M420 General Flux Vector Control Inverter Basic Reference Guide
5
The capacitor or surge absorber can’t be connected to the output side of the inverter, or it may
damage the inverter.
If the motor cable is too long, for the influence of the distribute capacitance, it’s easily to
have electrical resonance, causing the damage of the insulation or large leakage current which
make the inverter over-current protection. If the length of motor cable is more than 100m, a AC
output reactor should be installed near the inverter.
2.2. Control circuit terminals and wiring
The control circuit terminals displayed as below:
GND
AO1
10V
AI1
AI2
GND
TB
TA
TC
RA RB
RC
AO2
485+
485-
DI1
DI2
DI3 DI4 DI5
COM
COM
DI6 HDI7 CME COM Y1 24V
Three phase 380V ≤18.5KW control terminal diagram
GND
AO1
485- DI2DI1
DI3
COMDI4
10V
AI1
AI2 485+ CME
COM
Y1 HDI5 24V
GND
TB
TA
TC
RA RB RC
Three phase 380V ≥22KW control terminal diagram
☞ Function instruction of the control terminals
Tab.1. Control interface function declaration of M420
Category Terminal Terminal Name Function Description
Power source
+10V-GND
External +10 V
power supply
Provide +10 V power supply to external unit,
maximum output current: 10 mA Generally,
it provides power supply to external
potentiometer with resistance range of 1–5
kΩ.
+24V-COM
External +24 V
power supply
Provide +24 V power supply to external
unit. Generally, it provides power supply to
DI/DO terminals and external sensors.
Maximum output current: 200 mA
Analog input
AI1-GND
Analog input 1
1) Input voltage range: 0–10 VDC
;
2) Impedance: 100kΩ
AI2-GND
Analog input 2
1) Input range: 0–10 VDC/4–20 mA,
decided by CN3 dial switches on the control
board
2) Impedance: 100 kΩ (voltage input), 500
Ω (current input)
Digital input
DI1-COM
Digital input 1
1) Optical coupling isolation, compatible
with dual-polarity input. Switch over
through DI dial switch, factory set PNP
DI2-COM
Digital input 2
DI3-COM
Digital input 3
Содержание
- Fig inverters of 18 kw follow 2
- Inverter braking unit part of the matching function if there is demand when ordering 2
- Note this figure for adv 1 0 m420 m adv 18 m420 m 1 18 kw series 2
- Please specify 2
- Typical wiring 2
- Attention this figure is just for m420 series of inverter 22 75kw brake unit is the selective part plese declare it in order request if it s needed 3
- Fig inverters of 22 75kw 3
- Fig three phase inverter above 90kw 4
- Connect to the braking resistor for the ac drive of 7 kw and below 220 v and18 kw and below other voltage classes 5
- Connect to the single phase 220 vac power supply 5
- Connect to the three phase ac power supply 5
- Connecting terminals of braking resistor 5
- Connecting terminals of braking resistor connect to a braking resistor 5
- Grounding terminal grounding terminal must be grounded 5
- Main circuit terminals and wiring 5
- Main circuit terminals of three phase 5
- Output terminals connect to a three phase motor 5
- Positive and negative terminals of dc bus common dc bus input point 5
- Single phase power supply input terminals 5
- Three phase power supply input terminals 5
- Wiring precautions 5
- Control circuit terminals and wiring 6
- Operation and display 8
- Operation and display interface introduction 8
- Description of function led indicator 9
- Led display 9
- Keyboard instruction 10
- Organization way of the inverter function code 10
- Enter key 11
- Fig parameter setting operation flowchart 11
- Fig three level menu operation flow chart 11
- For example make function code f1 04 change from 0 0hz to 5 0hz 11
- Function code parameter of m420 inverter adopts three level menu it can view and monitor the parameter by operation panel the three level menu includes function parameter set level 1 menu function code level 2 menu function code setup value level 3 menu refer to fig 2 for the operation procedure in the state parameter interface it can check the different status parameter by the key 11
- In the status of the 11
- Instruction of function code viewing and modification methods 11
- Level menu but it will save the present parameter data and move to the next function code if press enter while it will give up the present parameter revising if press prg 11
- Menu the value can t be modified if the parameter doesn t have the flashing digit you can check the function code property description for the specific reasons 11
- Shift enter 11
- Tips when operating with the three level menu you can press prg or enter to return to 11
- Trouble shooting m420 general flux vector control inverter user manual 11
- Fault warnings and solutions 12
- Trouble shooting 12
- Common faults and treating methods 17
- Function code table 19
- F1 06 startup dc braking current pre excited current 0 25
- F1 07 startup dc braking time pre excited time 0 25
- F1 08 acceleration deceleration mode 0 linear 25
- S curve 0 25
- Fault type 67
Похожие устройства
- Advanced Control ADV 110 M420-M Общий каталог
- Advanced Control ADV 110 M420-M Руководство по эксплуатации
- Advanced Control ADV 110 M420-M Спецификация
- Advanced Control ADV 132 M420-M Краткое руководство
- Advanced Control ADV 132 M420-M Общий каталог
- Advanced Control ADV 132 M420-M Руководство по эксплуатации
- Advanced Control ADV 132 M420-M Спецификация
- Advanced Control ADV 160 M420-M Краткое руководство
- Advanced Control ADV 160 M420-M Общий каталог
- Advanced Control ADV 160 M420-M Руководство по эксплуатации
- Advanced Control ADV 160 M420-M Спецификация
- Advanced Control ADV 185 M420-M Краткое руководство
- Advanced Control ADV 185 M420-M Общий каталог
- Advanced Control ADV 185 M420-M Руководство по эксплуатации
- Advanced Control ADV 185 M420-M Спецификация
- Advanced Control ADV 200 M420-M Краткое руководство
- Advanced Control ADV 200 M420-M Общий каталог
- Advanced Control ADV 200 M420-M Руководство по эксплуатации
- Advanced Control ADV 200 M420-M Спецификация
- Advanced Control ADV 220 M420-M Краткое руководство