FILTERS
Common
mode filter
Output choke
Output choke &
overshoot clamp
Sine wave
filter
All-pole sine
wave filter
Phenomenon
Common mode currents
Effective Limited effect Limited effect Effective Very effective
Bearing currents Effective Very effective
Voltage spikes U-V-W Limited effect Very effective Very effective Very effective
Voltage spikes U-PE Limited effect Effective Limited effect Very effective
dU/dt Effective Effective Very effective Very effective
Minimize motor audible noise Limited effect Limited effect Effective Effective
EMC conducted emission Limited effect Limited effect Limited effect Effective Very effective
Recommendations with the different supply
voltages up to and including 480 V
FILTERS
Common
mode filter
Output choke
Output choke &
overshoot clamp
Sine wave
filter
All-pole sine
wave filter
Situation
Not rated, delicate or difficult positioned motors
X X
Motor in frame size >280 X
IEC 60034-17 motor X
IEC 60034-25
curve A motor
Cable lengths 0-100m**
Cable lengths 100-200m X
Cable lengths 200-500m X
Dynamic use with frequently raised DC voltage
(braking)
X
Unshielded cables * X
X = advised solution for this setup
Recommendations with the different supply
voltages from 500 V - 690 V
FILTERS
Common
mode filter
Output choke
Output choke &
overshoot clamp
Sine wave
filter
All-pole sine
wave filter
Situation
Not rated, delicate or difficult positioned motors
X X
Motor in frame size >280 X
3 kV isolation windings **
IEC 60034-25
curve B motor
Cable lengths 0-100m**
Cable lengths 100-200m X
Cable lengths 200-500m X
Dynamic use with frequently raised DC voltage
(braking)
X
Unshielded cables * X
X = advised solution for this setup
Filter selection guide
Remarks
Cable lengths should always be as short as possible.
The table is based on correct EMC wiring with shielded cable and proper
EMC installation.
Voltage drop over the complete system must be less than 10% of the
main supply.
* Conducted interference limits on unshielded motor - lines according to
EN61800-3, table 16.
** No marks in a row, means that there is no need to take precautions
CAD drawings available on the web
2D and 3D CAD drawings for Emotron AC drives,
softstarters and monitors are available via our website.
These will assist anyone working with our products, for
example, consultants, installers or machine builders.
Visit www.cgglobal.com or
www.emotron.com for direct access to all CAD
documents.