Emotron CDU/CDX 48-026 [5/8] Operation at higher temperatures

Emotron CDU/CDX 48-018 [5/8] Operation at higher temperatures
Emotron AB 01--4965--01r1 4
Operation at higher temperatures
Most Emotron variable speed drives are designed for
operation at maximum of 40°C ambient temperature.
However it is possible to use the VSD at higher temperatures
with little loss in performance.
Table 6 shows ambient temperature as well as derating for
higher temperatures.
Example
In this example we have a motor with the following data that
we want to run at the ambient temperature of 45°C:
Voltage 400 V
Current 29 A
Power 15 kW
Select variable speed drive
The ambient temperature is 5 °C higher than the maximum
ambient temperature. The following calculation is made to
select the correct VSD model.
Derating is possible with loss in current capacity of
2.5%/°C.
Derating will be: 5 x 2.5% = 12.5%
Calculation for model CDU/CDX 48-031:
31 A - (12.5% x 31) = 27.1 A; this is not enough.
Calculation for model CDU/CDX 48-037
37 A - (12.5% x 37) = 32.4 A
In this example we select the CDU/CDX 48-037.
Operation at higher switching
frequency
Only valid for CDU.
Table 7 shows the switching frequency for the different VSD
models. With the possibility of running at higher switching
frequency you can reduce the noise level from the motor.
Note!
For switching Frequency >3 kHz contact Emotron AB
Table 6 Ambient temperature and derating for
400 – 525V types
Model
IP55
Max temp. Derating: possible
CDU/CDX 48/52
008 to - 046
40°C
-2.5%/°C to
max +10°C (50 C)
Table 7 Switching frequency
Models
Standard
Switching
frequency
Range
CDU/CDX 48/52
008 to - 046
3 kHz 1,5 – 6 kHz

Содержание

Скачать