Galletti LER CS/CL 162 [2/9] Galletti com vm66000387 c

Galletti LER CS/CL 82 [2/9] Galletti com vm66000387 c
219
galletti.com VM66000387-C
Air chillers and heat pumps - LER
LER 40 - 420 kW
Version
Fields
1 2 3 4 5 6 7 8 9 10
LER062CS 0 B 0 0 0 1 G 0 0 0
CONFIGURATION
The models are completely configurable by selecting the
version and the options. To the right is shown an example
of configuration.
CONFIGURATION OPTIONS
Cooling only versions
LER..CS Standard execution
LER..CL Low noise execution
AVAILABLE VERSIONS
To verify the compatibility of the options, use the selection software or the price list.
1 - POWER SUPPLY
0 400/3/50 + N
2 400/3/50 + N + Circuit breakers
2 - CONTROL MICROPROCESSOR AND THERMAL EXPANSION VALVE
0 Base + electronic expansion valve
A Base + mechanical expansion valve
B Programmable (LCD 8x22 display) + electronic expansion valve
C Programmable (LCD 8x22 display) + mechanical expansion valve
3 - PARTIAL HEAT RECOVERY (condensation control option is mandatory)
0 Absent
D Desuperheater (40% of cooling capacity recovery in rated conditions)
4 - AIR FLOW MODULATION OF REMOTE UNIT
0 Absent
C Condensation control with fan adjusted by potentiometer
P Condensation control with 1-10V modulated output signal
5 – AIR FLOW MODULATION USER SIDE
0 Absent
D Air flow modulation with output signal in ∆T logic = cost
T Air flow modulation with output signal in T logic = cost
6 - REMOTE COMMUNICATION
0 Absent
1 RS485 Serial board (Modbus or Carel protocol)
2 Lonworks serial board
3 GSM modem kit
4 Ethernet card (SNMP or BACNET protocol) + clock card
5 Ethernet card + clock card + supervision software
7 - VIBRATION ISOLATION
0 Absent
G Rubber vibration dampers at the base of the unit
M Spring vibration dampers at the base of the unit
8 - PACKING
0 Standard
1 Wooden crate
2 Wooden case
9 - REMOTE CONTROL
0 Absent
1 Simplified remote control panel
2 Remote display for base microprocessor
3 Remote display for programmable microprocessor
10 - CONFIGURATION FOR LONG REFRIGERANT CIRCUITS
0 Absent
1 Oil recovery kit for refrigerant lines > 30 m (not for efficiency pack 1)
ACCESSORIES
MAIN COMPONENTS
Structure
Cooling circuit Electronic microprocessor controller
Scroll compressors Heat exchanger
Made in galvanised steel sheet
with a polyester powder coa-
ting for outdoors.
The compressor compartment
is completely sealed and may
be accessed on 3 sides thanks
to easy-to-remove panels that
greatly simplify maintenance
and/or inspection.
It can be made in three different versions with
the same power (Efficiency Pack), using mainly:
• R410A scroll compressors
• braze-welded plate exchangers
• electronic expansion valves
It allows complete management of the unit. The electronic control sy-
stem allows the setpoint to be adjusted automatically according to the
outdoor temperature in order to reduce consumption and broaden the
working temperature range. With the advanced microprocessor control
it is possible to set up LAN networks for controlling 4 units in parallel.
Scroll compressors are now
the best solution in terms of
reliability and sound power
emitted. The compressors are
supplied complete with motor
protection against overheating,
overcurrents and excessive
outlet gas temperatures.
Heat exchangers with bra-
ze-welded AISI 316 auste-
nitic stainless steel plates
and connections made of
AISI 316 L, characterised by a
reduced carbon content to
facilitate brazing.
A Power factor correction capacitors
B Soft-starter kit
C Service kit (kit of sensors for quick diagnosis)
D Clock card
E ON/OFF status of the compressors
F Remote contact for power step limits
G Configurable digital alarm card
H Pressure gauges
I Pair of Victaulic couplings for quick water IN-OUT connection
L Regulating filter kit (solenoid and tap on the liquid line)
M Outdoor temperature probe for setpoint compensation
N Normative reference other than "97/23/CE - PED"
P Unit lifting kit

Содержание