13 a1 2 7
- Opt a1 opt a2 7
- Opt a3 alternative 7
- Other typical options 7
- Vacon nxs standard i o 7
- A maximum of three values can be monitored simultaneously the multi monitoring feature 8
- Basic standard local remote multi step speed control 8
- First class usability 8
- Ncdrive for parameter setting copying storing printing monitoring and controlling 8
- Ncload for software updating and uploading special software to the drive 8
- The uncluttered text display panel with a well defined menu structure and functions such as automatic parameter copy and start up wizard makes commissioning and fine tuning as easy as possible 8
- The vacon pc tools require only an rs232c cable for communication with the drive no adapters etc required 8
- Vacon pc tools are available for download through our website at drives danfoss com 8
- Vacon pc tools include 8
- Vacon programming tool is available for makingtailor made software a license key and training required 8
- All in one application package standard water solutions application package option special applications several options 9
- Control with the integrated pid controller in most cases the default basic application is suitable and only the min max frequencies as well as motor nominal values must be set 9
- Package can be replaced by the water application package that contains several applications optimized for water handling there are also several other general purpose software applications available 9
- Pid control multi purpose control pump and fan control 9
- Software modularity 9
- Thanks to the modular software applications made by the vacon programming tool based on iec 61131 standard the all in one application 9
- The all in one application package has seven applications default settings and functionality of control inputs and outputs see tables below which can be selected with one parameter the application will also be requested by the start up wizard at the first power up with this single setting the controls can be programmed e g for two external control places or a pressure 9
- Emc and installation environment 10
- Emc selection table restricted distribution 10
- Environment 10
- Environments i e in practice the public and industrial networks respectively 10
- The product family standard en iec 61800 3 a1 sets limits for both emissions and immunity of radio frequency disturbances the environment has been divided into the 10
- Danfoss drives dkdd pb 13 a1 2 11
- Technical data 11
- Danfoss drives 12
- Danfoss drives is a world leader in variable speed control of electric motors we aim to prove to you that a better tomorrow is driven by drives it is as simple and as ambitious as that 12
Похожие устройства
- Vacon NXS0018-6A2L0SSS Краткое руководство
- Vacon NXS0018-6A2L0SSS Руководство по применению
- Vacon NXS0018-6A2L0SSS Руководство пользователя
- Vacon NXS0022-6A2L0SSS Брошюра
- Vacon NXS0022-6A2L0SSS Краткое руководство
- Vacon NXS0022-6A2L0SSS Руководство по применению
- Vacon NXS0022-6A2L0SSS Руководство пользователя
- Vacon NXS0027-6A2L0SSS Брошюра
- Vacon NXS0027-6A2L0SSS Краткое руководство
- Vacon NXS0027-6A2L0SSS Руководство по применению
- Vacon NXS0027-6A2L0SSS Руководство пользователя
- NATIONAL NK-MG010 Инструкция по эксплуатации
- Vacon NXS0034-6A2L0SSS Брошюра
- Vacon NXS0034-6A2L0SSS Краткое руководство
- Vacon NXS0034-6A2L0SSS Руководство по применению
- Vacon NXS0034-6A2L0SSS Руководство пользователя
- Vacon NXS0041-6A2L0SSS Брошюра
- Vacon NXS0041-6A2L0SSS Краткое руководство
- Vacon NXS0041-6A2L0SSS Руководство по применению
- Vacon NXS0041-6A2L0SSS Руководство пользователя