Invertek Drives ODE-2-22150-1K04 [12/24] Control terminal connections

Invertek Drives ODE-2-12150-1KB1 [12/24] Control terminal connections
12 Optidrive E2 IP66 / NEMA 4X User Guide
www.invertek.co.uk
5. Control Wiring
5.1. Control terminal connections
Default
Connections
Control
Terminal
Signal
Description
1
+24V User Output,
+24V, 100mA.
2
Digital Input 1
Positive logic
“Logic 1” input voltage range: 8V … 30V DC
“Logic 0” input voltage range: 0V … 2V DC
3
Digital Input 2
4
Digital Input 3 /
Analog Input 2
Digital: 8 to 30V
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
5
+10V User Output
+10V, 10mA, 1kΩ minimum
6
Analog Input 1 /
Digital Input 4
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
Digital: 8 to 30V
7
0V
User ground connected terminal 9
8
Analog Output /
Digital Output
Analog: 0 to 10V, 20mA maximum
Digital: 0 to 24V
9
0V
User ground connected terminal 7
10
Relay Common
11
Relay NO Contact
Contact 250Vac, 6A / 30Vdc, 5A
5.2. RJ45 Data Connection
For drives with software V1.02 & later
For MODBUS RTU register map
information please refer to the Optidrive
E2 Application note AN-ODE-01.
When using MODBUS control the Analog
and Digital Inputs can be configured as
shown in section 8.3 MODBUS control
mode (P12 = 3 or 4)
6. Operation
6.1. Managing the keypad
The drive is configured and its operation monitored via the keypad and display.
NAVIGATE
UP
DOWN
RESET /
STOP
START