Vacon NXS0027-6A2L0SSS [3/12] Ratings and dimensions

Vacon NXS0004-6A2L0SSS [3/12] Ratings and dimensions
Ratings and dimensions
Mains voltage 380-500 V, 50/60 Hz, 3~, Wall-mounted units
Mains voltage 380-500 V, 50/60 Hz, 3~, Standalone units
AC drive type
Loadability Motor shaft power
Enclosure
Dimensions
W x H x D [mm]
Low (+40°C) High (+50°C)
Maximum
current I
S
400 V supply
Rated
continuous
current I
L
[A]
10%
overload
current [A]
Rated
continuous
current I
H
[A]
50%
overload
current [A]
10% overl.
P [kW]
50% overl.
P [kW]
NXS 0003 5 A 2 H 1 SSS 3.3 3.6 2.2 3.3 4.4 1.1 0.75 FR4 128 x 292 x 190
NXS 0004 5 A 2 H 1 SSS 4.3 4.7 3.3 5.0 6.2 1.5 1.1 FR4 128 x 292 x 190
NXS 0005 5 A 2 H 1 SSS 5.6 6.2 4.3 6.5 8.6 2.2 1.5 FR4 128 x 292 x 190
NXS 0007 5 A 2 H 1 SSS 7.6 8.4 5.6 8.4 10.8 3 2.2 FR4 128 x 292 x 190
NXS 0009 5 A 2 H 1 SSS 9 9.9 7.6 11.4 14 4 3 FR4 128 x 292 x 190
NXS 0012 5 A 2 H 1 SSS 12 13.2 9 13.5 18 5.5 4 FR4 128 x 292 x 190
NXS 0016 5 A 2 H 1 SSS 16 17.6 12 18.0 24 7.5 5.5 FR5 144 x 391 x 214
NXS 0022 5 A 2 H 1 SSS 23 25.3 16 24.0 32 11 7.5 FR5 144 x 391 x 214
NXS 0031 5 A 2 H 1 SSS 31 34 23 35 46 15 11 FR5 144 x 391 x 214
NXS 0038 5 A 2 H 1 SSS 38 42 31 47 62 22 15 FR6 195 x 519 x 237
NXS 0045 5 A 2 H 1 SSS 46 51 38 57 76 22 22 FR6 195 x 519 x 237
NXS 0061 5 A 2 H 1 SSS 61 67 46 69 92 30 22 FR6 195 x 519 x 237
NXS 0072 5 A 2 H 1 SSS 72 79 61 92 122 37 30 FR7 237 x 591 x 257
NXS 0087 5 A 2 H 1 SSS 87 96 72 108 144 45 37 FR7 237 x 591 x 257
NXS 0105 5 A 2 H 1 SSS 105 116 87 131 174 55 45 FR7 237 x 591 x 257
NXS 0140 5 A 2 H 1 SSS 140 154 105 158 210 75 55 FR8 291 x 758 x 344
NXS 0168 5 A 2 H 1 SSS 170 187 140 210 280 90 75 FR8 291 x 758 x 344
NXS 0205 5 A 2 H 1 SSS 205 226 170 255 336 110 90 FR8 291 x 758 x 344
NXS 0261 5 A 2 H 1 SSS 261 287 205 308 349 132 110 FR9 480 x 1150 x 362
NXS 0300 5 A 2 H 1 SSS 300 330 245 368 444 160 132 FR9 480 x 1150 x 362
AC drive type
Loadability Motor shaft power
Enclosure
Dimensions
W x H x D [mm]
Low (+40°C) High (+40°C)
Maximum
current I
S
400 V supply
Rated
continuous
current I
L
[A]
10%
overload
current [A]
Rated
continuous
current I
H
[A]
50%
overload
current [A]
10% overl.
P [kW]
50% overl.
P [kW]
NXS 0385 5 A 2 L 0 SSA 385 424 300 450 540 200 160 FR10 595 x 2018 x 602
NXS 0460 5 A 2 L 0 SSA 460 506 385 578 693 250 200 FR10 595 x 2018 x 602
NXS 0520 5 A 2 L 0 SSA* 520 572 460 690 828 250 250 FR10 595 x 2018 x 602
NXS 0590 5 A 2 L 0 SSA 590 649 520 780 936 315 250 FR11 794 x 2018 x 602
NXS 0650 5 A 2 L 0 SSA 650 715 590 885 1062 355 315 FR11 794 x 2018 x 602
NXS 0730 5 A 2 L 0 SSA 730 803 650 975 1170 400 355 FR11 794 x 2018 x 602
* max. ambient temperature of +35˚C