Invertek Drives ODE-2-24220-3K04 [23/24] Rating tables

Invertek Drives ODE-2-14075-3KA1 [23/24] Rating tables
Optidrive E2 IP66 / NEMA 4X User Guide 23
www.invertek.co.uk
10.2. Rating tables
110-115V ±10% - 1 Phase Input - 3 Phase 230V Output (Voltage Doubler)
kW
HP
Frame
Size
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply
Cable
Size
Nominal
Output
Current
150%
Output
Current
60 secs
Motor
Cable
Size
Max
Motor
Cable
Length
Min
Brake
Res
Value
Amps
Amps
mm
2
Amps
Amps
mm
2
m
-
0.5
1
6.7
10
1.5
2.3
3.45
1.5
25
-
-
1
1
12.5
16(15)*
1.5
4.3
6.45
1.5
25
-
-
1.5
2
16.8
20
2.5
5.8
8.7
1.5
100
47
200-240V ±10% - 1 Phase Input 3 Phase Output
kW
HP
Frame
Size
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply
Cable
Size
Nominal
Output
Current
150%
Output
Current
60 secs
Motor
Cable
Size
Max
Motor
Cable
Length
Min
Brake
Res
Value
Amps
Amps
mm
2
Amps
Amps
mm
2
m
0.37
0.5
1
6.7
6
1.5
2.3
3.45
1.5
25
-
0.75
1
1
12.5
10
1.5
4.3
6.45
1.5
25
-
1.5
2
1
19.3
20
4
7
10.5
1.5
25
-
1.5
2
2
19.3
20
4
7
10.5
1.5
100
47
2.2
3
2
28.8
32(35)*
4
10.5
15.75
1.5
100
47
4.0
5
3
35
40
6
15
22.5
2.5
100
47
200-240V ±10% - 3 Phase Input 3 Phase Output
kW
HP
Frame
Size
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply
Cable
Size
Nominal
Output
Current
150%
Output
Current
60 secs
Motor
Cable
Size
Max
Motor
Cable
Length
Min
Brake
Res
Value
Amps
Amps
mm
2
Amps
Amps
mm
2
m
0.37
0.5
1
3
6
1.5
2.3
3.45
1.5
25
-
0.75
1
1
5.8
10
1.5
4.3
6.45
1.5
25
-
1.5
2
1
9.2
16(15)*
2.5
7
10.5
1.5
25
-
1.5
2
2
9.2
16(15)*
2.5
7
10.5
1.5
100
47
2.2
3
2
13.7
20
4
10.5
15.75
1.5
100
47
4.0
5
3
20.7
32(35)*
4
18
27
2.5
100
47
380-480V ±10% - 3 Phase Input 3 Phase Output
kW
HP
Frame
Size
Nominal
Input
Current
Fuse or
MCB
(type B)
Supply
Cable
Size
Nominal
Output
Current
150%
Output
Current
60 secs
Motor
Cable
Size
Max
Motor
Cable
Length
Min
Brake
Res
Value
Amps
Amps
mm
2
Amps
Amps
mm
2
m
0.75
1
1
2.9
5
1.5
2.2
3.3
1.5
25
-
1.5
2
1
5.4
10
1.5
4.1
6.15
1.5
25
-
1.5
2
2
5.4
10
1.5
4.1
6.15
1.5
50
100
2.2
3
2
7.6
10
1.5
5.8
8.7
1.5
50
100
4
5
2
12.4
16(15)*
2.5
9.5
14.25
1.5
50
100
5.5
7.5
3
16.1
20
2.5
14
21
2.5
100
22
7.5
10
3
17.3
20
4
18
27
2.5
100
22
Output Frequency range: 0 - P-01 (500Hz max)
For UL compliance Motor Cable to be Copper 75C and Fuse current rating defined by ratings marked ( )*
10.3. Maximum supply ratings for UL compliance:
Drive rating
Maximum supply voltage
Maximum supply
short-circuit current
115V ratings
0.5 HP to 1.5HP
120V rms (AC)
5kA rms (AC)
230V ratings
0.37kW (0.5HP) to 3.7kW (5HP)
240V rms (AC)
5kA rms (AC)
400/460V ratings
0.75kW(1HP) to 7.5kW(10HP)
480V rms (AC)
5kA rms (AC)
All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above specified maximum
short-circuit Amperes symmetrical with the specified maximum supply voltage.

Содержание