Cautions, Warnings and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The Cautions, Warnings, and instructions in this section summarize the
procedures necessary to ensure an inverter installation complies with
Underwriters Laboratories
®
guidelines.
Circuit Breaker and Fuse Sizes
The variable frequency drives connections to input power must include
UL Listed inverse time circuit breakers with 600 V rating, or UL Listed fuses as
shown in the table below.
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are
presented in the table below.
Wire Connectors
Motor Overload Protection
DA1 variable frequency drives provide solid-state motor overload protection,
which depends on the proper setting of the following parameter:
P1-08 current limit.
Set the rated current [Amperes] of the motor(s) with the above parameters.
The setting range is 25 % rated current to 100 % rated current,
manual MN04020005Z
NOTICE
Use 60/75 °C Cu wire only or equivalent.
NOTICE
Open Type Equipment.
NOTICE
Suitable for use on a circuit capable of delivering not more than
5,000 rms (AS) symmetrical amperes has:
240 V maximum for DA1-12 and DA1-32 models
480 V maximum for DA1-34 models
NOTICE
Field wiring connections must be made by a UL Listed and CSA
Certified ring lug terminal connector sized for the wire gauge being
used. The connector must be fixed using the crimping tool specified
by the connector manufacturer.
NOTICE
When two or more motors are connected to the inverter, they
cannot be protected by the electronic overload protection.
Install an external thermal relay on each motor.
Terminal (ring lug)
Cable
Cable support
Cable
Cable
PE
Inverter Model Mains Motor Screw Torque
Input Voltage Fuse/Braker Wiring Power Wiring Power unit
(UL-rated, class J, 600 V) Size range Size Range
A AWG kW HP AWG lb-in Nm
DA1-124D3 220-240 V 15 12 0.75 1 14 9 1
DA1-127D0
Single Phase 20 10 1.5 2 14
DA1-12011 25 8 2.2 3 14
DA1-324D3 220-240 V 6 14 0.75 1 14
DA1-327D0 Three Phase 10 14 1.5 2 14
DA1-32011 10 14 2.2 3 14
DA1-32018 25 10 4 5 10
DA1-342D2 440-480 V 6 14 0.75 1 14
DA1-344D1 Three Phase 10 14 1.5 2 14
DA1-345D8 10 14 2.2 3 14
DA1-349D5 15 14 4 5 14
DA1-34014 20 12 5.5 7.5 12
DA1-34018 25 10 7.5 10 10
1) kW @ 230 V/400 V, 50 Hz, 1500 min
-1
HP @ 230 V/460 V 60 Hz, 1800 rpm
AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
MCM/kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm
2
= square millimeters, a measure of wire cross-sectional area