3.3. Gland Sizes & Lock off
The use of suitable gland system is required to maintain the appropriate IP / Nema rating. Cable entry holes will need to be drilled to
suit this system. Some guidelines sizes are defined below:
Please take care when drilling to avoid leaving any particles within the product.
Cable Gland recommended Hole Sizes & types:
Hole Size
Imperial
Metric
Size 1
22mm
PG13.5
M20
Size 2 & 3
25mm
PG16
M25
Flexible Conduit Hole Sizes:
Drill Size
Trade Size
Metric
Size 1
28mm
¾ in
21
Size 2 & 3
35mm
1 in
27
UL rated ingress protection ("Type " ) is only met when cables are installed using a UL recognized bushing or fitting for a
flexible-conduit system which meets the required level of protection ("Type")
For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC
Not intended for rigid conduit system
Power Isolator Lock Off:
On the switched models the main
power isolator switch can be locked in
the „Off‟ position using a 20mm
standard shackle padlock (not
supplied).
Press the centre of the switch and
insert a suitable padlock.
3.4. Removing the Terminal Cover
Undoing the 2 screws on the front of the product allows access to the connection terminals, as shown below.