Siemens 6SL3210-1SE31-8AA0 [251/318] Cabinet design and emc for components blocksize format

Siemens 6SL3210-1SE13-1UA0 [251/318] Cabinet design and emc for components blocksize format
Manual
Manual, 01/2011, 6SL3097-4AC10-0BP2
251
Cabinet design and EMC for components, Blocksize
format
9
9.1 General
The SINAMICS S components are designed in accordance with degree of protection IP20 or
IPXXB acc. to EN 60529 and as open-type devices to UL 50. This ensures protection against
electric shock.
To ensure protection against mechanical stress and climatic conditions too, the components
should only be operated in housing, cabinets or enclosed electrical operating areas that fulfill
at least degree of protection IP54 and, as enclosure type 12, are designed to UL 50.
Prefabricated MOTION-CONNECT cables are recommended.
Note
Functional safety of SINAMICS components
The components must be protected against conductive pollution (e.g. by installing them in a
cabinet with degree of protection IP54B acc. to EN 60529. Provided that conductive pollution
can be prevented at the installation site, the degree of protection for the cabinet can be
decreased accordingly.
Installation in a cabinet with degree of protection IP54B according to EN 60529 is advisable
to ensure the safety functions of Safety Integrated are not compromised.
Low-voltage switchgear and controlgear assemblies
Part 1: Type-tested and partially type-tested low-voltage switchgear and controlgear
assemblies
If the SINAMICS S drive line-up is used for the electrical equipment of machines, the
applicable requirements of EN 60204-1 must also be adhered to.
Safety of machinery
Electrical equipment of machines
Part 1: General requirements
All information for device selection in this section applies to
Operation in a TN system
Operating voltage range from 200 V 1-ph. AC to 440 V 3-ph. AC