5.5. Terminal Control
When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and
default values as indicated in section 6 Parameters
.
•
Connect the drive to the supply, ensuring the correct voltage and fusing / circuit breaker prote
•
Connect the motor to the drive, ensuring the correct star/delta connection for the voltage rating
•
Enter the motor data from motor nameplate; P1
•
Connect a control switch between the control termina
• Connect a potentiometer (1k
Ω min to 10 kΩ max) between terminals 5 and 7, and the wiper to terminal 6.
•
With the potentiometer set to zero, switch on the supply to the drive. The display will s
• Close the control switch, terminals 1-
2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the potentiometer.
•
On first enable from factory default parameters, the Optidrive will carry out an Autotune, and the display sho
control switch closed an allow this to complete.
•
Following completion of the Autotune, the display shows zero speed in Hz (
•
Turn the potentiometer to maximum. The motor will accelerate t
control of the acceleration ramp time P1
-
•
If the potentiometer is turned to minimum, the motor will decelerate to 0Hz, the default mini
of the deceleration ramp P1-
04. The output speed can be adjusted anywhere between minimum and maximum speed using the
potentiometer.
•
To display motor current (Amps), briefly press the
• Press
again to display the motor power.
• Press
again to return to speed display.
•
To stop the motor, disable the drive by opening the control switch (terminals 1
•
If the enable/disable switch is opened the drive will decelerate to stop at which time the dis
5.6. Keypad Control
To allow the Optidrive to be controlled from the keypad in a forward direction only, set P1
•
Connect the supply and motor as for terminal control above.
•
Enable the drive by closing the switch between control terminals 1 & 2. The display will show
• Press the
key. If this is the first enable from factory default parameters, the drive will carry out an Autotune as described above. On
completion of the
Autotune, the display shows
• Press to increase speed.
•
The drive will run forward, increasing speed until
• Press
to decrease speed. The drive will decrease speed until
P1-04
• Press the
key. The drive will decelerate to rest at the rate set in P1
• The display will finally show
StoP
StoPStoP
StoP
at which point the drive is disabled
•
To preset a target speed prior to enable, press the
&
keys to adjust as required then press the
• Pressing the
key will start the drive accelerating to the target speed.
•
To allow the Optidrive to be controlled from the keypa
• Operation is the same as when P1-
12=1 for start, stop and changing speed.
• Press the
key. The display changes to
• Press to increase speed
•
The drive will run forward, increasing speed until
the speed set in P1-01.
•
To reverse the direction of rotation of the motor, press the
Optidrive Plus 3
GV
Compact - User Guide
www.invertek.co.uk
When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and
.
Connect the drive to the supply, ensuring the correct voltage and fusing / circuit breaker prote
ction
–
Connect the motor to the drive, ensuring the correct star/delta connection for the voltage rating
-
see section
Enter the motor data from motor nameplate; P1
-07 = motor rated voltage, P1-
08 = motor rated current, P1
Connect a control switch between the control termina
ls 1 and 2 ensuring that the contact is open (drive disabled).
Ω min to 10 kΩ max) between terminals 5 and 7, and the wiper to terminal 6.
With the potentiometer set to zero, switch on the supply to the drive. The display will s
how
StoP
StoPStoP
StoP
.
2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the potentiometer.
On first enable from factory default parameters, the Optidrive will carry out an Autotune, and the display sho
control switch closed an allow this to complete.
Following completion of the Autotune, the display shows zero speed in Hz (
H
HH
H 0
0 0
0.0
00
0
) with the potentiometer turned to minimum.
Turn the potentiometer to maximum. The motor will accelerate t
o 50Hz, (60Hz for USA drives), the default value of P1
-
03. The display shows 50Hz (
H
HH
H
5
55
50
00
0.0
00
0
) at max speed.
If the potentiometer is turned to minimum, the motor will decelerate to 0Hz, the default mini
mum speed set in P1
04. The output speed can be adjusted anywhere between minimum and maximum speed using the
To display motor current (Amps), briefly press the
(Navigate) key.
again to display the motor power.
again to return to speed display.
To stop the motor, disable the drive by opening the control switch (terminals 1
-2).
If the enable/disable switch is opened the drive will decelerate to stop at which time the dis
play will show
To allow the Optidrive to be controlled from the keypad in a forward direction only, set P1
-12 =1:
Connect the supply and motor as for terminal control above.
Enable the drive by closing the switch between control terminals 1 & 2. The display will show
StoP
StoPStoP
StoP
.
key. If this is the first enable from factory default parameters, the drive will carry out an Autotune as described above. On
Autotune, the display shows
H
HH
H 0
0 0
0.0
00
0
.
The drive will run forward, increasing speed until
is released.
to decrease speed. The drive will decrease speed until
is released. The rate of deceleration is limited by the setti
key. The drive will decelerate to rest at the rate set in P1
-04.
at which point the drive is disabled
To preset a target speed prior to enable, press the
key whilst the drive is stopped. The disp
lay will show the target speed, use the
keys to adjust as required then press the
key to return the display to
StoP
StoPStoP
StoP
.
key will start the drive accelerating to the target speed.
To allow the Optidrive to be controlled from the keypa
d in a forward and reverse direction, set P1-
12 =2:
12=1 for start, stop and changing speed.
key. The display changes to
H
HH
H 0
0 0
0.0
00
0
.
The drive will run forward, increasing speed until
is
released. Acceleration is limited by the setting in P1
To reverse the direction of rotation of the motor, press the
key again.
11
When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and
all parameters have the
–
see section 2.2 on page 5.
see section
0 on page 8.
08 = motor rated current, P1
-09 = motor rated frequency.
ls 1 and 2 ensuring that the contact is open (drive disabled).
Ω min to 10 kΩ max) between terminals 5 and 7, and the wiper to terminal 6.
2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the potentiometer.
On first enable from factory default parameters, the Optidrive will carry out an Autotune, and the display sho
ws
Auto-t
Auto-tAuto-t
Auto-t
. Leave the
) with the potentiometer turned to minimum.
o 50Hz, (60Hz for USA drives), the default value of P1
-01, under the
mum speed set in P1
-02, under the control
04. The output speed can be adjusted anywhere between minimum and maximum speed using the
play will show
StoP
StoPStoP
StoP
.
.
key. If this is the first enable from factory default parameters, the drive will carry out an Autotune as described above. On
is released. The rate of deceleration is limited by the setti
ng in
lay will show the target speed, use the
12 =2:
released. Acceleration is limited by the setting in P1
-03. The maximum speed is
Содержание
- Compact 1
- Optidrive plus 1
- User guide 1
- Ce konformitätserklärung 2
- Copyright invertek drives ltd 2007 2
- Declaration of conformity 2
- Déclaration de conformité 2
- This user guide is for use with v3 0 firmware user guide issue 1 6 11 08 2
- Analog and digital input configurations 18 3
- Introduction 4 3
- Mechanical installation 6 3
- Operation 9 3
- Parameters 13 3
- Power and control connections 7 3
- Technical data 5 3
- Troubleshooting 20 3
- Critical applications 4
- Electromagnetic compatibility emc 4
- Important safety information 4
- Information 4
- Introduction 4
- Safety of machinery and safety critical applications 4
- 240v 10 1 phase input 3 phase output with emc filter 200 240v 10 1 phase input 3 phase output with emc filter 5
- 240v 10 1 phase input 3 phase output without emc filter 5
- 480v 10 3 phase input 3 phase output with emc filter 5
- 480v 10 3 phase input 3 phase output without emc filter 5
- Compact user guide 5
- Environmental 5
- Opc 1 12075 1k012 0 5 1 12 16 1 4 6 1 10 5
- Opc 1 12075 1kb12 0 5 1 12 16 1 4 6 1 10 5
- Opc 1 12150 1k012 1 2 19 25 4 7 10 1 10 5
- Opc 1 12150 1kb12 1 2 19 25 4 7 10 1 10 5
- Opc 1 14075 3k012 0 5 1 2 6 1 2 3 1 10 5
- Opc 1 14075 3ka12 0 5 1 2 6 1 2 3 1 10 5
- Opc 1 14150 3k012 1 2 5 6 1 4 6 1 10 5
- Opc 1 14150 3ka12 1 2 5 6 1 4 6 1 10 5
- Operational ambient temperature range 10 60 c frost and condensation free storage ambient temperature range 40 60 c maximum altitude 2000m derate above 1000m 1 100m maximum humidity 95 non condensing 5
- Optidrive plus 5
- Rating tables 5
- Technical data 5
- Www invertek co uk 5
- Base view 6
- Enclosure mounting 6
- General 6
- Mechanical dimensions and mounting 6
- Mechanical installation 6
- Mounting location holes mounting location holes four total located at each corner 4 mm diameter suitable for m4 screws 2 nm max 6
- Ground fault monitoring 7
- Grounding guidelines 7
- Grounding the drive 7
- Power and control connections 7
- Safety ground 7
- Wiring precautions 7
- Connection diagram 8
- Drive and motor connections 8
- Motor terminal box connections 8
- Connections 9
- Control terminal connections 9
- Operation 9
- Optional optiport plus keypad 9
- 10 10 10 10
- 110 110 110 10
- Advanced keypad operation short cuts 10
- Changing parameters 10
- Factory default settings 10
- P2 p2 p2 p2 01 01 01 01 10
- P2 p2 p2 p2 26 26 26 26 10
- Pppp x xx 10
- Pppp1 0 1 0 1 0 1 02222 10
- Pppp1 0 1 0 1 0 1 03333 etc 10
- Pppp1 01 1 01 1 01 1 01 10
- Pppp1 10 1 10 1 10 1 10 10
- Reset all parameters to factory default settings 10
- Stop stop stop stop 10
- ____0000 10
- ____10 10 10 10 10
- Ì p def 10
- Auto t auto t auto t auto 11
- Hhhh 0 0 0 0 000 11
- Hhhh 55550000 000 11
- Keypad control 11
- Stop stop stop sto 11
- Terminal control 11
- Auto auto auto auto ttt 12
- Autotune after factory reset or from factory set parameters 12
- Motor autotuning 12
- Operating in sensorless vector speed control mode 12
- Sensorless vector torque control mode 12
- User selected autotune 12
- Parameter group 1 basic parameters 13
- Parameters 13
- Edge edge edge edge rrrr auto auto auto auto 0 0 0 0 auto auto auto auto 1 1 1 1 14
- Parameter group 2 extended parameters 14
- Aaaa 4444 22220000 15
- Aaaa0 0 0 0 22220000 15
- Dddd 0 0 0 0 24 24 24 2 15
- Dddd 0 0 0 0 24 24 24 24 15
- Uuuu 0 0 0 0 24 24 24 2 15
- Uuuu 0 10 0 10 0 10 0 1 15
- Uuuu 0 10 0 10 0 10 0 10 15
- Vvvv 0 0 0 0 24 24 24 24 15
- Parameter group 3 pid control 16
- Parameter group 0 monitoring parameters read only 17
- Parameter group 4 high performance motor control 17
- Analog and digital input configurations 18
- Compact user guide 18
- Optidrive plus 18
- Terminal mode p1 12 0 18
- Www invertek co uk 18
- Compact user guide 19
- Keypad mode p1 12 1 or 2 19
- Optidrive plus 19
- User pi control mode p1 12 19
- Www invertek co uk 19
- Fault messages with optional optiport plus keypad 20
- Troubleshooting 20
Похожие устройства
- Invertek Drives OPC-1-12150-1K012 Инструкция по эксплуатации
- Invertek Drives OPC-1-14075-3K012 Инструкция по эксплуатации
- Invertek Drives OPC-1-14150-3K012 Инструкция по эксплуатации
- Kitfort KT-1374 Инструкция по эксплуатации
- Kitfort KT-1377-1 Инструкция по эксплуатации
- Kitfort KT-1377-2 Инструкция по эксплуатации
- Kitfort KT-1377-3 Инструкция по эксплуатации
- Kitfort KT-1381 Инструкция по эксплуатации
- Kitfort KT-1380 Инструкция по эксплуатации
- Kitfort KT-1379 Инструкция по эксплуатации
- Kitfort KT-1368 Инструкция по эксплуатации
- Kitfort KT-1376-1 Инструкция по эксплуатации
- Kitfort KT-1376-2 Инструкция по эксплуатации
- Kitfort KT-1376-3 Инструкция по эксплуатации
- Kitfort KT-1375-1 Инструкция по эксплуатации
- Kitfort KT-1375-2 Инструкция по эксплуатации
- Kitfort KT-1375-3 Инструкция по эксплуатации
- Kitfort KT-1373 Инструкция по эксплуатации
- Kitfort KT-677 Инструкция по эксплуатации
- Kitfort KT-676 Инструкция по эксплуатации